Wiring
WARNING
• Donotusetappedwires,extensioncords,orstarburstconnections,astheymaycauseoverheating,electricshock,orre.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminalblock.)Doingsomaycauseelectricshockorre.
• The circuit must be protected with safety devices in accordance with local and national codes, i.e. a circuit breaker.
• Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.
• When carrying out wiring, take care not to pull at the conduit.
• Donotconnectthepowerwiretotheindoorunit.Doingsomaycauseelectricshockorre.
• Do not turn on the circuit breaker until all work is completed.
[Method of Mounting Conduit]
•When connecting indoor units for 3 rooms or more, open knockout holes without deforming the conduit mounting plate.
1) Remove the right side plate (7 screws).
2) Remove the shield cover (2 screws).
3) Pass wires through the conduit and secure them with a lock nut.
Right side plate
Conduit mounting plate
Shield cover
Hooks
A
Lock nut
Knockout holes
Conduit
Conduit
mounting plate
View A
English