Spec Sheet
Daikin North America LLC 5151 San Felipe, Suite 500 Houston, TX 77056
(Daikin’s products are subject to continuous improvements. Daikin reserves the right to modify product design, specifications and information in this data sheet without
notice and without incurring any obligations)
Submittal Revision Date: May 2020 Page 1 of 4
Performance
Cooling (Btu/hr)
Rated (Min/Max)
34,400 (10,200 / 34,400)
Sensible @ AHRI
22,160
Standard Operating Range
50°F – 115°F
Extended Operating Range*
-4°F – 115°F
Rated Cooling Conditions:
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
*With field settings and wind baffle
Heating (Btu/hr)
1:@ 47° Rated (Min/Max)
36,000 (10,200 / 36,000)
2: @ 17° Rated
22,800
3: @ 5°
15,740
Operating Range
5 – 65°F
1: Rated Heating Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
2: Rated Heating Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 17°F DB/15°F WB
3: Heating Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 5°F DB/5°F WB
Submittal Data Sheet
FTX36NVJU / RX36NMVJUA
3-Ton Wall Mounted Heat Pump System
Efficiency
Cooling
Heating
SEER
15.9
HSPF
9.2
EER
9.10
COP
2.78
Electrical
208/60/1
230/60/1
System MCA
19.8
19.8
System MFA
20
20
Compressor RLA
18.25
18.25
Outdoor fan motor FLA
.83
.83
Outdoor fan motor W
123
123
Indoor fan motor FLA
.37
.37
Indoor fan motor W
64
64
MFA: Max. fuse amps MCA: Min. circuit amps (A) FLA: Full load amps (A)
RLA: Rated load amps (A) W: Fan motor rated output (W)
Piping
Liquid (in)
1/4
Gas (in)
5/8
Drain (in)
5/8
Max. Interunit Piping Length (ft)
98.4
Max. Interunit Height Difference (ft)
65.625
Chargeless (ft)
32.8
Additional Charge of Refrigerant (oz/ft)
.32
Indoor Specifications
Airflow Rate (cfm)
Cooling
Heating
H
M
H
M
915
742
960
791
L
SL
L
SL
572
512
629
544
Sound (dBA)
H / M / L / SL
54 / 47 / 40 / 37
53 / 46 / 38 / 35
Dimensions (H × W × D) (in)
13-3/8 × 47-1/4 × 10-3/16
Weight (Lbs)
38
Outdoor Specifications
Compressor
Hermetically Sealed Swing Type
Refrigerant
R-410A
Factory Charge (Lbs)
3.64
Refrigerant Oil
PVE (FVC50K)
Airflow Rate (cfm)
Cooling
Heating
H
2,811
H
2,352
Sound Pressure Level (dBA)
59
Dimensions (H × W × D) (in)
28-15/16 × 34-1/4 × 12-5/8
Weight (Lbs)
133
Job Name:
Tag#
Complete warranty details available from your local dealer or at
www.daikincomfort.com. Warranty registration not required to
receive the 10-Year parts limited warranty for residential or
commercial installations.