Product Manual B

3. Wiring5-2019
290962-0617 (Issue 8) Copyright © 2019 Cummins Inc.
The Reset button is used to select menu options and to clear fault messages.
The status LED is displays the appropriate color for the following conditions.
Green - On solid indicates unit is charging
Amber - On solid indicates Equalizing
Red - On solid indicates a fault condition. The fault number is shown on the digital display.
Optional Battery Temperature Sensor - A connector for an optional battery temperature sensor is located
on the front of the battery charger. When used to monitor battery temperature, the optional battery
temperature sensor is connected from the battery charger to the positive terminal of the battery. A fault
message (fault code 2263) is displayed if the battery temperature is too high (reaches 131 degrees F (55
degrees C)).
Battery Charger Configuration - The RESET button on the control panel (see Figure 21) is used to
configure the battery charger, (More information on Setup menus is included in the Battery Charger
Operator's Manual .)
Battery Voltage and Type - The battery charger must be correctly configured, using the Setup
menus, for the correct battery voltage and type before it is connected to the battery. The battery
voltage can be set for 12 or 24 VDC (default = 12 VDC). The battery type can be set for Lead-Acid,
Gel, or AGM batteries (default = Lead-Acid) .
NOTICE
A factory installed battery charger is set up for the proper DC battery voltage requested on
the production order, with the Lead-Acid battery type selected as the default.
Battery Equalization - Battery equalization is available for lead-acid batteries that are completely
charged, using the Equalize Battery screen in the Setup menus. When batteryequalization is in
process, the LED status indicator turns amber.
No. Description No. Description
1 Reset Button 3 LED Status Indicator
2 Digital Display
FIGURE 21. 15/12-AMP CHARGER CONTROL PANEL