Product Manual B

3. Wiring 5-2019
22 0962-0617 (Issue 8)Copyright © 2019 Cummins Inc.
No. Description No. Description
1 GND 5 Remote Test
2 2 6 Transfer Inhibit
3 B+ 7 Load Shed (Optional)
4 RMT 8 Common
FIGURE 13. TB2 CONNECTIONS FOR TRANSFER INHIBIT
NOTICE
TB1 and TB2 will accept 22 AWG - 12 AWG wire with 3/8 inch (10 mm) strip. Torque to 9 in-lbs.
3.2.6 Retransfer Inhibit Input
To add retransfer inhibit, connect a normally open, dry contact between terminals 7 and 8 of TB2. Closing