Product Manual B

3. Wiring5-2019
130962-0617 (Issue 8) Copyright © 2019 Cummins Inc.
3.1 AC Connections
TABLE 1. TERMINAL LUG CAPACITY FOR COPPER OR ALUMINUM CONDUCTORS
Switch Current Rating Wires per Phase Size Range of Wires
40/70/125 (3-Pole) Source 1 12 AWG-2/0 Cu-Al
40/70/125 (3-Pole) Load &
Neutral
1 14 AWG-2/0 Cu-Al
40 Amp (4-Pole) 1 14 AWG-2/0 Cu-Al
70, 125 Amp (4-Pole) 1 6 AWG-300 MCM Cu-Al
150/225 1 6 AWG-300 MCM Cu-Al
260 1 6 AWG-400 MCM Cu-Al
300/400 2
1
3/0 AWG-250 MCM Cu-Al
3/0 AWG-600 MCM Cu-Al
600 2 250-500 MCM Cu-Al
800/1000 4 250-500 MCM Cu-Al
Perform wiring in the following sequence:
1. Test the operation of the generator set from its own controls.
2. Stop the generator set and remove the negative lead from the cranking battery to prevent starting.
WARNING
Failure to prevent the generator set from starting before wiring procedures are performed
presents a shock hazard that can cause severe personal injury or death. Disconnect
generator set battery (negative (-) terminal first) before proceeding.
3. Connect conductors of sufficient size (see contract drawings) to carry rated current from the line,
load, and generator set directly to the transfer switch terminals, which are marked A, B, and C (A, B,
C, and N on 4-pole switches). A neutral bar with lugs is standard on 3-pole switches. Phase rotation
must be the same on the utility and genset power sources.
4. On 120-volt switches, connect the hot side to the (A) lug and the neutral side to the Neutral lug. On
240-volt single phase switches, connect the two hot lines to the A- and C-lugs and the Neutral line to
the Neutral lug.
5. Connect power cables to the load terminals. Tighten the lugs as indicated in the following table:
TABLE 2. LUG TORQUES
Set Screw Socket Size (Across Flats) Minimum Torque For Proper Operation
3/16 In 80 In-lbs (9 N•m)
1/4 In 200 In-lbs (23 N•m)
5/16 In 275 In-lbs (31 N•m)
3/8 In 375 In-lbs (43 N•m)
1/2 In 500 In-lbs (57 N•m)