6CRP235, 6V Flooded Specifications

AVAILABLE CAPACITY AT
APPLICATION OPERATING TEMPERATURE
60%40%20%0% 80% 100% 120%
140
120
100
80
60
40
20
-20
-40
0
50
60
40
30
20
10
-10
-20
-30
-40
0
Temperature (C)
Temperature (F)
Percent of Available Capacity
Visit our website at www.crownbattery.com
CR-235 Commercial Deep Cycle Battery
©2013 Crown Battery Manufacturing Company
Effect of Battery Temperature on Battery Life
Lead acid batteries are electrochemical storage devices that store and release chemical energy upon
demand in the form of electricity. By virtue of their design lead acid batteries are highly reactive to
temperature – with the rate of chemical reactions that occur within the battery being affected by the
operating temperature where the battery is used. Higher operating temperatures will result in faster
chemical reactions within the battery – delivering improved discharge performance; conversely, cooler
operating temperatures will result in slower internal chemistry. However, higher operating temperatures
also result in shortened battery life as the increased rate of chemical reactions will accelerate the rate of
deterioration of internal components.
Typical battery life is based upon a baseline operating temperature of 80°F / 27°C. Temperature
increases of 15°F / 10°C over the baseline will cause the battery’s rate of internal chemical reactions
to double – something that will reduce battery life due to the accelerated deterioration of internal
components. Please contact Crown Battery to discuss any minimal requirements for battery life when
operating batteries in temperatures greater than 80°F / 27°C.
Form No. TDS-D06235-0213
APPLICATION RECOMMENDATIONS
Specific Gravity Operating Temperature Range Self Discharge Terminal Torque Specifications
Fully charged battery specific gravity
(100% state-of-charge) is 1.275
Fully discharged battery specific gravity
(100% depth-of-discharge) is 1.125
-40°F to 120°F (-4C to 49°C). Flooded
lead acid battery capacities are temperature
sensitive: refer to the temperature / capacity
projection chart below to identify available
capacity at the application operating
temperature. Application Note: Maintain
a state of charge greater than 60 percent
when operating flooded lead acid batteries
at temperatures below 3F (0°C).
Fully charged batteries that are stored
at a temperature of 80°F (27°C) will
self-discharge at a rate of 3.5% per week.
SAE / Automotive Terminal Style:
50 to 70 in-lbs / 6 to 8 Nm
Stainless Threaded Terminal
(Types C, S, Z):
100 to 120 in-lbs / 11 to 14 Nm
Application Note:
Lead acid batteries contain corrosive battery electrolyte and generate highly flammable hydrogen gas. When working near batteries wear protective clothing, gloves, and safety glasses when handling batteries and electrolyte and always
work in a well-ventilated area. Do not over-torque terminals. Over-torque can result in terminal damage, breakage, terminal meltdown or fire.
Crown Battery’s flooded lead acid deep cycle batteries require periodic preventative maintenance and effective charging service to ensure dependable service life. Customers can find Crown Battery’s recommended best practices for deep cycle battery care,
maintenance and application at
www.crownbattery.com/en/wp-content/uploads/2012/10/SafetyFirst-DeepCycle2.pdf
or by contacting Crown Battery to request this information.
1445 Majestic Drive | P.O. Box 990
Fremont, OH 43420-0990 USA
+1.419.334.7181 | Fax +1.419.334.7124
www.crownbattery.com
sales@crownbattery.com
TYPICAL BATTERY CYCLE LIFE / DEPTH OF DISCHARGE
Battery
Model
100% DOD
Cycles
End-Cycle
Voltage
50% DOD
Cycles
End-Cycle
Voltage
40% DOD
Cycles
End-Cycle
Voltage
20% DOD
Cycles
End-Cycle
Voltage
CR-235 500 1.75 VPC 1200 1.94 VPC 1500 1.97 VPC 3000 2.05 VPC
The battery life references presented above are estimations based upon stationary life cycle testing conducted at Crown Battery
Manufacturing’s Testing Center in Fremont, Ohio USA. The data references are nominal and should not be construed as maximum or
minimum values for specifications or for final design. Data for this product type may vary from that shown herein, and Crown Battery
makes no warranties – expressed or implied – based upon the data shown above.
The data shown are nominal and should not be construed as maximum or minimum values for specification or final design.
Data for this product type may vary from that shown herein.
10.25 (260) 7.06 (179)
9.88 (251
)
10.94 (278)