User Manual

Crestron CHV-TSTATRF infiNET™ Thermostat
NOTE: While in SETUP Mode, a period of one minute with no button activity will
cause the CHV-TSTATRF to revert to standard operation.
The following table shows the available Setup Parameter/Functions.
SETUP Mode Parameters/Functions
PARAMETER/
FUNCTION
MNEMONIC VALID VALUES
DEFAULT
VALUE
Temperature Scale FC F or C F
Half-degree Setpoint
1
Hd
Enabled (Y) or Disabled (no)
(valid for Celsius only)
Y (for
Celsius
only)
Backlight Timeout bL 1 – 4 seconds or disabled (--) --
Heat/Cool Type HC
Heat/Cool (HC), Heatpump (HP),
Dual-Fuel Heatpump (dF)
HC
Temperature Offset
2
to
-9 to +9 (for Fahrenheit) or
-5 to +5 (for Celsius)
0
Wide-range Cool Mode
(Extended Cool)
EC Enabled (Y) or Disabled (no) no
Heat Anticipator
3
HA 1 - 6 3
Cool Anticipator
3
CA 1 - 6 3
Heatpump Balance
Point (Heatpump and
Dual-Fuel Heatpump
systems only)
Hb
16 to 90 (for Fahrenheit) or
-9 to 32 (for Celsius) or
Disabled (--)
--
Aux-Heat Balance
Point (Heatpump type
systems only)
Ab
16 to 90 (for Fahrenheit) or
-9 to 32 (for Celsius) or
Disabled (--)
--
Interstage Differential
(Heatpump systems
only)
dF
05 to 80 (tenths of a degree
Fahrenheit, adjustable in 5 tenths
degree increments or
05 to 45 (tenths of a degree
Celsius, adjustable in 5 tenths
degree increments
20 (F) or
1 (C)
Run Fan During Heat
Calls
HF Enabled (Y) or Disabled (no) no
Changeover Outputs
4
co Enabled (Y) or Disabled (no) no
Power Source
5
Po
24V always available (24) or “steal
power” (SP)
24
Check Firmware
Version
6
rE
Firmware version is in xxx.yy.zzzz
format.
—“ can also be displayed
--
infiNET ID (MNET ID)
7
id 01, 03 - FE 01
infiNET RF Channel Ch
11-26 for fixed-channel operation,
“Au” for auto or “0” for disabled
(battery save mode)
26
infiNET Sleep Time SL Short (S) or Long (L) L
Start infiNET Acquire Ac
Not started (--)
In progress (flashing --)
Finished, found GW (00)
Finished, could not find GW (E#,
where # represents an error code)
N/A
(Continued on following page)
Operations & Installation Guide – DOC. 6490 infiNET™ Thermostat: CHV-TSTATRF 19