Cut the opening in the ceiling tile at least 0.25 in. larger than the outer diameter of the
sprinkler head or trim ring/escutcheon (whichever is larger). This enables the tile to fall
from the ceiling grid without becoming entangled with the sprinkler or interfering with its
operation.
or
Use a 0.030 in. thick Signature style panel backed by a mineral ber ceiling panel at
each sprinkler penetration. This holds the tile in place and keeps it insulated, preventing
it from interfering with sprinkler operation.
Never use a restraining-type trim ring/escutcheon at a sprinkler penetration without an
appropriately sized tile opening or mineral ber ceiling panel backer.
Drop-out Ceiling Panels Beneath Sprinklers
All of Ceilume’s 0.013 in. thick Feather-Light ceiling panels and two 0.030 in. thick Signature styles
(Oxford and Fleur-de-lis) are suitable for installation beneath re sprinklers in Light Hazard and
Ordinary Hazard Group I occupancies. When exposed to heat from a developing re, these drop-out
ceiling panels soften, distort, and fall from the ceiling grid. Heat from the growing re activates the
sprinkler which, unimpeded by the panels, controls or extinguishes the re.
All Feather-Light panels, Oxford, and Fleur-de-lis, are suitable for use beneath Standard Response
(SR) sprinkler systems rated with an activation temperature of 165°F or above, where allowed by
local safety authorities. See IAPMO ER-310.
Additionally, all Feather-Light styles are suitable for use beneath Quick Response (QR) and Standard
Response (SR) sprinkler systems rated with an activation temperature of 155°F or above, where
allowed by local safety authorities. See IAPMO ER-310.
Grid tape/strips have not been tested for use in drop-out installations, though there is no mechanical
reason that their use, when installed properly, would aect the panels’ ability to drop from your grid.
Drop-out installations must use grid that provides up to a 3/8 in. horizontal edge support on
all four sides and has a loading bearing capacity of no less than 16 lbs. per lineal foot, OR be
rated as Heavy Duty Grid per ASTM C635.
Consult with your local building and re ocials to make sure that your intended use will
conform with the appropriate local codes.