Questions About ENT
1. WHAT ABOUT STUB UPS OF ENT?
First, read your job specifications for any particular
requirements. Then refer to Carlon suggested stub up
methods shown in this section.
2. WHAT FITTINGS DO I USE WHEN INSTALLING
1
/2 INCH THROUGH 1 INCH ENT IN CONCRETE?
Carlon offers a complete line of one piece quick connect
fittings. These fittings are suitable for damp locations and
are concrete-tight when used with Carlon ENT and a flat
sealing washer on the box connection end. Remember,
when using Carlon one piece quick connect fittings, NO
TAPING IS NEEDED.
3. WHAT FITTINGS DO I USE WHEN INSTALLING
LARGER CONDUIT 1
1
/4 INCH THROUGH 2 INCH
ENT TERMINATIONS?
All Schedule 40 fittings are compatible with ENT using
Carlon Blue ENT cement.
4. WHAT DO I USE FOR STUB DOWNS OF ENT?
For stub downs of ENT when installed in a deck, fabricate
a stub down (see illustration 2-1 in this section.)
REFERENCE NEC SECTION 362.10:
(7) For wet locations indoors as permitted in this section or
in a concrete slab on or below grade, with fittings listed
for the purpose.
This Section (7) permits the use of ENT in wet locations
providing fittings identified for this purpose are used. The
identified fittings are solvent cemented (glue-on) fittings
of the type used for Schedule 40 rigid PVC conduit.
Fabricated Stub Down