User manual
49
EN
“UEX-PLUS” +030220621 - rel. 1.1 - 30.05.2008
installeruserservice
13.6 CONTROLLING THE BOARD VIA NETWORK
The variables shown in the list are only some of the total variables
available.
DO NOT CONFIGURE VA-RIABLES THAT ARE NOT SHOWN IN THE TABLE,
OTHERWISE THE OPERATION OF THE HUMIDIFIER MAY BE AFFECTED.
“A” read (R)/
write (W)
analogue variables* (Modbus®: REGISTERS)
CAREL - Modbus®
1 R room probe/external regulator: demand
2 R/W room probe/external regulator: minimum (calibration)
3 R/W room probe/external regulator: maximum (calibration)
4 R/W room probe/external regulator: o set (calibration)
5 R current production (kg/h)
6 R limit probe reading
7 R/W limit probe: minimum (calibration)
8 R/W limit probe: maximum (calibration)
9 R/W limit probe: o set (calibration)
10 R nominal production (kg/h)
11 R total actual current (a)
12 R cylinder 1: actual current (a)
13 R cylinder 2: actual current (a)
14 R/W maximum production (p0)
15 R/W %rh set point
16 R/W %rh di erential
17 R/W limit probe set point
18 R/W limit di erential
19 R/W temperature set point
20 R/W temperature di erential
21 R/W dehumidi cation o set
22 R/W dehumidi cation di erential
23 R/W room probe: low humidity warning threshold
24 R/W room probe: high humidity warning threshold
25 R/W limit probe: high humidity warning threshold