LIQUID CYLINDER CYLINDER LIQUID OPERATING MANUAL • Dura-Cyl 160MP/HP • Cryo-Cyl 80HP • Cryo-Cyl 120, 180, 230LP • Dura-Cyl 180MP/HP • Dura-Cyl MCR 180MP/HP • Dura-Cyl 200MP/HP • Dura-Cyl MCR 230LMP/HP • Dura-Cyl 230MP/HP • Dura-Cyl MCR 160MP/HP • Dura-Cyl 265MP/HP • Dura-Cyl MCR 200MP/HP • Dura-Cyl MCR 265MP/HP
CHART- LIQUID CYLINDER USERS MANUAL NOTES REVISION LOG LETTER DATE DESCRIPTION G 9/01/92 New release with PLC and Dura III Models H 5/01/94 New release with Dura-Cyl and Cryo-Cyl Models I 10/01/95 Added Cryo-Cyl 80HP, Cryo-Cyl 265 MP & HP; Deleted Dura-Mite J 3/01/96 Add Dura-Cyl MCR, Delete Cryo-Cyl MP & HP Model (except 80 HP) K 5/01/98 Addition of new Dura-Cyl HP LCCM module L 10/07/08 Updated exploded views of Dura-Cyl and Cryo-Cyl tanks Any comments or suggestions related to this
PREFACE 1 This edition of the Chart Liquid Cylinder Users Manual documents Release I and all subsequent releases of the Chart Inc. Dura-Series cryogenic liquid cylinders users manual. This edition has information regarding both Chart Dura-Cyl and Cryo-Cyl cryogenic liquid cylinders.
2 TABLE OF CONTENTS 1 Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2 Contents 3 Safety 11 Operation of Dura-Cyl MCR-HP General Filling Parts Identification Operation Pressure Liquid CO2 Withdrawal Gas withdrawal Service and Maintenance ...........................3 ...........................4-5 4 Safe Handling . . . . . . . . . . . . . . . . . . . . . 5 - 7 5 Introduction . . . . . . . . . . . . . . . . . . . . . .
SAFETY Chart has conducted a rigid test program for liquid cylinders, both internally and through an independent testing laboratory, to verify the safety of Chart equipment. Chart cylinders are safely designed with the following features: 3 Keep all organic materials and other flammable substances away from possible contact with oxygen; particularly oil, grease, kerosene, cloth, wood, paint, tar, coal dust, and dirt which may contain oil or grease.
4 SAFE HANDLING This section describes and illustrates proper cylinder handling procedures. Major considerations for liquid cylinder handling are summarized as follows: Caution Only use replacement equipment which is compatible with liquid oxygen and has been cleaned for oxygen use. Do not use regulators, fittings, hoses, etc., which have been previously used in compressed air service. Similarly, do not use oxygen equipment for compressed air.
SAFE HANDLING Preferred Handling Procedures 4 This method is used when frequent and short distance moves of a liquid cylinder are required. Before utilizing this method of transportation, make sure the area over which the liquid cylinder is to be moved is flat and smooth. Figure B illustrates the preferred cylinder handling procedures. It shows the proper way to approach a cylinder when using a pneumatic-tired hand truck.
4 SAFE HANDLING Use Straps Do Not Use Chains Use A Handtruck And A Power Liftgate Figure C Transporting Procedures The Dura-Cyl/Cryo-Cyl Series liquid cylinders are designed to withstand the normal handling associated with transportation by truck. Do Not use chains. Chain tie downs will scratch the finish and could crush or dent the vacuum jacket. Figures C also shows the proper method of unloading a cylinder from a truck.
INTRODUCTION 5 Transport Canada for the transporting of liquid nitrogen, oxygen, and argon. They are authorized by Transport Canada for the transporting of carbon dioxide and nitrous oxide with an exemption. General The Chart Inc. Dura-Series cryogenic liquid cylinders and the Cryo-Cyl Series cryogenic liquid cylinders (figure D) are double walled, vacuum and multi-layer insulated cylinders designed for the transportation and storage of liquefied gases.
5 INTRODUCTION Figure D 0ROTECTION 2ING over pressurization by a bursting disc that acts as a secondary relief device. These devices meet the requirements of CGA Pamphlet S-1.1 “Pressure Relief Device Standard — Part 1 — Cylinders For Compressed Gases.” ,IQUID ,EVEL 'AUGE (ANDLING 3LOT 3AFETY 2ELIEF $EVICES (ANDLING 0OST 0LUMBING #ONTROLS A back control regulator is used to build and maintain operator pressure while assuring a no-loss operation under normal usage during gas withdrawal service.
INTRODUCTION 5 Cylinder Identification gauge protector color is an easy way to determine the pressure rating of a liquid cylinder. There are twenty-four Dura-Cyl/Cryo-Cyl Series liquid cylinders described in this manual. They vary in size, capacity, pressure, gas service and various plumbing features. It is important that these liquid cylinders can be easily identified. The data plate (Figure G) is permanently attached to the handling post of the liquid cylinder.
5 INTRODUCTION Responsibilities of Distributor and Fillers of Liquid Cylinders 3. Dispense only to knowledgeable users. The filler must determine that the user is knowledgeable about the general characteristics of the product and the proper safety precautions for its use. Do not allow customers to fill their own cylinders. Chart is stating below the responsibilities of the filler of any cryogenic liquid cylinder: 1. The cylinder must be in a safe condition. 4. Dispose of cylinders properly.
FEATURES General 6 The performance of the vaporizer to convert cold liquid into gas is shown by how the outlet gas temperature drops as the gas flow rate increases. The Chart cryogenic liquid cylinders were designed to furnish a convenient, reliable, and economical method for the transportation and delivery of liquefied gases.
6 FEATURES CO2 W/P.B.@ 300 PSIG 100 SCFH 50 200 SCFH 40 300 SCFH 350 300 SCFH 500 SCFH 300 (230 lb. 200 30 Pressure (PSIG) TEMPERATURE OF EXITING GAS (NITROGEN) -˚F 60 400 SCFH 20 10 0 -10 N2O W/P.B.@ 300 PSIG 350 200 SCFH 500 SCFH 800 S CFH -20 200 20 40 60 80 100 SATURATION PRESSURE (PSIG) 2 hr. 1 hr. Figure J-1 Figure K Figure K illustrates continuous flow rates for CO2 and N2O when a pressure-build coil is used and adequate external vaporization is present (Dura-Cyl HP only).
FEATURES 6 CHART DURA-CYL & DURA CYL MCR SPECIFICATIONS 160 MP 160 HP 180 MP 180 HP 200 MP 20 (50.8) 20 (50.8) 20 (50.8) 20 (50.8) 20 (50.8) 59.6 (151.3) 59.6 (151.3) 63.5 (161.3) 63.5 (161.3) 65.8 (167.1) Empty Weight - lbs. ( kg.) ¨ Fill Weight 250 (113.4) 280 (127.0) 260 (117.8) 300 (136.1) 280 (126.9) See pg. 35 See pg. 47 See pg. 35 See pg. 47 See pg. 35 Design Specification (DOT/CTC) 4L 4L 4L 4L 4L DOT Service Pressure psig (BAR) 200 (13.8) 292 (20.1) 200 (13.
6 FEATURES CHART DURA-CYL & DURA-CYL MCR SPECIFICATIONS 200HP 230MP 230HP 265MP 265HP Physical Characteristics Diameter - inches. (cm.) ¬ Height - inches (cm.) 20 (50.8) 26 (66.0) 26 (66.0) 26 (66.0) 26 (66.0) 65.8 (167.1) 54.8 (139.2) 54.8 (139.2) 59.8 (151.9) 59.8 (151.9) Empty Weight - lbs. ( kg.) ¨ Fill Weight 320 (145.1) 324 (147) 375 (170) 353 (160) 430 (195) See pg. 47 See pg. 35 See pg. 47 See pg. 35 See pg.
FEATURES 6 CHART CRYO-CYL SPECIFICATIONS Physical Characteristics Diameter - inches. (cm.) ¬ Height - inches (cm.) Empty Weight - lbs. ( kg.) ¨ Fill Weight Design Specification (DOT/CTC) 80 HP 120 LP 180LP 230 LP 20 (50.8) 20 (50.8) 20 (50.8) 26 (66.0) 39.5 (100.3) 51 (129.5) 63.5 (161.3) 54.8 (139.2) 165 (74.8) 165 (74.8) 210 (95.2) 290 (131.5) See pg. 52 See pg. 24 See pg. 24 See pg. 24 4L 4L 4L 4L DOT Service Pressure psig (BAR) 292 (20.1) 100 (6.9) 100 (6.9) 100 (6.
THEORY OF OPERATION 7 General Liquid cylinder operation is done completely with the control valves located on the top of the tank. The valves are labeled and color coded for easy identification: Fill/Liquid Valve – blue; Gas Use Valve – green; Vent Valve – silver; Pressure Building Valve – green. The various liquid cylinders of the Dura-Cyl/Cryo-Cyl Series have the same general operating characteristics.
THEORY OF OPERATION Filling Procedures 7 The liquid cylinder should be visually inspected before every fill for possible damage, cleanliness and suitability for its intended gas service. If damage is detected (e.g. serious dents, loose fittings, etc.) remove it from service and repair the unit as soon as possible. The following recommendations should be used to optimize liquid cylinder filling: * Keep the transfer lines as short as possible.
7 THEORY OF OPERATION Economizer Closed Pump Transfer The pump transfer method lowers the product losses associated with filling. Liquid may be pumped into the cylinder so that venting is not necessary. The vent valve on the liquid cylinder has a spray header that will splash the incoming cold liquid onto the somewhat warmer gas in the tank. The cold liquid will actually collapse the vessel pressure while being sprayed into the warmer gas.
THEORY OF OPERATION Pressure Builder 7 fer line. Normal liquid withdrawal operations are performed at lower pressure (approximately 22 psig) to reduce flash-off losses and splashing. For this reason, the pressure building valve is customarily closed during liquid withdrawals. Transfer of liquid at higher pressures can lead to excessive splashing of the cryogenic liquid which could result in burns to the operator and/or nearby personnel.
8 OPERATION OF CRYO-CYL 120 / 180 / 230 LP General The Cryo-Cyl 120/180/230 LP cryogenic liquid cylinders have been designed to transport, store and dispense liquid oxygen, nitrogen or argon in their liquid states only. Liquid product is generally used at ambient or very low pressures. The Cryo-Cyl LP has a working pressure of 22 psig ( 1.5 BAR )to allow for transfer into vented cryogenic dewars or equipment. The pressure is maintained in the liquid cylinder through its normal heat leak of the cylinder.
OPERATION OF CRYO-CYL 120 / 180 / 230 LP Part No 11769595 1110072 1110112 Qty 1 2 2 11905956 11692575 2015169 11884770 1911622 1211102 2300094 2 1 1 1 1 1 1 10 11 12 13 14 15 15a 15b 15c 15d 16 17 18 19 20 5410486 2910501 2910601 1210752 10658826 10658826 10582809 1011432 8512163 1011442 11732629 11732637 2300059 3911217 3811609 1 3 3 1 1 – 1 1 1 1 1 1 2 1 1 21 22 23 3811619 3811589 12967551 1 1 1 Item 1 2 2 3 4 5 6 7 8 9 Spares * 1 1 1 1 1 1 1 1 8 Description Globe Valve – 3/8" FPT (Liquid)
8 OPERATION OF CRYO-CYL 120 /180 / 230 LP Filling Procedures 6. When the scale reads the calculated total filling weight, turn off the liquid valve (Item 1) on the cylinder. Close the vent valve (Item 3). The Cryo-Cyl LP is equipped with a Liquid and Vent valve that are used for filling. Use a pressure transfer fill as the proper filling method for this style of cylinder. The delivery tank pressure should be as low as practical for the transfer to be efficient. Use the following procedure. 7.
OPERATION OF CRYO-CYL 120 /180 / 230 LP 8 4. Open the liquid valve (Item 1) on the liquid cylinder. This valve can be adjusted to obtain the proper liquid flow rate. 1. Connect the transfer hose to the liquid valve (Item 1) of the cylinder. 2. Connect or place the other end of the hose onto the inlet of the cryogenic equipment that will receive liquid. Atmospheric dewars are filled with a phase separator mounted to the open end of the hose. 5.
9 OPERATION OF DURA-CYL MCR 160 / 180 / 200 / 230 / 265MP General This section of the manual deals with the Dura-Cyl MCR 160 MP, Dura-Cyl MCR 180 MP, Dura-Cyl MCR 200 MP, Dura-Cyl MCR 230 MP and Dura-Cyl MCR 265 MP. They will be referred to in this section as liquid cylinders. These liquid cylinder models are functionally the same and only vary in capacity. They are designed to transport, store and delivery liquid oxygen, nitrogen or argon as a cryogenic liquid or gas.
OPERATION OF DURA-CYL MCR 160 / 180 / 200 / 230 / 265MP 9 Item Part No Qty Spares * Description 50 2015179 1 1 Pressure Gauge (0-400 psig/27.6 BAR) 51 1910882 1 1 Safety Rupture Disc – 1/4" MPT (400 psig/27.6 BAR) 53 11884796 1 1 Pressure Relief Valve (230 psig/15.
9 OPERATION OF DURA-CYL MCR 160 / 180 / 200 / 230 / 265MP 4. To determine the total filling weight add the tare weight of the cylinder, the hose weight and the proper filling weight from the table (pg 29). The table indicates the product across the top and the relief valve pressure down the side. Connect the two columns to find the proper weight. Example: Dura-Cyl MCR 160 MP for Oxygen at 230 psi has a product weight of 379 pounds.
OPERATION OF DURA-CYL MCR 160 / 180 / 200 / 230 / 265MP Gas Withdrawal 9 CAUTION: The liquid and vent valves on an empty liquid cylinder should always be kept closed to protect the inner vessel and plumbing from being contaminated. The liquid cylinder will deliver gas at various flow rates and temperatures (as shown in Table J1, page 13) for different applications. The flow rate is controlled by the equipment that is being supplied gas from the liquid cylinder.
9 OPERATION OF DURA-CYL MCR 160 / 180 / 200 / 230 / 265MP S TA N D A R D F I L L I N G W E I G H T TA B L E RELIEF VALVE ARGON Setting (PSIG) LBS SCF DURA-CYL 160 MP (235 psig max. RV) Gross Cap = 176 Liters 0 to 45 514 4971 46 to 75 503 4864 76 to 105 491 4748 106 to 170 472 4564 **171 to 230 460 4448 231 to 235 445 4303 DURA-CYL 180 MP (235 psig max.
OPERATION OF DURA-CYL MCR 160 / 180 / 200 / 230 / 265MP 9 M E T R I C F I L L I N G W E I G H T TA B L E RELIEF VALVE Setting (BAR) DURA-CYL 160 MP (16 bar max. RV) Gross Cap = 176 Liters 0 to 3.1 3.2 to 5.2 5.3 to 7.2 7.3 to 11.7 **11.8 to 15.9 16.0 to 20.3 DURA-CYL 180 MP (16 bar max. RV) Gross Cap = 196 Liters 0 to 3.1 3.2 to 5.2 5.3 to 7.2 7.3 to 11.7 **11.8 to 15.9 16.0 to 20.3 DURA-CYL 200 MP (16 bar max. RV) Gross Cap = 209 Liters 0 to 3.1 3.2 to 5.2 5.3 to 7.2 7.3 to 11.7 **11.8 to 15.9 16.
10 OPERATION OF DURA-CYL 160 /180 / 200/ 230 / 265 MP General This section of the manual deals with the Dura-Cyl MP model liquid cylinder. The Dura-Cyl MP liquid cylinder has the unique feature of a combination pressure building and economizer regulator (known as the “LCCM- liquid cylinder control manual”). The LCCM eliminates the need to adjust two regulators when the operating pressure needs to be changed.
OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 MP Item 90 91 92 93 94 95 96 97 98 99 101 102 103 104 105 106 106 107 Part No. 11534542 2911071 11884796 1910882 2015179 11077134 10951539 2910601 2910501 12967551 10534583 – 11906043 11905956 11905964 4016639 4016649 1110072 Qty. 4 4 1 1 1 1 1 3 3 1 1 1 1 1 1 2 2 2 Spares * 4 4 1 1 1 1 1 107 108 108 1110112 4010022 4010012 2 1 1 1 1 1 1 1 10 Description Bolt SS # 10-32 x 2.5" Washer Split Lock #10 SS Pressure Relief Valve – 1/4" MPT (230 psi/ 15.
10 OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 MP Filling Procedures 2. Place the cylinder on the filling scale. Record the weight. Compare this weight to the registered tare weight on the data plate. The difference is the weight of the residual gas. The Dura-Cyl MP is regulated by the Department of Transportation (US DOT/Transport Canada) for transporting liquid oxygen, nitrogen or argon. The filling of this liquid cylinder must be done by product weight.
OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 MP Operating Pressure 10 To supply gaseous product follow this step by step procedure: The liquid cylinder will automatically maintain a normal operating pressure between the pressure building portion of the LCCM (125 psi/ 8.6 BAR) and the economizer portion of the LCCM (140 psi/ 9.7 BAR). The operating pressure can be set up or down by simply adjusting the LCCM control knob (item B) while watching the pressure gauge.
10 OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 MP S TA N D A R D F I L L I N G W E I G H T TA B L E RELIEF VALVE Setting (PSIG) DURA-CYL 160 MP (235 psig max. RV) Gross Cap = 176 Liters 0 to 45 46 to 75 76 to 105 106 to 170 **171 to 230 231 to 235 DURA-CYL 180 MP (235 psig max. RV) Gross Cap = 196 Liters 0 to 45 46 to 75 76 to 105 106 to 170 **171 to 230 231 to 235 DURA-CYL 200 MP (235 psig max.
OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 MP 10 M E T R I C F I L L I N G W E I G H T TA B L E RELIEF VALVE Setting (BAR) DURA-CYL 160 MP (16 bar max. RV) Gross Cap = 176 Liters 0 to 3.1 3.2 to 5.2 5.3 to 7.2 7.3 to 11.7 **11.8 to 15.9 16.0 to 20.3 DURA-CYL 180 MP (16 bar max. RV) Gross Cap = 196 Liters 0 to 3.1 3.2 to 5.2 5.3 to 7.2 7.3 to 11.7 **11.8 to 15.9 16.0 to 20.3 DURA-CYL 200 MP (16 bar max. RV) Gross Cap = 209 Liters 0 to 3.1 3.2 to 5.2 5.3 to 7.2 7.3 to 11.7 **11.8 to 15.9 16.0 to 20.
11 OPERATION OF DURA-CYL MCR160 / 180 / 200 / 230 / 265 HP General exemption Chart has received from Transport Canada. The common applications for these high pressure liquid cylinder is to provide gas at pressures around 300 psi or deliver liquid CO2. The high pressure liquid cylinder will build and maintain pressure at the pressure control regulator setting of 300 psi (20.7 bar). If the pressure exceeds 325 psi (22.
OPERATION OF DURA-CYL MCR 160 /180 / 200 / 230 / 265 HP Qty Spares * 11 Item Part 120 2010064 1 1 Pressure Gauge (600 psig/ 41.4 BAR) 121 1911632 1 1 Safety Rupture Disc (600 psig/ 41.4 BAR) 122 11884788 1 1 Pressure Relief Valve – 1/4" MPT (350 psi/ 24.
11 OPERATION OF DURA-CYL MCR 160 /180 / 200 / 230 / 265 HP Filling Procedures 3. Connect the transfer hose to the fill valve (Item 127). Record the new weight. The difference between this weight and the initial weight is the weight of the transfer hose. The high pressure liquid cylinder is regulated by the DOT/Transportation Canada for transporting liquid oxygen, nitrogen, argon, carbon dioxide, or nitrous oxide. The filling of these high pressure liquid cylinders must be done by product weight.
OPERATION OF DURA-CYL MCR 160 /180 / 200 / 230 / 265 HP 11 Operating Pressure Gas Withdrawal The liquid cylinder will automatically maintain a normal operating pressure between the pressure building portion of the regulator (300 psi- 20.7 bar) and the economizer portion of the regulator (325 psi- 22.4 bar). The operating pressure can be set up or down by simply adjusting the regulator while watching the pressure gauge. The adjustment range of the regulators is between 150 and 350 psi (10.6 & 24.1 bar).
11 OPERATION OF DURA-CYL MCR 160 /180 / 200 / 230 / 265 HP STANDARD FILLING WEIGHT TABLE RELIEF VALVE ARGON NITROGEN Setting (PSIG) LBS SCF LBS SCF DURA-CYL MCR 160 HP (350 psig max. RV) Gross Cap = 176 Liters 0 to 45 514 4971 294 4058 46 to 75 503 4865 286 3948 76 to 105 491 4748 278 3837 106 to 170 472 4565 271 3741 171 to 230 460 4448 267 3685 231 to 295 445 4304 263 3630 **296 to 350 437 4226 251 3465 DURA-CYL MCR 180 HP (350 psig max.
11 OPERATION OF DURA-CYL MCR 160 /180 / 200 / 230 / 265 HP METRIC FILLING WEIGHT TABLE RELIEF VALVE ARGON NITROGEN Setting (BAR) KG NM3 KG NM3 DURA-CYL MCR 160 HP (24 bar max. RV) Gross Cap = 176 Liters 0 to 3.1 233 130 133 106 3.2 to 5.2 228 128 130 104 5.3 to 7.2 222 124 126 101 7.3 to 11.7 214 120 123 98 11.8 to 15.9 209 117 121 97 16.0 to 20.3 202 113 119 95 **20.4 to 24.8 198 111 114 91 DURA-CYL MCR 180 HP (24 bar max. RV) Gross Cap = 196 Liter 0 to 3.1 260 146 148 3.2 to 5.2 254 142 145 5.3 to 7.
12 OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 HP General Transportation (Transport Canada). The common applications for these high pressure liquid cylinders are to provide gas at pressures up to 350 psi (24.1 BAR) or deliver liquid CO2. The high pressure liquid cylinder will build and maintain pressure with a pressure control manifold. The pressure building portion of the regulator has a setting of 300 psi (20.7 bar). If the pressure exceeds 325 psi (22.
OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 HP Item 160 161 162 163 164 165 166 167 168 169 171 172 173 174 175 176 176 177 177 178 178 179 179 180 181 182 183 184 185 186 Part No. 11534542 2911071 11884788 1911632 2010064 11077142 10951539 2910601 2910501 12967551 10534567 — 11906043 11905956 11905964 4016639 4016649 1110072 1110112 4010022 4010012 4010629 4010512 3811599 3811609 3811589 11732629 11732637 2300059 3911217 Qty.
12 OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 HP Operating Pressure Filling can be accomplished by either pressure transfer or pump fill. The following procedure should be used for pressure transfer fillings, refer to the illustration on page 43: The liquid cylinder will automatically maintain a normal operating pressure between the pressure building portion of the regulator (300 psi –20.7 bar) and the economizer portion of the regulator (325 psi –22.4 bar).
OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 HP 12 CAUTION: The liquid and vent valves on high pressure liquid cylinders should always be kept closed to protect the inner vessel and plumbing from being contaminated. CAUTION: The liquid and vent valves on an empty liquid cylinder should always be kept closed to protect the inner vessel and plumbing from being contaminated.
12 OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 HP STANDARD FILLING WEIGHT TABLE RELIEF VALVE Setting (PSIG) DURA-CYL 160 HP (350 psig max. RV) 0 to 45 46 to 75 76 to 105 106 to 170 171 to 230 231 to 295 **296 to 350 DURA-CYL 180 HP (350 psig max.
12 OPERATION OF DURA-CYL 160 / 180 / 200 / 230 / 265 HP METRIC FILLING WEIGHT TABLE RELIEF VALVE ARGON NITROGEN Setting (BAR) KG NM3 KG NM3 DURA-CYL 160 HP (24 bar max. RV) Gross Cap = 176 Liters 0 to 3.1 233 130 133 106 3.2 to 5.2 228 128 130 104 5.3 to 7.2 222 124 126 101 7.3 to 11.7 214 120 123 98 11.8 to 15.9 209 117 121 97 16.0 to 20.3 202 113 119 95 **20.4 to 24.8 198 111 114 91 DURA-CYL 180 HP (24 bar max. RV) Gross Cap = 196 Liter 0 to 3.1 260 146 148 3.2 to 5.2 254 142 145 5.3 to 7.
13 OPERATION OF CRYO-CYL 80 HP General This section of the manual deals with the Cryo-Cyl 80HP liquid cylinder. The Cryo-Cyl 80 HP is designed to transport and store liquid oxygen, nitrogen, argon, carbon dioxide or nitrous oxide and provide it as a gas. It is a smaller version of the liquid cylinder that is designed to supply gas at lower flow rates than the regular liquid cylinders. The Cryo-Cyl 80 HP can provide gas at pressures up to 350 psi (24.1 BAR).
OPERATION OF CRYO-CYL 80 HP Part No. 2010064 1911632 Qty. 1 1 Spares * 1 1 1 13 Description Pressure Gauge (0-600 psig/ 41.4 BAR) Safety Rupture Disc (600 psi/ 41.4 BAR) Pressure Relief Valve – 1/4" MPT (350 psi/24.
13 OPERATION OF CRYO-CYL 80 HP 6. When the scale reads the calculated total filling weight turn off the liquid valve (Item 197) on the cylinder. Close the vent valve (Item 198). Filling Procedures The Cryo-Cyl 80 HP is regulated by the Department of Transportation (US DOT) for transporting liquid oxygen, nitrogen, argon, CO2 or N2O. The filling of these liquid cylinders must be done by product weight.
OPERATION OF CRYO-CYL 80 HP 13 CAUTION: The liquid and vent valves on an empty liquid cylinder should always be kept closed to protect the inner vessel and plumbing from being contaminated. 5. Open the gas use valve (Item 198). 6. Adjust the final line regulator for the proper delivery pressure. Service and Maintenance 7. When the gas delivery is completed, close all liquid cylinder valves. Refer to section 15 and 16 of this manual to trouble shoot problems and service these liquid cylinders.
14 DURA-CYL / CRYO-CYL BASE DESIGN The Dura-Cyl/Cryo-Cyl Series liquid cylinder has various base designs that help the cylinder stand straight and make handling easier. Refer to the Base Identification table on page 48 to match the Dura-Cyl/ Cryo-Cyl Series model with it's base design. Dura-Cyl / Cryo-Cyl Footring Footring Design: The Dura- Cyl/Cryo-Cyl liquid cylinder has a footring design that employs a Belleville washer to absorb the shock associated with normal handling.
DURA-CYL / CRYO-CYL BASE DESIGN 14 HP 65 R2 MP MC 65 YL -C R2 RA HP MC 30 DU YL -C R2 MP RA MC 30 DU YL R2 -C P RA MC 0H L 0 DU Y R2 -C MP R A L MC 00 DU Y -C R2 RA MC HP DU 80 YL 1 -C R P RA MC 0M DU YL 18 -C CR RA HP LM 60 DU 1 Y R -C P RA L MC 0M DU Y 16 -C R RA MC DU YL -C HP 5 RA 26 DU YL MP -C 5 RA 26 DU YL P -C 0H RA 23 DU YL MP -C 0 RA 23 DU YL HP -C 0 RA 20 DU YL P -C 0M RA 0 2 DU YL P -C 0H RA 18 DU YL -C MP 0 RA 18 DU YL -C HP 0 RA 16 DU YL MP -C 0 RA 16 DU YL P -C 0L RA 23 DU YL LP -C 80 YO 1
15 TROUBLESHOOTING The troubleshooting section of this manual deals with the normal operating conditions and the problems that may occur with the Dura-Cyl/Cryo-Cyl Series liquid cylinders. The troubleshooting guide assumes that the tank is in its normal operating environment having a cooled down inner vessel and a reasonable vacuum. Before troubleshooting an operational problem, the liquid cylinder should be examined for vacuum. 7.
TROUBLESHOOTING Problem Liquid cylinder builds excessive pressure or builds pressure too fast. Problem Cause 15 Corrective Action Low usage. If daily gas usage is under 100 SCF (2.8 NM3), the cylinder will build pressure. In liquid service, the cylinder should be equipped with low pressure relief valve and regulator. Normal pressure rise should not be more than 50 psi (3.4 BAR)per day. Cylinder is over filled.
15 TROUBLESHOOTING Problem Frost occurs on head or knuckle. Problem Cause Corrective Action Residual frost remains from This is normal. Ice may remain for days after a fill or heavy use. last fill or recent product use. Check for gas escaping from under sight gauge. Refer to Section 16, page 62, for repair. Sight gauge is leaking. Frost occurs evenly over the cylinder surface. This is normal. The gas withdrawal rate is high. Both the P. B. and gas use vaporizers are frosted. Cylinder has lost vacuum.
SERVICE AND MAINTENANCE General 16 WARNING: Cylinders used in oxygen service must not be changed to CO2 service. This section contains the information regarding the liquid cylinder care and maintenance. It includes the particular maintenance procedures for changes to the operating pressure, service pressure and liquid service changes. When performing a procedure that is described in this section, refer to the previous sections on operation (Section 8 through 13) for a components item number and location.
16 SERVICE AND MAINTENANCE Fittings And Decals It is very important that the proper fittings for the specific gas product being transported are installed on the liquid cylinder. The Compressed Gas Association regulates the fitting design so that equipment compatibility is based on gas product. This keeps from having a nitrogen tank being attached to a hospitals oxygen supply. DO NOT use fitting adapters.
SERVICE AND MAINTENANCE The following relief valve parts list shows the various pressure settings that are offered. The relief valves that are marked for CO2 and N2O are specially designed for those gas products. Reliquefying Solid CO2 In the event the Dura-Cyl HP/Cryo-Cyl HP loses pressure and the contents become solidified, the following procedure should be used: 1. 2. 3. 4. 16 Rego Relief Valve Part No.
16 SERVICE AND MAINTENANCE For Dura-Cyl with LCCM Pressure Control Manifold in Gas Service (Refer to Figure AA) psig is normal). Use an oxygen compatible liquid thread sealant (or Teflon tape) to prevent leaking. 4. Pressure test all new joints using an oxygen compatible leak test solution. 1. Close all four manual valves on the Dura-Cyl . 2. Back out adjusting knob (Item A) on pressure control manifold. 3. Release pressure in the container by opening the vent valve.
SERVICE AND MAINTENANCE Bench Set Combo Regulator Level Gauge Pressure Source Regulator Valve P.B. IN The liquid level gauge in the Cryo-Cyl LP model is a float and spring that approximates the amount of product in the container. The design of this gauge makes it possible to use the same float and spring for nitrogen, oxygen and argon. However, the liquid level decal must be changed for each product. The decals are marked N for nitrogen, O for oxygen, and A for argon. Relief Valve P.B.
16 SERVICE AND MAINTENANCE 18 1 12 4 1 7 5 3 14 7 6 11a 15 (old style) 1/2 8 2 9 2 F 1/2 E F E LIQ NITR UID OGEN 9 LIQ NITR UID OGEN 10 12 a (new style) 17 11 Item Part No Qty 1 2 3 3 3 4 4 4 4 4 5 6 7 8** 8** 9** 10 10 10 10 10 10 11 11 11 11 11 11a 11a 11a 11a 11a 12 12a 14 15 15 17 17 17 17 18 18 2910501 2910601 5410446 5410486 5410476 3830659 3830569 3830579 3830799 3831069 5411086 5410591 2300094 5410582 10561266 2952321 10659280 9091609 5411369 5410769 9092339 10616095
SERVICE AND MAINTENANCE Rebuilding the Operational Valves 5. The valves that are used on the Dura-Cyl/Cryo-Cyl models have a spring loaded rotary stem. This automatically compensates for thermal shrinkage and wear. Reassembly Disassembly and Repair Procedure 1. Partially thread seat disc and nipple assembly (Item 12) (seat disc first), into large end of bushing (Item 9), leaving tang of nipple assembly exposed about 1/3" beyond top of bushing (nipple must rotate freely in bushing). 2.
17 APPLICATIONS AND ACCESSORIES GENERAL 7. Place handwheel (Item 1) over stem and on bonnet. This section of the Dura-Cyl/Cryo-Cyl Series liquid cylinder service manual describes the optional accessories that are available from Chart to aid in; Handling, Filling, Liquid Withdrawal, or Gas Use Applications. 8. Install seal (Item 10) over stem into recess of handwheel. 9. Install seal washer (Item 13) over seal at the bottom of handwheel recess as shown. Handling Carts and Roller Bases 10.
APPLICATIONS AND ACCESSORIES Filling 17 Phase separators are available from Chart in standard hose sizes from 1/8" to 1" thread size. The filling of liquid cylinders can be done more economically if the liquid fill system uses a Chart Lo-Loss System. The Lo-Loss System automatically adjusts the liquid cylinders vent gas flow to minimize the filling loss while maintaining quick filling times. Order Chart form # 2072 for more information on the LoLoss System.
18 SAFETY BULLETIN General Oxygen Deficient Atmospheres Cryogenic containers, stationary or portable, are from time to time subjected to assorted environmental conditions of an unforeseen nature. This safety bulletin is intended to call attention to the fact that whenever a cryogenic container is involved in any incident whereby the container or its safety devices are damaged, good safety practices must be followed.
SAFETY BULLETIN 18 Oxygen Enriched Atmospheres Nitrogen And Argon An oxygen enriched atmosphere occurs whenever the normal oxygen content of the air is allowed to rise above 23%. While oxygen is nonflammable, ignition of combustible materials can occur more readily in an oxygen-rich atmosphere than in air; and combustion proceeds at a faster rate, although no more total heat is released. Nitrogen and argon (inert gases) are simple asphyxiants.