Specifications
24
Functions
and characteristics
Associated controllers 0
Controller selection
By combining a remote-operated source-
changeover system with an integrated BA
or UA automatic controller, it is possible to
automatically control source transfer
according to user-selected sequences.
These controllers can be used on source-
changeover systems comprising 2 circuit
breakers.
For source-changeover systems comprising
3 circuit breakers, the automatic control
diagram must be prepared by the installer
as a complement to to diagrams provided in
the “electrical diagrams” section of this
catalogue.
Controller BA UA
Compatible circuit breakers All Compact NS and
Masterpact circuit breakers
4-position switch
Automatic operation bb
Forced operation on “Normal” source bb
Forced operation on “Replacement” source bb
Stop (both “Normal” and “Replacement” sources off) bb
Automatic operation
Monitoring of the “Normal” source and automatic transfer bb
Generator set startup control b
Delayed shutdown (adjustable) of generator set b
Load shedding and reconnection of non-priority circuits b
Transfer to the “Replacement” source if one of the phases
of the “Normal” phase is absent
b
Test
By opening the P25M circuit breaker supplying the controller b
PB100855
By pressing the test button on the front of the controller b
Indications
Circuit breaker status indication on the front of the controller:
on, off, fault trip
bb
Automatic mode indicating contact bb
Other functions
Selection of type of “Normal” source (single-phase or three-phase)
(1)
b
Voluntary transfer to “Replacement” source (e.g. energy
management commands)
bb
During peak-tariff periods (energy management commands)
forced operation on “Normal” sourceif “Replacement” source not
operational
b
Additional contact (not part of controller).
Transfer to “Replacement” source only if contact is closed. (e.g.
used to test the frequency of UR).
bb
BA controller. Setting of maximum startup time for the replacement source b
Options
PB100856
Communication option
Power supply
Control voltages
(2)
110 V bb
220 to 240 V 50/60 Hz bb
380 to 415 V 50/60 Hz
and 440 V 60 Hz
bb
Operating thresholds
Undervoltage 0.35 Un y voltage y 0.7 Un bb
Phase failure 0.5 Un y voltage y 0.7 Un b
Voltage presence voltage u 0.85 Un bb
IP degree of protection (EN 60529) and IK degree of protection against
external mechanical impacts (EN 50102)
Front IP40 bb
Side IP30 bb
Connectors IP20 bb
UA controller. Front IK07 bb
Characteristics of output contacts (dry, volt-free contacts)
Rated thermal current (A) 8
Minimum load 10 mA at 12 V
Output contacts:
Position of the Auto/Stop switch bb
Load shedding and reconnection order b
Generator set start order. b
AC DC
Utilisation category (IEC 947-5-1) AC12 AC13 AC14 AC15 DC12 DC13
Operational current (A) 24 V 875582
48 V 87552-
110 V 86440.6-
220/240 V8643- -
250 V ----0.4-
380/415 V5-----
440 V 4-----
660/690 V------
(1) For example, 220 V single-phase or 220 V three-phase.
(2) The controller is powered by the ACP auxiliaries control plate. The same voltage must be used
for the ACP plate, the IVE unit and the circuit-breaker operating mechanisms. If this voltage is the
same as the source voltage, then the “Normal” and “Replacement” sources can be used directly
for the power supply. If not, an isolation transformer must be used.