Installation Manual

11 Installer Guide
No. Installer Setting Factory Setting Comments
(
Notes follow this table) Default Options (More information follows this table)
11 1st Stage Fan Control HG FAN 1 HG FAN 1 Select for 1st stage Gas heating
[note 3] HE FAN 1 Select for 1st stage Electric heating
12 Emergency Heat] HE EMER HE EMER Select for Electric Emergency Heat
Fan Control [note 4] HG EMER Select for Gas Emergency Heat
13 Reversing Valve REVO REVO Select for cool active Reversing Valve (O terminal)
(O/B Terminal) [note 5] REVB Select for heat active Reversing Valve (B terminal)
14 Fossil Fuel AE AUX AE AUX Select for Electric Auxiliary heat (with compressor)
Backup Heat [note 4] AG AUX Select for Gas Auxiliary heat (without compressor)
15
Compressor Power Outage
oF CPOP oF CPOP Disables Power Outage Lockout Delay
Protection [notes 3, 6] on CPOP Enables Power Outage Lockout Delay
16 AC Power Interrupt
AC oF MONR
AC oF MONR Disables AC Power Interrupt Warning
Warning [note 6] AC on MONR Enables AC Power Interrupt Warning
17 Compressor Short 5 CSCP 5, 4, 3, 2 or Select a compressor short cycle protection delay of 5,
Cycle Protection 0 CSCP 4, 3, 2 or 0 minutes
18 Residual Cooling 60 FAN 90, 60, 30 Select a Residual Cooling Fan Delay of 90, 60,
Fan Delay or 0 FAN 30 or 0 seconds.
19 Circulating Fan Lock oF CIRC oF CIRC Disables Circulating Fan Lock mode
on CIRC Enables Circulating Fan Lock mode
20 Adaptive Recovery oF REC oF REC Disables Adaptive (early) Recovery mode
Mode (ARM
) [note 7] on REC Enables Adaptive (early) Recovery mode
21 Indoor Remote Sensor I SENS I SENS Temperature is sensed from thermostat only.
Control* [note 8] E SENS Temperature is sensed from remote sensor only.
A SENS Temperature is combined with the thermostat and
the remote sensor.
22 Lockout Security Level 2 LOCK 2 LOCK If locked – Complete lockout is enabled
1 LOCK If locked – Partial lockout is enabled (SpeedBar
®
is
still functional)
23 Auto Changeover 3 BAND 2, 3, 4 or 5 Select a Dead Band of 2°, 3°, 4° or 5˚ F
Dead Band [note 9] BAND (1°, 2° or 3° C) for Auto Changeover mode.
24 Compressor Balance NO BALC NO BALC Disables Balance Points
Point [notes 4, 10] 15-50 BALC Select a Compressor Balance Point of 15°- 50°F
(-9°-10° C)
25 Auxiliary Heat Balance NO BALA NO BALA Disables Balance Points
Point [notes 4, 10]
70-40 BALA
Select a Auxiliary Heat Balance Point of 70°- 40° F
(21°- 4° C)
26 Outside Air Intake OA NONE OA NONE Disables Outside Air Intake option
(A Terminal) [note 11] OA ECON Enables Outside Air Intake (Economizer Mode)
OA TOD Enables Outside Air Intake (Time of Day Mode)
27
Heat Set Point Upper Limit
90LIM 90-60 LIM
Select a Heat Set Point Upper Limit of 90°-60° F (32°-10° C)
28
Cool Set Point Lower Limit
45LIM 45-80 LIM
Select a Cool Set Point Lower Limit of 45°-80° F (7°-27° C)
*When a Braeburn
®
outdoor sensor is connected, the thermostat automatically recognizes it.
NOTE: Additional options such as Service Monitors, Setting the lock code, audible tone, etc. are located in the
User Settings – See User manual for information on setting these options.