Installation / Operation Instruction Manual

1 2385032000B 9/15
SUPPLEMENTVENTINGINSTRUCTIONSFORINSTALLATIONANDOPERATIONINSTRUCTIONMANUALSFOR
THEFOLLOWINGPRODUCTTYPES:
HIGHEFFICIENCYCONDENSINGCOMMERCIAL,COMMERCIALPOWERDIRECTVENT,LIGHTDUTYCOMMERCIAL
POWERDIRECTVENT,LIGHTDUTYCOMMERCIALPOWERVENT,RESIDENTIALPOWERDIRECTVENT,
RESIDENTIALPOWERVENTMODELSERIES,ULTRALOWNOxRESIDENTIALPOWERDIRECTVENT,ULTRALOW
NOxLIGHTDUTYPOWERDIRECTVENT,ULTRALOWNOxRESIDENTIALPOWERVENT,ULTRALOWNOxLIGHT
DUTYPOWERVENT,HIGHPERFORMANCESERIESPOWERVENT,COMBIPOWERVENT,SOLARPOWERVENT
GASBACKUP.
INSTALLATIONOFDURAVENTPOLYPRO®SINGLEWALLPOLYPROPYLENEVENTINGSYSTEMS
ThissupplementisfortheinstallationofpolypropylenesinglewallventingsystemmanufacturedbyM&GDuraVent,Inc.
TheDuraVentPolyproventingsystemisaCSAapprovedalternativetothePVC,ABS,andCPVCventingcomponentsfor
theHighEfficiencyCondensing Commercial,
CommercialPowerDirectVent,LightDutyCommercialPowerDirectVent,
LightDutyCommercialPowerVent,ResidentialPowerDirectVent,ResidentialPowerVentModelSeries,UltraLow
NOxResidentialPowerDirectVent,UltraLowNOxLightDutyPowerDirectVent,UltraLowNOxResidentialPower
Vent,UltraLowNOxLightDutyPower
Vent,HighPerformanceSeriesPowervent,CombiPowerVent,SolarPowerVent
GasBackupModelSeries.
TheDuraVentventingsystemcomponentsareULCS636approvedandlistedbyarecognizedagencyandmaybe
installedintheU.S.andCanada. Allcomponentsusedmustbefromthesamemanufacturerand
aredesignedforuse
withtheabovenotedproducts. TheDuraVentcomponentsmaybepurchasedfromplumbingsupplydistributors. The
ventsizediameterandmax imu mventlengthsmustbefollowedasdetailedinthe InstallationandOperatingInstruction
Manualthatwassuppliedwiththewaterheater. Thoroughlyreadandunderstand
theventingsectionoftheinstruction
manualsuppliedwiththewaterheaterbeforeproceedingwiththefollowinginstructionsinthissupplement. Thevent
terminalssuppliedwiththewaterheaterorthefactoryapprovedaccessoryventterminalkitsmustbeusedwiththis
ventingsystem.
WARNING
The venting system must be properly installed. Failure to properly install the vent system could result in
property
damage, personal injury, or death.
DO NOT install damaged venting system components. If damage is evident then please contact the supplier
where
the water heater or venting system components were purchased for replacement parts.
Use only the vent terminals provided or factory authorized terminals for venting this water heater.
The water heater requires its own separate venting system. Do not connect the exhaust vent into an existing vent
pipe
or chimney.
All of the exhaust venting connections must be leak checked with a soap solution upon initial start-up of the
water
heater. Any leaks must be repaired before continuing operation of the water heater.
Do not terminate the venting where noise from the exhaust or intake will be objectionable. This includes
locations
close to or across from windows and doors. Avoid anchoring the vent and intake pipes directly to framed
walls, floors,
or ceilings unless rubber isolation pipe hangers are used. This prevents any vibrations from being
transmitted into the
living spaces.
Do not exceed the venting distances or the number of elbows listed in the instruction manual supplied with the
water
heater. Exceeding the maximum venting distances may cause the water heater to malfunction or cause
an unsafe
condition.
DO NOT operate this water heater until the venting installation is complete and the piping completed. Failure
to
complete installation before operation can result in property damage, personal injury, or death.