Installation / Operation Instruction Manual
7
Installation (Locating the Water Heater) continued-
A drain pan can be purchased from your plumbing professional. The drain pan
must be piped to an adequate drain. The piping must be at least 3/4 in (1.9 cm)
in diameter and pitched for proper drainage.
It is recommended that a minimum clearance of 4 in (10.2 cm) be provided on
the side of the water heater for servicing and maintenance of the combination
temperature and pressure relief valve.
THIS WATER HEATER MUST BE INSTALLED INDOORS OUT OF THE
WIND AND WEATHER.
Note: For California installation this water heater must be braced,
anchored, or strapped to avoid falling or moving during an earthquake.
See instructions for correct installation procedures. Instructions may be
obtained from DSA Headquarters Office, 1102 Q Street, Suite 5100,
Sacramento, CA 95811.
Minimum Clearances
This installation must allow access to the front of the water heater and
adequate clearances must be provided for servicing and operating this water
heater. The water heater may be installed on either a combustible or non-
combustible floor.
If the water heater is to be installed directly on carpeting, it must be installed on
top of a metal or wood panel extending beyond the full width and depth of the
appliance by at least 3 in (7.6 cm) in any direction or, if the appliance is to be
installed in an alcove or closet, the entire floor must be covered by the panel.
The minimum clearances to combustibles for this water heater are: 0 in (0 cm)
from the sides and rear, 5 in (12.7 cm) from the front of the jacket, 0 in (0 cm)
from the vent connector and 15 in (38.1 cm) from the jacket top. Increase
distances to provide clearance for servicing.
WARNING
Failure to adhere to these installation and operating instructions may
create a hazard to life and property and will nullify the warranty.