SEQUENCE OF OPERATION
A 4 wire, double element heater wired for simultaneous operation is essentially two single element systems operating
independently. The heaters are wired internally with two independent circuits, one circuit for each thermostat/element
combination. When installed using a two wire service, the blue and red (or white) wires will be connected together,
likewise black and yellow wires will be connected together.
Sequence of Operation- Double Element, Simultaneous Operation, Single Phase, 4 wire service
installation.
Circuit two Circuit two
12
1
Line voltage from circuit one is applied
across terminals L1 & L3 of the lower
thermostat. Likewise, line voltage from
circuit two is applied across terminals L1 &
L3 of the upper thermostat. ECO in both
upper and lower thermostat is closed, so
there is voltage at terminal L4 of each
thermostat and to one side of the upper and
lower elements.
Circuit one Circuit one
ECO
Closed
Thermostat closed
at terminal T2
2
Tank is cold therefore both thermostats
are closed at terminal T2 (calling for heat).
This completes the circuit through the
thermostats and allows current to flow
through the elements.
ECO
Closed
Thermostat closed
at terminal T2
Circuit two
3
3
When either thermostat is satisfied, it will
open at terminal T2, interrupting current
flow through the corresponding element. As
both thermostats satisfy, the system will be
in stand-by mode waiting for the next call
for heat. Thermostats will operate
independent of each other.
Circuit one
Thermostat open
at terminal T2
Thermostat open
at terminal T2