Submittal
Thermal Gas Conn. Water
eziS .nnoCeziSycneiciffE.E.U.F.AledoM
BTU/h kW BTU/h kW %%NPTNPT lbs kg
MT2H0200 200,000 58.6 170,000 50.4 85.1N/A 3/41-1/2
85.1N/A 3/41-1/2
270 123
MT2H0300 299,000 87.6 255,000 74.7 300 136
MT2H0400 399,000 116.9 340,000 99.6 N/A85.33/4 1-1/2 330 150
MT2V0200 199,900 58.6 169,915 49.8 N/A 85 270 123
MT2V0300 300,000 87.9 255,000 74.7 N/A 85 300 136
MT2V0400
400,000
117.2
339,915
99.6 N/A 85
330
150
gnippihStuptuOtupnI
Weight
3/41-1/2
3/41-1/2
3/41-1/2
Sizing Data
Accessories
Side-wallventterminalforindoorinstallation(requiredforside-wallventing)
Side-wallcombustionairterminalforindoorinstallation
(required only for ducted combustion air)
Outdoor vent terminal and combustion air terminal
NOTES:
1. Inputandoutputmustbederated4%per1000feetabovesealevelwheninstalledabove2000feetaltitude.
2. Dimensionsarenominal.
3. Forotherboilerratings:
BoilerHorsepower:HP=Output RadiationSurface:EDRsq.ft.= Output
33,475 150
Water Flow
Data
MT2H (Boiler)
TEMPERATURE RISE
20°F 11°C 25°F 14°C 30°F 17°C 35°F 19°C
Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L Flow H/L
Size gpm feet lpm m gpm feet lpm m gpm feet lpm m gpm feet lpm m
200 17 1.6 64 0.5 14 1.0 53 0.3 11 0.7 42 0.2 10 0.5 38 0.2
300 26 3.5 97 1.1 20 2.3 76 0.7 17 1.6 64 0.5 15 1.2 57 0.4
400 34 6.3 129 1.9 27 4.0 102 1.2 23 2.8 87 0.9 19 2.1 72 0.6
MT2V (Water Heater)
HARD WATER NORMAL WATER SOFT WATER
Flow H/L Temp Flow H/L Temp Flow H/L Temp Flow H/L Temp Flow H/L Temp Flow H/L Temp
Size gpm feet rise °F lpm m rise °C gpm feet rise °F lpm m rise °C gpm feet rise °F lpm m rise °C
200 45 7.3 8 170 2.2 4 35 4.4 10 133 1.3 6 23 1.9 15 87 0.6 8
300 45 7.4 11 170 2.3 6 35 4.5 15 133 1.4 8 23 2.0 22 87 0.6 12
400 45 7.4 15 170 2.3 8 35 4.5 19 133 1.4 11 23 2.0 30 87 0.6 17
BMT2H
BMT2V
BMT2H0200
BMT2H0300
BMT2H0400
BMT2V0200
BMT2V0300
BMT2V0400