Quick Installation Guide

DSA E-Series (E2800 60-bay) Installation | en 13
Bosch Sicherheitssysteme GmbH Quick Installation Guide 2017.12 | V1 | DOC
4. Secure the unit to the front of the cabinet by inserting two screws in the 1st and 3rd
holes (counting down from the top) on each side.
!
4.2 Installing a 60-bay unit with SuperRail
You can install the unit in a four-post rack or system cabinet.
Observe the following:
You can install the unit in either a square-hole or round-hole rack.
If you are installing the unit in a cabinet not provided by Bosch:
Ensure that the rack is adequate for the weight and size of the unit to be installed.
Calculate the thermal output of your equipment and compare the results with the
target system cabinet's thermal rating. You might need to remove the system cabinet
doors to improve airflow through the system cabinet.
For thermal rating information refer to the rack or system cabinet manuals provided
by the manufacturer.
You must use only the screws that are provided in the kit.
Notice!
When installing the units, load the cabinet so as not to make it top-heavy. One approach is to
place the controller-unit in the middle portion of the cabinet while allowing room for
expansion units to be placed above and below the controller unit.
4.2.1 Installing SuperRail to square-hole four-post rack
Scope of delivery: SuperRail for square-hole four-post rack
x 2x 4
To install SuperRail to square-hole four-post rack:
1. Determine where you want to install the unit in the rack or system cabinet.
Note: Whenever possible, install the units from the bottom of the rack up, so that you can
use the units underneath as a guide for installing the next set of rails.
2. Attach the rails to the rack or system cabinet as follows:
Hook in the left rail in the adapter brackets and tighten all screws completely to hold
the rail firmly in place.