Panel event Modem4 code
D6500 mode
Modem4 code
Bosch SIA mode
Contact ID event Contact ID code
Status: Fire Alarm SFpppp OriaaFApppp NA NA
Status: Fire Supervisory SEpppp OriaaFSpppp NA NA
Status: Fire Trouble SGpppp OriaaFTpppp NA NA
Status: Gas Alarm SApppp NriaaGAppp NA NA
Status: Gas Supervisory SJpppp NriaaGSppp NA NA
Status: Gas Trouble STpppp NriaaGTppp NA NA
Status: Open by Area SOssss OriaOP NA NA
Swinger Bypass Nsppp NriaaUBpppp Swinger Bypass 1 575 aa ppp
Test Report – System
Normal, Expanded Status
RsssE NRP & see
D6600 CIM for
Status Items
Periodic Test Report 1 602 00 000
Test Report – System
Normal, Non-expanded
Status
RsssE NRP Periodic Test Report 1 602 00 000
Test Report – System Off-
normal, Expanded Status
RsssE NRY & see
D6600 CIM for
Status Items
Periodic Test – System
Trouble Present
1 608 00 000
Test Report – System Off-
normal, Non-expanded Status
RsssE NRY Periodic Test – System
Trouble Present
1 608 00 000
Time Changed – No User
Identified
NsD07 NJT Time/Date Reset 1 625 00 000
Time Changed by Receiver
Sync
NsD07 Nid5001JT Time/Date Reset 1 625 00 F01
Time Changed by User NsD07 NidiiiiJT Time/Date Reset 1 625 00 uuu
Trouble Tspppp NriaaBTpppp Sensor Trouble 1 380 aa ppp
Unverified Event Kpppp NriaaUGpppp Cross-Zone Trouble 1 378 aa ppp
User Authority level has
changed
NsD40 NidiiiiJZiiii Local Only Local Only
User Passcode Tamper – Too
Many Attempts
NsD03 NriaJA Wrong Code Entry 1 461 aa 000
Walk Test End RsssF Nriaa/idiiiiTE Walk Test Mode Emd 3 607 aa uuu
Walk Test Start TsssF Nriaa/idiiiiTS Walk Test Mode 1 607 aa uuu
Watchdog Reset NsD09 NpiddddYW System Reset 1 305 00 000
Watchdog Reset – SDI Device
Reported identifies the
Source
NsD09 NpiddddYW System Reset 1 305 00 000
160 en | Appendix Control Panel