Installation Manual
Table Of Contents
- Title Page
- Table of Contents
- Certifications, approvals, listings, and safety
- Introduction
- System overview
- Installation checklist
- Control panel installation
- Power supply
- Telephone communications
- IP communications
- Keypads, keyswitches, keyfobs and transmitters
- Keypads
- B915 Basic Keypad
- B920 Two-line Alphanumeric Keypad
- B921C Two-line Capacitive Keypad with Inputs
- B930 ATM Style Alphanumeric Keypad
- B942 Touch Screen Keypad
- Shortcuts and custom functions
- Address settings
- Supervision
- Installation and control panel wiring (keypads)
- Sensor loops overview and wiring (B921C/B942/B942W only)
- Output wiring (B942/B942W only)
- Troubleshooting
- Keyswitches
- RADION keyfobs and Inovonics pendant transmitters
- Keypads
- On-board outputs
- Off-board outputs
- On-board points
- Off-board points
- Wireless modules
- Access control
- Program and test the control panel
- Control panel board overview
- System wiring diagrams
- Approved applications
- Keypad Installer menu
- [1] Program menu
- [1] Reporting > [1] Phone menu parameters
- [1] Reporting > [2] Network menu parameters
- [1] Reporting > [3] Routing menu parameters
- [1] Reporting > [4] Personal Note menu parameters
- [2] Network > [1] Ethernet > (choose the bus module or on-board) > [1] Module Parameters menu
- [2] Network > [1] Ethernet > (choose the bus module or on-board) > [2] Address Parameters menu
- [2] Network > [1] Ethernet > (choose the bus module or on-board) > [3] DNS Parameters menu
- [2] Network > [2] Cellular > (choose the SDI2 cellular module or plug-in module)
- [3] RPS > [1] RPS Passcode menu parameters
- [3] RPS > [2] RPS Phone Number menu parameters
- [3] RPS > [3] RPS IP Address menu parameters
- [3] RPS > [4] RPS Port Number menu parameters
- [4] Area Options menu parameters
- [5] Keypad menu parameters
- [6] Users menu parameters
- [7] Points menu parameters
- [8] Disable Programming menu
- [2] Wireless menu
- [1] RF Point Menu> [1] Enroll Point RFID
- [1] RF Point Menu> [2] Replace Point RFID
- [1] RF Point Menu> [3] Remove Point RFID
- [2] RF Repeater Menu > [1] Add Repeater
- [2] RF Repeater Menu > [2] Replace Repeater
- [2] RF Repeater Menu > [3] Remove Repeater
- [3] RF Diagnostic Menu > [1] RF Points
- [3] RF Diagnostic Menu > [2] RF Repeater Menu
- [3] Diags menu
- [4] Serv Byp (Service Bypass) menu
- [5] Versions menu
- [6] Cloud menu
- [1] Program menu
- Specifications
- Appendix
- Back Page
Central Station (Mercantile) 4 N/A
Police Station Connected (Bank) 72 30 (CUL)/15 (UL)
Police Station Connected (Mercantile) 24 30 (CUL)/15 (UL)
Local Burglary (Bank) 72 30 (CUL)/15 (UL)
Local Burglary (Mercantile) 24 30 (CUL)/15 (UL)
Holdup 8 N/A
Residential Fire 24 5 (CUL)/4 (UL)
Table 19.3: Minimum standby and alarm times
Type Required capacity Calculations
Household Burglary and
Commercial Burglary
4 h
Bank Safe and Vault 72 h (UL 365). Auxiliary power current for all devices, including
keypads, must be limited to 80 mA or less to meet this
requirement.
Table 19.4: Standby battery requirements
Notice!
Because of changing regulations, verify the necessary time with your local authority having
jurisdiction (AHJ).
Household Fire Warning equipment
The Household Fire Warning Equipment Standard requires 24 hours of standby current plus 4
minutes of alarm operation at the end of the 24-hour period. Use battery Ah calculations to
confirm compliance. The formula shown below includes the calculation for 4 minutes of alarm
operation at the end of the 24-hour period, and a 15% contingency factor that allows for
depletion of battery capacity with age.
Total B
1
Hours Total C
1
Alarm Operation
2
Contingency Total Ah
3
( ________ x 24 ) + ( ________ x 0.083) + 15% = _________
1
Refer to previous table.
2
Value = Minutes of alarm operation/60
3
Total Ah requirements must not exceed the Ah capacity of batteries:
– One D126 Battery = 7 Ah
– Two D126 Batteries = 14 Ah
– One D1218 Battery = 17.2 or 18 Ah
Table 19.5: Household fire ampere-hour (Ah) calculation formula
UL 365 - Police Station Connected Burglar Alarm Units and
Systems
In a mercantile burglar alarm system, a mercantile alarm sounding device located within a
building but outside the protected area is acceptable provided it is rated for outside service
and alarm conditions are transmitted to:
19.4.1
19.5
Control Panel Approved applications | en 101
Bosch Security Systems, Inc. Installation and System Reference Guide 2016.05 | 14 | F.01U.287.180