Installation Instructions

Input point wiring, dual EOL resistor circuit
style
Notice!
For the dual EOL resistor circuit style order ICP-1K22AWG-10,
package of 10 1.0 kΩ EOL resistors.
1.0 k
1.0 k
Point
COM
NC
1
4
3
2
Figure 7.5: Input wiring with dual EOL resistors
Callout Description
1 Point sensor loop terminals
2 Normally closed device (contact)
3 1.0 kΩ resistor at device
4 1.0 kΩ resistor at EOL (end of line)
Notification appliance circuit wiring
The control panel does not have an onboard NAC. Use a D192G
Notification Appliance Circuit Module for systems requiring a
NAC.
Programming determines the output format and the conditions
that activate the output. One self-resetting circuit breaker
protects against shorts. When using the output to activate
notification appliance circuits in UL Listed fire alarm
applications, install a D192G Notification Appliance Circuit
module.
Refer to the D192G Notification Appliance Circuit Module
Installation Guide (P/N: 4998122260) for detailed wiring
information and specifications.
7.5
7.6