Control Panels B5512/B4512/B3512 (B5512E/B4512E/B3512E) en UL Installation Instructions
Control Panels Table of Contents | en 3 Table of contents 1 Introduction 5 1.1 About documentation 5 1.1.1 Related documentation 6 1.2 Bosch Security Systems, Inc. product manufacturing dates 8 2 System overview 9 3 Control panel installation 10 3.1 Install the enclosure and wiring label 10 3.2 Install the control panel 11 3.2.1 Mount the control panel 11 3.2.2 Connect earth ground 13 3.2.3 Configure OUTPUT A using the jumper 14 3.
en | Table of Contents Control Panels 7.2 Battery lead supervision wiring 35 7.3 2-wire smoke wiring (B201) 36 7.4 2-wire smoke wiring (D125B) 37 7.5 Input point wiring, dual EOL resistor circuit style 38 7.6 Notification appliance circuit wiring 38 7.7 Keyswitch wiring 40 7.8 SDI2 devices general system wiring 41 7.8.1 SDI2 bus wiring recommendations 42 7.9 Wiring label 45 8 Specifications 46 8.1 Wire requirements 49 2015.09 | 08 | F.01U.287.
Control Panels 1 Introduction | en 5 Introduction This section includes an introduction to documents for this product and other document-related instructions. 1.1 About documentation This document contains instructions for a trained installer to properly install, configure, and operate this control panel, and optional peripheral devices. Review this document before beginning the installation to determine the hardware and wiring requirements for the features used. (Bosch Security Systems, Inc.
en | Introduction Control Panels Copyright This document is the intellectual property of Bosch Security Systems, Inc. and is protected by copyright. All rights reserved. Trademarks All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly. 1.1.
Control Panels Introduction | en 7 Two-line Capacitive Keypad with Inputs (B921C) Installation Guide (P/N: F01U297887)* ATM Style Alphanumeric Keypad (B930) Installation Guide (P/N: F01U265451)* Touch Screen Keypad (B942/B942W) Installation Guide (P/N: F01U294527)* *Shipped with the keypad.
en | Introduction Control Panels Auxiliary Power Supply (B520) Installation and Operation Guide (P/N: F01U265445)* RADION receiver SD (B810) Installation Guide (P/N: F01U261834)* SDI2 Inovonics Interface Module (B820) Installation Guide (P/N: F01U265460)* *Shipped with the module. Located on the documentation CD shipped with the module. + 1.2 Bosch Security Systems, Inc. product manufacturing dates Use the serial number located on the product label and refer to the Bosch Security Systems, Inc.
Control Panels 2 System overview | en 9 System overview B91x/B92x/B93x/B94x Use keypads to operate the control panel by area. B5512 control panels support up to 4 areas. B4512 control panels support up to 2 areas. B3512 control panels support 1 area. Each area can have its own account number or you can group together areas with a common account number. B820 SDI2 Inovonics Interface modules interface with an Inovonics wireless receiver.
3 en | Control panel installation Control Panels Control panel installation This section explains how to mount the control panel enclosure, how to mount the control panel into the enclosure, and provides an overview of how to wire modules to the control panel. 3.1 Install the enclosure and wiring label Refer to Enclosures to determine if the application requires a specific enclosure. Installing the enclosure: 1. Remove any knockouts prior to installing the control panel. 2.
Control Panels Control panel installation | en 1 2 3 11 2 3 4 2 5 2 Figure 3.1: Enclosure and control panel mounting (B10 shown) Callout ᅳ Description 1 ᅳ Control panel wiring label 2 ᅳ Enclosure mounting holes (4) 3 ᅳ Module mounting locations (4) 4 ᅳ Tamper switch mounting location 5 ᅳ Control panel mounting location 3.2 Install the control panel This section includes instructions to mount the control panel in the enclosure, connect earth ground, and make other control panel connections.
en | Control panel installation Control Panels 2 3 3 Figure 3.2: B10 and B11 control panel placement locations Callout ᅳ Description 1 ᅳ B10 Medium Control Panel Enclosure 2 ᅳ B11 Small Control Panel Enclosure 3 ᅳ Mounting clip locations for the B5512/B4512/B3512 2. Snap the four supplied plastic standoffs onto four enclosure support posts. If using the B12 Mounting Plate for D8103 Enclosure, attach the standoffs to the plate support posts. Do not attach the standoffs with screws at this time.
Control Panels 3. Control panel installation | en 13 Place the control panel on top of the standoffs. Align the holes in the corners of the control panel with the openings at the top of each standoff. Secure the control panel to the standoffs with supplied, self-threading screws. Figure 3.4: Mount control panel on standoffs 4. If using the B12 Mounting Plate for D8103 Enclosure, rest the hook tabs on the mounting plate hooks within the enclosure.
en | Control panel installation Control Panels Caution! ! Avoid electrostatic discharge. Always touch the earth ground connection with the icon first, before beginning work on the control panel. 3.2.3 Configure OUTPUT A using the jumper When planning your installation, carefully consider the use of OUTPUT A. OUTPUT A is a form C relay.
Control Panels Control panel installation | en 15 OUTPUT A (C terminal) = AUX PWR P1 COM AUX OUTPUT A (C terminal) = COM P1 COM AUX P1 OUTPUT A (C terminal) = DRY COM AUX COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T LINK USB RESET P1 ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 1.
en | Control panel installation Control Panels COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T LINK OUTPUT A Jumper Under Cover ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 1.
Control Panels 4 Power supply | en 17 Power supply This section provides information on installing and maintaining primary power, batteries, and auxiliary power. 4.1 Primary (AC) power The control panel uses an 18 VAC, 22 VA internally fused transformer (CX4010) for its primary power source. The control panel draws 125 mA when idle and 155 mA when in the alarm state. The auxiliary power available for powered devices is 800 mA.
en | Power supply 4.1.1 Control Panels Install the transformer Caution! Do not short-circuit the terminals of the transformer: Shorting ! the terminals opens the internal fuse, causing permanent failure. Connect the transformer to the control panel's AC power terminals before plugging it into the power source. Notice! Plan ahead Route telephone, SDI2 bus wiring, and sensor loop wiring away from any AC conductors, including the transformer wire.
Control Panels Power supply | en 19 Notice! Use sealed lead acid batteries only The charging circuit is calibrated for lead-acid batteries. Do not use gel-cell or NiCad batteries. Extra batteries To increase battery back-up time, connect a second 12 V battery in parallel to the first battery. Use a D122/D122L Dual Battery Harness to ensure proper and safe connection. Refer to Standby battery requirements and calculations.
en | Power supply Control Panels Caution! The battery terminals and wire are not power limited. Maintain ! a 0.250 in (6.4 mm) space between the battery terminals, battery wiring, and all other wiring. Battery wiring cannot share the same conduit, conduit fittings, or conduit knockouts with other wiring. COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T 2 LINK OUTPUT A Jumper Under Cover ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 1.
Control Panels Power supply | en 21 Callout ᅳ Description 6 ᅳ 12 V sealed lead-acid rechargeable battery (D126/D1218) 7 ᅳ Sensor loop wires Charge the battery Connect the battery and then the transformer to allow the control panel to charge the battery while you complete the installation. 4.2.2 Battery maintenance Use 12 VDC sealed lead-acid rechargeable battery (7 Ah or 18 Ah). The control panel supports up to 18 Ah of battery.
en | Power supply Control Panels When battery voltage returns to 13.4 V, the keypads stop showing the low battery messages. If the control panel is programmed for power supervision, it sends a BATTERY RESTORAL report in the Modem4 communication format or a Control Panel Battery Restored to Normal (302) report in the Contact ID format. If programmed for power supervision, the control panel adds a missing battery event to the event log.
Control Panels Power supply | en 23 instructions, and for battery standby time calculations, refer to the B520 Auxiliary Power Supply Module Battery Standby Chart within the installation guide. 4.3.1 SDI2 address settings Notice! The module reads the address switch setting only during module power up. If you change the setting after you apply power to the module, you must cycle the power to the module in order for the new setting to take effect.
en | Power supply Control Panels Caution! ! Remove all power (AC and battery) before making any connections. Failure to do so might result in personal injury and/or equipment damage. Install the module 1. Set the module address using the address switches before you install it in the enclosure. 2. Insert the plastic mounting clips onto the appropriate standoff locations inside the enclosure or on a mounting skirt, when required. 3.
Power supply | en Control Panels 25 Figure 4.2: B520 earth ground wiring Callout ᅳ Description 1 ᅳ B520 Auxiliary Power Supply Module 2 ᅳ 14 AWG - 16 AWG (1.8 mm - 1.5 mm) wire 3 ᅳ Ground device (grounding rod or cold water pipe) Wire to the control panel When wiring a module to a control panel, use the terminal strip labeled with PWR, A, B, and COM for SDI2 IN to wire to corresponding control panel terminals PWR, A, B, and COM. Use 12 AWG to 22 AWG (2 mm to 0.65 mm) wire.
en | Power supply Control Panels Callout ᅳ Description 1 ᅳ Control panel 2 ᅳ B520 Auxiliary Power Supply Module 3 ᅳ Terminal strip wiring 4.3.5 Powered device and battery wiring Wire to SDI2 powered devices When wiring the output of a B520 to a SDI2 module, you can use either the SDI2 OUT terminal strip labeled with PWR, A, B, and COM to wire to terminals labeled PWR, A, B, and COM on the next module, or you can use the interconnect cable (included).
Control Panels Power supply | en 27 Callout ᅳ Description 3 ᅳ Terminal strip wiring 4 ᅳ Interconnect wiring (P/N: F01U079745) Wire to batteries Wiring the B520 to BATT 1 is required for proper operation of standby power for the B520 module. Wiring the second battery (BATT 2) is optional. If a B520 is configured for two batteries as the standby power source, then BATT 2 is also required for proper operation. BATT 2 must have the same capacity and rating as BATT 1.
5 en | On-board outputs Control Panels On-board outputs The control panel provides one configurable (power, common, dry) and two open collector on-board outputs. 5.1 Circuit protection The powered outputs come with circuit protection. Three self-resetting circuit breakers protect the control panel from short circuits on the continuous and programmable power outputs. One self-resetting circuit breaker protects the AUX (auxiliary power) terminal.
Control Panels On-board outputs | en 29 R/PWR terminal and power output of the interconnect connector (SDI2 power) R PWR Power SDI2 devices such as a B208 Octo-input Module, a B308 Octo-output Module, or keypads. Plug-in module connector Connect plug-in modules such as the B440 Conettix Plug-in Cellular Communicator. OUTPUT A NO C NC OUTPUT A Configure Output A as a dry contact (contact rating is 3 Amps), switched common (sink current), or a powered output.
en | On-board outputs Control Panels COMMUNICATION MODULE 1 1 ETHERNET 100BASE-T ETHERNET 30 LINK OUTPUT A Jumper Under Cover ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 1.
Control Panels 6 Control panel board overview | en 31 Control panel board overview 1 2 4 3 5 6 MODULE 1 Y 7 X MODULE RELEASE COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T 9 LINK OUTPUT A Jumper Under Cover USB 1k BATTERY AUX OUTPUT A - 12 V + C OUTPUT B End of Line Resistors 1 COM 2 3 COM 4 5 COM 6 7 COM 8 1 5 7 C B OUTPUT ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 1.
en | Control panel board overview Control Panels Callout ᅳ Description Callout ᅳ Description 7 ᅳ Plug-in module 17 ᅳ Auxiliary power terminals retention clip 8 ᅳ On-board Ethernet 18 ᅳ Terminals for Output A connector (optional) 9 ᅳ USB connector 19 ᅳ Battery terminals 10 ᅳ Heartbeat LED (blue) 20 ᅳ 18 VAC power input terminals 2015.09 | 08 | F.01U.287.185 Bosch Security Systems, Inc.
Control Panels System wiring diagrams | en 7 System wiring diagrams 7.1 System wiring overview 33 Notice! For UL Certificated accounts, additional power can be obtained using only a UL Listed auxiliary 12.0 VDC regulated, powerlimited power supply, such as the B520 Auxiliary Power Supply Module. All terminals are power limited except BAT+ (battery positive). All terminals are supervised except OUTPUT A, OUTPUT B, and OUTPUT C. For proper supervision, do not loop wire under terminals.
en | System wiring diagrams Control Panels MODULE 1 Y X MODULE RELEASE COMMUNICATION MODULE 1 ETHERNET ETHERNET 100BASE-T 1 14 LINK OUTPUT A Jumper Under Cover ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 1.
Control Panels System wiring diagrams | en Callout ᅳ Description Callout ᅳ Description 6 ᅳ Audible signaling device 13 ᅳ USB connector 7 ᅳ UL Listed four-wire smoke 14 ᅳ RJ-45 modular jack for detectors with EOL resistor Ethernet (optional) 7.2 35 Battery lead supervision wiring COMMUNICATION MODULE 1 ETHERNET 4 ETHERNET 100BASE-T LINK OUTPUT A Jumper Under Cover BAT 2BAT 2+ OUTPUT A ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 1.
en | System wiring diagrams Control Panels 2-wire smoke wiring (B201) 7.3 1 o COM B SMOKE RESET A 2 3 PASS-THRU A COM SMOKE B PWR 6 4 5 Figure 7.3: B201 to control panel wiring (B5512 shown) Callout ᅳ Description 1 ᅳ Control panel 2 ᅳ Interconnect cable 3 ᅳ B201 4 ᅳ 1 kΩ EOL resistor (P/N: F01U026703) (included with the control panel) 5 ᅳ 1.8 kΩ EOL resistor (P/N: F01U009011) (included with the module) 6 ᅳ Smoke reset wire 2015.09 | 08 | F.01U.287.185 Bosch Security Systems, Inc.
Control Panels 37 2-wire smoke wiring (D125B) 7.4 PTC1 PTC2 UX PWR R1 R21 R14 U1 C2 R13 R4 R5 R6 R2 R3 C1 R7 C3 CCD 0x - 0xxxx - 000 © RADIONICS INC. D125B 1992 System wiring diagrams | en R11 R12 R9 R22 R10 RV1 RV4 RV3 R8 RV2 TB1/J1 or 5 D125B 1 SWITCH POWER 2 ZONE B 3 ZONE A 4 5 PANEL COMMON 6 BLOOP 7 ALOOP 1 8 B+ LOOP 9 A+ LOOP 10 EARTH GND 10 7, 9 10 11 6, 8 4, 5 2 3 Figure 7.
7.5 en | System wiring diagrams Control Panels Input point wiring, dual EOL resistor circuit style Notice! For the dual EOL resistor circuit style order ICP-1K22AWG-10, package of 10 1.0 kΩ EOL resistors. 2 1 NC 4 Point 1.0 kΩ COM 1.0 kΩ 3 Figure 7.5: Input wiring with dual EOL resistors Callout ᅳ Description 1 ᅳ Point sensor loop terminals 2 ᅳ Normally closed device (contact) 3 ᅳ 1.0 kΩ resistor at device 4 ᅳ 1.0 kΩ resistor at EOL (end of line) 7.
Control Panels System wiring diagrams | en 39 Figure 7.6: Notification appliance circuit wiring (B5512 shown) Callout ᅳ Description 1 ᅳ Control panel 2 ᅳ Output jumper set to configure OUTPUT A terminal C for AUX POWER (jumper cover removed) 3 ᅳ D192G Notification Appliance Circuit module 4 ᅳ 1k Ω EOL resistor (P/N: F01U033966) Bosch Security Systems, Inc. 2015.09 | 08 | F.01U.287.
7.7 en | System wiring diagrams Control Panels Keyswitch wiring 2 1 6 7 3 3 5 5 4 4 Figure 7.7: Keyswitch wiring Callout ᅳ Description Callout ᅳ Description 1 ᅳ Maintained keyswitch 5 ᅳ EOL (End of Line) resistor 2 ᅳ Momentary keyswitch 6 ᅳ Open on the circuit arms the area 3 ᅳ Common 7 ᅳ Momentary short on the circuit toggles the arming state 4 ᅳ Point input Keyswitches are not intended for use in UL listed systems. 2015.09 | 08 | F.01U.287.185 Bosch Security Systems, Inc.
Control Panels COM AUX 1 2 2 4 5 6 7 R Y PWR A G B B COM C OUTPUT B End of Line Resistors 1 COM 2 3 COM 4 5 COM 6 7 COM 8 1 5 7 COM 2 3 COM 4 COM 6 COM C B OUTPUT ON-BOARD POINTS Voltage Ranges Open 3.7 - 5.0 VDC Normal 2.0 - 3.0 VDC Short 0.0 - 1.3 VDC 1k AUX - 12 V + RESET SDI2 devices general system wiring SDI2 Device Bus R Y G B 1 41 TMPR 7.8 System wiring diagrams | en 8 3 Figure 7.
en | System wiring diagrams Control Panels Notice! The SDI2 power terminal (R/PWR) is power limited. The SDI2 terminals are supervised. 7.8.1 SDI2 bus wiring recommendations Use the following SDI2 bus wiring recommendations for SDI2 installation. The control panel and SDI2 modules use the SDI2 bus to communicate with one another.
Control Panels System wiring diagrams | en 43 Callout ᅳ Description 1 ᅳ Control panel 2 ᅳ SDI2 device (module or keypad) 3 ᅳ Daisy chain wiring 4 ᅳ Single-level T-tapped wiring 5 ᅳ Home run wiring Notice! There can only be a difference of 2 volts (maximum) between the AUX power terminals of the control panel or power supply and the device for the modules and keypads to work properly under all conditions.
en | System wiring diagrams Control Panels Cable Overall cable Cable Overall cable capacitance length capacitance length 20 7000 30 4700 21 6666 31 4516 22 6363 32 4400 23 6086 33 4242 24 5800 34 4100 25 5600 35 4000 26 5385 36 3800 Table 7.1: Maximum cable length Notice! Use unshielded cable only. Maximum capacitance of 140nF (140,000 pF) per system. Contact the wire manufacturer for the capacitance ratings of the wire being used. 2015.09 | 08 | F.01U.287.
Control Panels 7.9 System wiring diagrams | en 45 Wiring label This equipment should be installed in accordance with the NFPA 70 (National Electrical Code), the NFPA 72 (National Fire Alarm Code), and the local authority having jurisdiction.
en | Specifications 8 Control Panels Specifications Control panel power supply specifications Voltage input Primar 18 VAC 18 VAC 22 VA Class 2 transformer (power y terminals (CX4010) Secon BAT 12 Volt Sealed Lead Acid dary terminals Rechargeable Battery (D126 or supply) D1218) Current Control Panel: Idle 125 mA; Alarm 155 mA requirements Refer to the Standby battery requirements and calculations section in the control panel Installation and System Reference Guide for the current dra
Control Panels Specifications | en Fire and 47 Alarm power output for OUTPUT A cannot Fire/Burglary exceed 500 mA. Systems Minimum 10.2 VDC (The control panel might operate below this operating voltage, but it will cease to operate as an alarm panel.) voltage SDI2 bus 12 VDC nominal (7500 ft combined length) maximum Ethernet 10BASE-T connection 100BASE-TX (optional) Battery Discharge 13.65 VDC - Charging float level. discharge/ cycle 12.
en | Specifications Control Panels Point On-board Open - 3.7 to 5.0 VDC thresholds points 1 to 8 Normal - 2.0 to 3.0 VDC (Single EOL Short - 0.0 to 1.3 VDC resistor circuit Short circuit current - 5 mA style) Compatible B10 Medium Control Panel Enclosure, B11 Small Control enclosures Panel Enclosure, D2203 Enclosure, D8103 Universal Enclosure, D8108A Attack Resistant Enclosure, and D8109 Fire Enclosure 2015.09 | 08 | F.01U.287.185 Bosch Security Systems, Inc.
Control Panels 8.1 Specifications | en 49 Wire requirements Terminal label Terminal Requirements description 18VAC AC 18 AWG min (up to 12 AWG max) Earth ground 16 AWG min (up to 14 AWG max) BAT + Battery + Bosch supplied wire lead, included BAT - Battery - OUTPUT A NO Output A normally with control panel.
en | Specifications COM Point 5/6 common 6 Point 6 7 Point 7 COM Point 7/8 common 8 Point 8 OUTPUT B Output B OUTPUT C Output C 2015.09 | 08 | F.01U.287.185 Control Panels Bosch Security Systems, Inc.