Installation Instructions
Table Of Contents
!
Caution!
Avoid electrostatic discharge. Always touch the earth ground
connection with the icon first, before beginning work on the
control panel.
Configure OUTPUT A using the jumper
When planning your installation, carefully consider the use of
OUTPUT A. OUTPUT A is a form C relay. You can configure the
common terminal (C) of Output A (OUTPUT A) using the jumper:
– To provide +12 VDC (AUX power)
– To be a COM terminal (parallel to all COM terminals)
– To be a dry contact (no voltage, not common)
The control panel ships with the jumper in the default position,
AUX power. (OUTPUT A, ‘C’ terminal providing AUX PWR). To
reconfigure the ‘C’ terminal as a COM terminal (parallel to all
COM terminals), remove the door covering the jumper pins, and
move the jumper to the left two pins. The OUTPUT A LED lights
when OUTPUT A is active. Refer to the figure below or to the
Enclosure Wiring Label (B5512/B4512/B3512) to set the OUTPUT
A jumper.
3.2.3
14 en | Control panel installation Control Panels
2015.09 | 08 | F.01U.287.185 Bosch Security Systems, Inc.