3. Place the control panel on top of the standoffs. Align the
holes in the corners of the control panel with the openings
at the top of each standoff. Secure the control panel to the
standoffs with supplied, self-threading screws.
Figure 3.4: Mount control panel on standoffs
4. If using the B12 Mounting Plate for D8103 Enclosure, rest
the hook tabs on the mounting plate hooks within the
enclosure. Secure the lock-down tab to the plate mounting
hole with the screw provided.
Connect earth ground
To help prevent damage from electrostatic discharges or other
transient electrical surges, connect the system to earth ground
before making other connections. The icon indicates the earth
ground terminal. Use a recommended earth ground reference,
such as a grounding rod or a cold water pipe. Make the
connection using 14 AWG (1.8 mm) to 16 AWG (1.5 mm) wire.
Notice!
Do not use telephone or electrical ground for the earth ground
connection. Do not connect other control panel terminals to
earth ground.