3. Select Tools >OTA Provisioning Manager. The OTA Provisioning Manager dialog box is
displayed.
4. Click the check box of one or more devices that you want to unprovision.
5. Click Reset Provisioning Information and then click Apply. The device is removed from the
channel and reset to its original mode.
Unprovision Using the Honeywell ISA100 Gateway
To unprovision Ranger Pro devices using the the Honeywell OneWireless device gateway:
1. Open Honeywell OneWireless Wireless Device Manager.
2. Expand the Selection Panel.
3. Select one or more Ranger Pro device(s).
4. In the tool bar, click Channel >Inactivate. The Inactivate Channels dialog box is displayed.
5. Select the device(s) you want to inactivate and click Inactivate. The device is inactivated
and its status is changed to out of service (OOS).
6. In the tool bar, click Provisioning >Delete. The Delete Devices dialog box is displayed.
7. Select the device(s) you previously inactivated.
8. Click Delete. The device is removed from the network. It is restarted and reset to its factory
defaults.
When you inactivate a devices' IOchannels on a Honeywell gateway, the device IO
channel remain inactivated when the device is re-provisioned to the same or different
network. You must reactivate the IOchannels for data to publish from the sensor.
Reactivate using the "activate" feature or by manually setting the IO channel mode to
"Auto".
Unprovision Using a NFCReader
Placing the NFC reader on a bare metal surface may cause interference. Insulate the NFC
reader from the metal surface by placing a 2.5 cm (1 in.)thick book or similar material
under the NFC reader.