Installation Tester BENNING IT 130 Short instructions GB: Detailed instruction manual on enclosed CD-Rom.
BENNING IT 130 short instructions Benning Elektrotechnik & Elektronik GmbH & Co. KG Münsterstraße 135 - 137 D - 46397 Bocholt Phone: +49 (0) 2871 - 93 - 0 • Fax: +49 (0) 2871 - 93 - 429 www.benning.de • duspol@benning.de © 2014 BENNING This document must not be reproduced or used in any other form without the express written consent of BENNING. IDNR. 20 752 285 TN: 10110214.
BENNING IT 130 short instructions Table of Contents 1 Start up guide ................................................................................................................................... 4 1.1 Safety and operational considerations .................................................................................... 4 1.2 Front and connector panel ....................................................................................................... 5 1.3 Standard scope of delivery ..........
BENNING IT 130 1 short instructions Start-up guide 1.
BENNING IT 130 short instructions Warnings related to safety – measurements Insulation resistance Insulation resistance measurement should only be performed on de-energized objects! Do not touch the test object during the measurement or before it is fully discharged! Risk of electric shock! When an insulation resistance measurement has been performed on a capacitive object, automatic discharge may not be done immediately! The warning message and the actual voltage are displayed during discharge
BENNING IT 130 short instructions 1.2 Front and connector panel Legend: 1 2 3 4 LCD UP DOWN TEST 128 x 64 dots matrix display with backlight. Modifies selected parameter. 5 6 7 8 ESC TAB Backlight, Contrast ON/OFF 9 HELP/CAL Help function with connection diagrams (press for approx. 2 seconds for R LOW and ΔU) For calibrating the test cables in the R LOW and CONTINUITY function Starts the ZREF measurement in the sub-function ΔU voltage drop Selects test function.
BENNING IT 130 short instructions Legend: 1 2 3 4 5 Test connector Charger socket USB connector Protection cover C1 6 PS/2 connector Measuring inputs / outputs. For charging the rechargeable Ni-MH storage batteries USB interface for PC connection Measuring input for optional current clamp adapter BENNING CC 1 / BENNING CC 2 / BENNING CC 3 Serial RS-232 interface for PC connection Connection for optional measuring adapters, e.g. BENNING luxmeter type B Connection for optional barcode scanner 1.
BENNING IT 130 short instructions 1.4 Indications and meaning of symbols Terminal voltage monitor The terminal voltage monitor displays on-line the voltages on the test terminals and information about active test terminals in the AC installation measuring mode. The voltage applied is displayed by means of the testing terminal symbol. All three testing terminals L, N and PE are used for the selected measurement. The voltage applied is displayed by means of the testing terminal symbol.
BENNING IT 130 short instructions The test cable resistance for the low-impedance measurement / continuity test has not been compensated. The test cable resistance for the low-impedance measurement / continuity test has been compensated. High resistance to earth of test probes. Results may be impaired. The current is too low for the accuracy specified. This might result in incorrect measuring results. Please check in the current clamp settings whether the accuracy of the current clamp can be increased.
BENNING IT 130 short instructions 1.6 Switch position „AUTO“ Turn the rotary selector switch to the "AUTO" position in order to select the measuring function by means of the "Commander" probe tip (10105455) or by means of the optional "Commander" test plug (044149).
BENNING IT 130 short instructions 1.9 Batteries and fuses Batteries Warning: Disconnect all test cables / accessories from the tester and from the installation and switch the tester off before opening the cover of the battery / fuse compartment.
BENNING IT 130 short instructions Legend: 1 2 3 4 Fuse F1 Fuses F2 and F3 Serial number label Storage batteries/ batteries M 315 mA / 250 V F 4 A / 500 V (breaking capacity 50 kA) Size AA, rechargeable NiMH / alkaline quantity: 6 pieces 1.10 Calibration and Service Calibration To maintain accuracy of the measuring results, the device must be recalibrated in regular intervals by our factory service. We recommend recalibrating the device once a year. In case of need, please contact our service.
BENNING IT 130 short instructions 1.11 Optional accessories Earthing set Earthing set consisting of 2 earth rods and 3 test cables 2 x L = 20 m, 1 x L = 4.5 m item no.: 044113 Current clamp adapter BENNING CC 1, 1 A - 400 A AC output: 1 mV per 1 A item no.: 044037 BENNING CC 2, 0.5 A - 20 A AC output: 1 mA per 1 A item no.: 044110 BENNING CC 3, 0.2 A - 300 A AC/DC output: 1 mV/10 mV per 1 A item no.: 044038 Luminous intensity sensor BENNING luxmeter type B item no.
BENNING IT 130 2 short instructions Measurements 2.1 Null balance (compensation) of the test cables 1. Set function Select R LOW or CONTINUITY. R LOW Short-circuit the test cables. Shorted test leads 3. Press the key . 4. Press the key CAL (HELP). After performing test leads compensation first measured value and then 0.00 is displayed. Successful compensation is displayed by means of the "CONTINUITY" function.
BENNING IT 130 short instructions 2.2 TRMS voltage (V AC/DC), frequency and phase sequence (rotary field) 1. Set function V 2. Connection diagrams Connection of plug "Commander" (optional) and 3-wire test lead in single-phase system Connection of the three-wire test cable and of the three-phase adapter (optional) in a three-phase system 3. The measuring result can be stored by means of the "MEM" key. Uln ..... Voltage between phase (L) and neutral conductors (N) Ulpe ...
BENNING IT 130 short instructions 2.3 Insulation Resistance (RISO) 1. Set function 2. Set parameters and limits. Test voltage [50 V, 100 V, 250 V, 500 V, 1000 V] Minimum limiting value [without (---), 0.01 M ÷ 200 M] R ISO 3. Connection diagrams Connection of 3-wire test lead and tip "Commander" 4. Press and hold the key Double-click until result is stabilized. to start continuous measurement. 5. The measuring result can be stored by means of the "MEM" key. R ................
BENNING IT 130 short instructions 2.4 Low-impedance resistance (RLOW)/ continuity test 1. Set function R LOW 2. Set sub-function and limit. R LOW low-impedance resistance (testing current > 200 mA) or CONTINUITY (testing current < 8.5 mA) Maximum limiting value [without (---), 0.1 Ω ÷ 20.0 Ω] Buzzer [ON/OFF] only for CONTINUITY function 3.
BENNING IT 130 short instructions 2.5 Residual current operated device (RCD) 1. Set function 2. Set sub-function, parameters and limits. RCD I Tripping current RCD t Tripping time Uc Contact voltage AUTO automatic test Nominal tripping differential current IN [10/30/100/300/500/1000 mA]. RCD type [AC, A, F, B, B+] Starting polarity [ RCD , Characteristic [selective , , , , ] , general non- delayed , PRCD, PRCD-S, PRCD-K] Multiplication factor for test current [½ x IN, 1/2/5 x IN].
BENNING IT 130 short instructions 2.6 Loop impedance (Zs L-PE) 1. Set function 2. Set sub-function, parameters and limits. Loop impedance: Zs (for systems without RCD) Zs rcd (for systems with RCD) Fuse type [---, gL/gG, gG, B, C, K, D] Nominal current of the fuse Tripping time of the fuse ZS 3. Connection diagrams Connecting the plug "Commander" (044149) and the 3-wire test lead 4. Press the key . 5. The measuring result can be stored by means of the "MEM" key. Zs .....
BENNING IT 130 short instructions 2.7 Line impedance (ZI L-N/L) 1. Set function 2. Set sub-function, parameters and limits. Z Line Line impedance ΔU Voltage drop Fuse type [---, gL/gG , gG, B, C, K, D] Nominal current of the fuse Turn-off time of the fuse Maximum voltage drop [3,0 % ÷ 9,0 %] ZL 3.
BENNING IT 130 short instructions 2.8 Earth resistance (RE) 1. Set function 2. Set limits. ERDE RE Earth resistance Maximum limiting value [without, 1 Ω ÷ 5 kΩ] RE 3. Connection diagrams Connection of the optional earthing set (044113) 4. Press the key . 5. The measuring result can be stored by means of the "MEM" key. R ...... Earth resistance Rp .... Probe resistance of the S probe (potential) Rc ....
BENNING IT 130 short instructions 2.9 Current (A AC/DC) 1. Set function Note: Please set the current clamp adapter used under "SETTINGS". I 2. Connection diagrams Connection of the optional current clamp adapter BENNING CC 1 (044037) , BENNING CC 2 (044110), BENNING CC 3 (044038) 4. Press the key . 5. The measuring result can be stored by means of the "MEM" key. I ........
BENNING IT 130 short instructions 2.10 Luminous intensity (LUX) 1. Set function 2. Set limit. Minimum illumination [OFF, 0.1 lux ÷ 20 klux] LUX 3. Connection diagrams Positioning of the luminous intensity sensor BENNING luxmeter type B (044111) 4. Press the key . 5. The measuring result can be stored by means of the "MEM" key. E ......
BENNING IT 130 short instructions 2.11 First fault current (RISO) in IT supply system (ISFL) 1. Set function 2. Set sub-function and limit. ISFL Single-fault leakage current (only in IT networks) Maximum limiting value [without, 3.0 mA ÷ 20.0 mA] RISO 3. Connection diagrams Connection of the three-wire test cable 4. Press the key . 5. The measuring result can be stored by means of the "MEM" key. Isc1 .. Single-fault current between L1 and PE Isc2 ..