Operating Manual

Appendix A
DG Series
Premier K Series A-1MN2414
Information in this Appendix applies to the following Baldor Generators:
DG3E and DG6E.
Caution: The brass connecting tab on some 120VAC duplex receptacles have been removed. Each
receptacle is powered by a separate generator winding. When replacing a receptacle, inspect
the brass tab that normally links both receptacles. If it is removed, be sure to remove the
brass tab from the replacement receptacle before it is installed. Failure to remove the tab will
cause a direct short to the generator windings and cause possible generator damage.
Operator Panel Configuration
Figure A-1 DG3E Operator Panel
120V 120V
AC VOLTS
AC BREAKERS
120 Volts NEMA 5−15R GFCI Receptacle.
This ground fault circuit interrupter duplex receptacle is rated at 125VAC, 15 Amps.
120 Volts NEMA L5−30R Receptacle.
Twist−lock style receptacle rated for 125VAC, 30 Amps.
120/240 Volts NEMA L14−30R Receptacle.
Twist−lock style receptacle rated for 125/250VAC, 30 Amps.
AC Voltmeter.
This voltmeter displays the voltage level being produced by the generator set.
Elapsed Time.
Displays the total run time hours of the generator set.
120/240V
ELAPSED
TIME
OIL
OIL Low Oil pressure indicator. Illuminates when oil pressure is low.
AC Circuit Breakers. Provide overload protection for the generator set.
Figure A-2 DG6E Operator Panel
Elapsed Time.
Displays the total run time hours of the generator set.
AC Voltmeter.
This voltmeter displays the voltage level being produced by the generator set.
AC Circuit Breakers.
Provide overload protection for the generator set.
120 Volts NEMA 5−15R GFCI Receptacle.
This ground fault circuit interrupter duplex receptacle is rated at 125VAC, 15 Amps.
120 Volts NEMA L5−30R Receptacle.
Twist−lock style receptacle rated for 125VAC, 30 Amps.
120/240 Volts NEMA L14−30R Receptacle.
Twist−lock style receptacle rated for 125/250VAC, 30 Amps.
AC
VOLTMETER
AC CIRCUIT
BREAKERS
120 VOLTS
120 VOLTS
120/240 VOLTS
120 VOLTS
ELAPSED
TIME