Instruction 2100-9000 Operation and Maintenance Rev.
WARRANTY Bacharach, Inc. warrants to Buyer that at the time of delivery this Product will be free from defects in material and manufacture and will conform substantially to Bacharach Inc.’s applicable specifications. Bacharach’s liability and Buyer’s remedy under this warranty are limited to the repair or replacement, at Bacharach’s option, of this Product or parts thereof returned to Seller at the factory of manufacture and shown to Bacharach Inc.
Pur•Chek™ Contents 1 Introduction...............................................................................1 1.1 How to Use This Manual ............................................1 1.2 Warnings & Cautions ..................................................1 1.2.1 Analyzer Warnings ......................................1 1.2.2 General Warnings & Cautions ....................2 1.3 Features and Capabilities ...........................................2 1.4 Pur•Chek™ Models and Contents ...................
Pur•Chek™ ii Instruction 2100-9000
Pur•Chek™ 1 Introduction 1.1 How to Use This Manual This manual provides important information on how to operate and maintain Bacharach’s Pur•Chek™ HVAC Advanced Refrigerant Identifier. To assure operator safety and proper use of the Pur•Chek™, please read, understand, and follow the contents of this manual. 1.
Pur•Chek™ 1.2.2 General Warnings & Cautions • • • • • • • • • • Always inspect the sample hose before each use. Replace the hose if it appears cracked, frayed, obstructed or fouled with oil. ALWAYS turn the compressor off before connecting the instrument to an air conditioning system. Always wear eye and skin protection when working with refrigerants. Escaping refrigerant vapors will present a freezing danger.
Pur•Chek™ 1.5 Functional Overview Contamination of refrigerants either in storage cylinders or air conditioning systems can lead to component corrosion, elevated head pressures and system failures when utilized by unsuspecting technicians. The ability of the technician to determine refrigerant type and purity is severely hampered by the presence of air when attempting to utilize temperature-pressure relations.
Pur•Chek™ 2 Specifications Sample Parameters Vapor only, oil-free, 300psig (2 MPa) max. Detected Compounds R12, R134A, R22, Hydrocarbons, Air Sensor Technology Non-Dispersive Infrared (NDIR) Refrigerant Sample Size 0.3 ounces (8.5 grams) per sample Power 110/220 VAC Power Adapter 12 - 15 VDC Battery Pack, 2 Amps max. (Optional) Operational Temperature 40 - 130 °F (4 - 54 °C) Blend Refrigerants Displays R410A. Not suitable for R404A or R507A, as they are presented as R134A.
Pur•Chek™ 3 Components 3.1 Base Unit The Pur•Chek™ base unit houses the Graphic Display, Infrared Bench, Electrical Connections, and Optional Printer Module. These components require no maintenance, therefore there are no serviceable components internal to the instrument, and disassembly will void the warranty. Control Panel Sample Filter Printer Door Air Intake Port 3.2 R12 Sample Hose The 6-foot (1.8 meter) R12 Sample Hose is constructed of a nylon inner tube and a polyurethane outer tube.
Pur•Chek™ 3.4 Control Panel The Control Panel serves as the main user interface. The Control Panel features three soft key buttons that change their function as the instrument changes modes. The current function for each button is displayed by the soft key label at the bottom of the graphic display. Red and Green LED’s at the top of the Control Panel are used for visual status indications. Green LED Red LED Soft Keys Power On/Off 3.
Pur•Chek™ 3.6 Hard Shell Storage/Carrying Case The hard shell storage/carrying case is custom fit to the Pur•Chek™. It provides rugged protection for the instrument as well as convenient storage for all components. The enclosure is general purpose and is not watertight.
Pur•Chek™ 4 Operation 4.1 Battery Installation The Pur•Chek™ has, as an option, an internal rechargeable battery. If your Pur•Chek™ is equipped with the optional rechargeable battery, you must first install and charge the battery prior to use. NOTE: The Pur•Chek™ can be operated with or without the battery using the supplied AC adapter. Refer to Section 2.2 for instructions.
Pur•Chek™ 4.2 Turning On the Unit Connect the included AC power supply to the 12 VDC power input jack on the back of the unit. Plug in the AC power supply to a 110/220 240 VAC outlet. NOTE: If the optional battery module is installed and charged, the AC power supply is not required. Press the left, soft key, power button and the splash screen shown in Figure 1 will appear for approximately three seconds followed by the elevation screen shown in Figure 2. See section 5.
Pur•Chek™ READY 1. CONNECT HOSE TO UNIT 2. CONNECT HOSE TO TANK 3. PRESS TEST HELP TESTING SAMPLE THIS WILL ONLY TAKE 30 SECONDS CAL Figure 7. Figure 8. 4.4 Viewing the Test Results Upon completion of the test, the Pur•Chek™ will display a screen similar to that shown in Figure 9 or Figure 10. RESULTS A R134a R12 R22 HC AIR XX.X XX.X XX.X XX.X XX.X EXIT PRINT RESULTS DET - 1 DET - 2 DET - 3 DET - 4 NON XX.X XX.X XX.X XX.X XX.X EXIT Figure 9. PRINT Figure 10.
Pur•Chek™ 4.6 Printing the Test Results For units equipped with the optional factory-installed printer module, the test results can be printed by selecting the “PRINT” button. After the print is complete, carefully tear off the printout and the unit will return to the previous screen. Additional printouts may be made following the same procedure. To exit the test, press the “EXIT” button. Figures 14, 15, & 16, show sample printouts for various test results. Bacharach Inc.
Pur•Chek™ 5 Maintenance & Troubleshooting 5.1 Setting the Elevation During the initial power-up, the Pur•Chek™ will indicate that the elevation has not been set. To set the elevation, press the “Help” button on the “Ready to Air Cal” screen as shown in Section 4.3, Figure 3. The screen will display several options as shown in Figure 17. Pressing the “SET” button will display the options in Figure 18.
Pur•Chek™ TO SET THE ELEVATION PRESS ELEV BUNNON TO SET THE LCD CONTRAST PRESS CONT ELEV CONT ADJUST CONTRAST FROM 0 TO 80 SETTING DONE SET Figure 23. 045 FEED DONE Figure 24. 5.3 Changing the Sample Filter When inspecting the sample filter, look completely around the entire outside diameter of the white filter element located inside of the clear plastic housing. Look for red spots or the beginnings of discoloration on the white outside diameter of the element.
Pur•Chek™ TO CHANGE SETTINGS OR REPLACE PAPER ROLL PRESS SET FOR OTHER HELP PRESS HELP SET HELP TO FEED IN A NEW PAPER R TOLL PRESS FEED PRESS SET TO ADJ LCD CONTRAST OR ELEVATION DONE SET Figure 25. FEED DONE Figure 26. TO LOAD PAPER 1. PRESS FEED 2. INSERT PAPER 3. PRESS STOP 4. PRESS TEST TO TEST AND EXIT FEED STOP TEST Figure 27.
Pur•Chek™ 6 Replacement Parts Part Number Description 2100-0003 Printer Paper (Single Roll) 2100-0004 AC Adapter 2100-0005 Hose Assembly 2100-0006 Replacement Sample Filter 2100-0007 Optional Rechargeable Battery Kit w/ Battery and Charger 2100-0012 Spare Rechargeable Battery 2100-9000 Instruction Manual 7 Service Centers Service and replacement parts can be found by contacting any of the following Bacharach Service Centers: United States Bacharach, Inc.
Pur•Chek™ NOTES: 16 Instruction 2100-9000
Pur•Chek™ NOTES: Instruction 2100-9000 17