User's Manual

30
4 - Operations
Overshoot
control
(Automatically disabled when the
adaptive tuning is running).
This parameter specifies the span of
action of the overshoot control. Setting
lower values (0.99 —> 0.01) the over-
shoot generated by a Setpoint change
is reduced. The overshoot control
doesn’t affect the effectiveness of the
PID algorithm. Setting 1, the over-
shoot control is disabled.
Heat/Cool
dead band
This parameter specifies the width
of the deadband between the Cool
and the Heat channel.
Control output
high limit
Cool output
high limit
It specifies the maximum value the
control output can be set
#Op.HC
#Op. H
#d.bnd
#O.C.
Control output
hysteresis
Cool output
hysteresis
Control or alarm output hysteresis
span, set in % of the full scale.
Off
SP
On
Hysteresis of the threshold
hy
#hy. C
#hy.
AL2
alarm hysteresis
AL3
alarm hysteresis
Hysteresis of the threshold of both
the alarms, that activate OP1 and
OP2 control output. It is specified
as a % of the full scale.
Setpoint
low limit
Setpoint
high limit
Low / high limit of the Setpoint value.
AL2, AL3
latching
and blocking
functions
For each alarm it is possible to
select the following functions
none none
Ltch latching
bloc blocking
Lt.bL both latching and blocking
#A2L.b
#A3L.b
#s.p. H
#s.p. l
#A3hy
#A2hy
SECOND GROUP
Stand-by
Setpoint
Used by Timer function too.
Setpoint
ramp up
Setpoint
ramp down
This parameter specifies the max-
imum rate of change of the Setpoint
in digit/min. When the parameter is
Off, this function is disabled.
#sl. d
#sl. u
#S.P. 2
SECOND GROUP