User manual

Network Management Card & Modbus/Jbus 34022321XT indice :AD Page 77/91
Network Management Teleservice Card
APC by Schneider Electric
www.apc.com
Status description
Status to
0
Status to 1
Word (hex) Bit (0-15)
Overlaptransfert fault on SSC No yes 45 11
Maintenance position No yes 46 1
AC bypass overload (Nota 7) No yes 46 5
AC bypass thermal overload (Nota 7) No yes 46 6
AC bypass fault (Nota 7) No yes 46 7
AC bypass frequency out of tolerance (Nota 7) No yes 46 9
AC bypass voltage out of tolerance (Nota 7) No yes 46 A
Phase AC bypass out of tolerance (Nota 7) No yes 46 B
AC bypass sitch (Q4S) Open Closed 46 E
AC bypass internal fault (Nota 7) absent present 47 0
Forced desynchronization
absent present 47 1
Bypass frequency independent (Nota 7)
absent present 47 8
Output switch (Q5N) Open Closed 47 B
Charger general fault No Yes 49 0
Battery charge (Nota 5) No Yes 49 3 & 1
(bit1 for
legacy
product)
Chopper major fault (Nota 5) No Yes 4A 1
Inverter major fault (Nota 5) No Yes 4C 1
Inverter overload (Nota 5) No Yes 4C 2
Inverter thermal overload (Nota 5) No Yes 4C 3
Inverter limitation (Nota 5) No Yes 4C 4
UPS fuse fault (Nota 5) absent Present 4C 5
Load Short circuit absent Present 4F 1
Nota 1 : for Battery charge it is necessary to set 2 bits, for legacy JBUS table
Nota 3 : switch status equal 1, when closed
Nota 4 :
INMC/NMTC
Galaxy
@41 Hex @41 Bin @41 Bit3 @41 Bit2 @41 Bit1 @41 Bit 1, 2 and 3 in Dec
Unitary 2 0010 0 0 1 1
Modular
4 0100 0 1 0 2
Parallel 6 0110 0 1 1 3
SSC 8 1000 1 0 0 4
Nota 5 : This Information is not present with a Static Switch Cabinet unit.
Nota 6 : Device Ventilation Fault is present only in a Static Switch Cabinet 800kVA, this information is not present in a Static Switch Cabinet
1200kVA
Nota 7 : For a configuration with UPS in parallel with SCC unit, the Main 2 data need to read on the card installed in the SSC unit.