Specifications

Installation Procedures: Connect the Power Source to the PDU
150 kW InfraStruXure Power Distribution Unit 15
For overhead wiring: Remove the gland plate on the roof of the PDU, and then detach the
user connection plate from the gland plate, route the user connection plate through the
opening left by the gland plate, and then carefully set the user connection plate aside on top
of the enclosure (do not disturb the connected wires).
2. Use a knock-out punch to create an appropriate-
sized hole in the gland plate for the conduit.
3. Install a lock-nut and bushing to the conduit.
4. Thread the conduit through the hole.
5. Re-attach the user connection plate to the gland
plate.
6. Re-attach the gland plate to the PDU enclosure.