1.6.1 Power supplies
The control circuits Class 2 are fed by sources intrinsically limited. In particular
UL508A imposes
1. transformers: CCN XOKV,XOKV2 (UL 1585 ”Class 2 transformer”);
2. transformers:CCN NWGQ, QQGQ2 (UL 1950 “Information Technology
Equipment”) only if use in Class 2 circuits is expressly indicated in the
marking.
All the derived circuits down line of a Class 2 supply are to be considered Class 2
circuits if properly wired.
1.6.2 Overcurrent Protection
Protections are not needed down line from the power source because the circuit
is self/protected (there might be some few rare exceptions in the case of the use
of conductors or components with particular characteristic).
Up line from the supply, the protection should be suitable for the point of
installation (only BCPs are derived directly from the general feeder,overcurrent
protection if we derive from a pre-existing BCP,down lines) and it should respect
all restrictions imposed on the marking or instructions.
1.6.3 External Wiring and Terminal
The conductors on the machine of Class 2 circuits should be appr
o v ed; in
addition they should be separated (with the use of special accessories) or isolated
(minimum distance 50.8 mm) from the conductors of all the other non Class 2
circuits.
The panel-on machine interface should follow the same provisions valid for the
terminal blocks of a general control circuit (for example the limits on the cross-
section that can be connected): in opposite cases the terminal blocks should be
separated from of all the other circuits (not Class 2).
The Class 2 circuit terminal block should be clearly indicated with a marking.
If this instruction is not respected the circuit goes automatically to Class 1, losing
all the relative advantages.
1.6.4 Internal Wiring
The Class 2 approved conductors should be separated or isolated from the
conductors of the other circuits (not Class 2) unless they are insulated f or the
maximum v oltag e present.
CONTROL CIRCUITS