Installation Guide

DC Outdoor - 3 -
Fig. 1
CAUTION: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: When installing in a non-restricted service area, use lock or other fastened means on door
latches. This installation should be made by qualified service personnel and should conform to the National
Electrical Code and all local codes.
LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal operating condition.
ON OFF Loss of AC. Stand-by battery supplying power.
OFF ON No DC output. Short circuit or thermal overload condition.
OFF OFF No DC output. Loss of AC. Discharged or no battery present.
The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the
presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient
magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of important
operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION: To reduce the risk of electric shock do not open enclosure. There are
no user serviceable parts inside. Refer servicing to qualified service personnel.
Terminal Identification:
Terminal Legend Function/Description
--- DC +
WayPoint3: 12VDC or 24VDC @ 2.5 amp peak supply current (2 amp continuous).
WayPoint5: 12VDC or 24VDC @ 4 amp peak supply current (3.2 amp continuous).
WayPoint7: 12VDC or 24VDC @ 6 amp peak supply current (4.8 amp continuous).
WayPoint1012V: 12VDC @ 10 amp peak supply current (8 amp continuous).
WayPoint104: 24VDC @ 10 amp peak supply current (8 amp continuous).
– BAT + Stand-by battery connections. Maximum charge rate 500mA (700mA for WayPoint1012V/104).
Bottom of Enclosure
Suggested Locations
for Wiring Inlets