Installation Instructions

Prerequisites and Site Planning
Chapter
2
Oct 2013
AfiAct II™ Installation Manual13
The Reader mounting location is based on the cowshed size and location, and
should comply with the following conditions:
x Height
: The Reader is mounted on a pole about 3.5 meters high from the
ground.
x Coverage (tags and Wi-Fi/wire)
: (fine-tuning will be performed while mounting)
x The mounting pole location must allow tag-coverage range for the whole
defined area. This is determined according to the shed scheme, and will
probably be around the center of the required 80 meters coverage radius,
also covering the feeding and water trough areas.
x The Reader should have a line of sight towards cow tags, with minimal
interference from other sheds/poles/buildings, etc.
x The Reader should have WiFi / Wired connectivity to the Access Point /
office.
x Power access
: The pole has near access to a power outlet (to be provided by
the farmer).
x Accessibility
: The Reader and power box can be easily viewed and accessed
for maintenance (if possible – accessible from the passage).
x Weather protection
: The Reader and power box must be located under a roof
with minimal exposure to weather conditions, according to the following
specifications:
x The structure may be made of metal or wood.
x The roof should be at least 4 meters high and may be made of a plastic
material (but not aluminum or sheet metal).
x The roof must be large enough to prevent any direct sun or rain exposure to
the device.
x If the sides are closed, this siding material should not be metal either.
x If metal fencing is used to keep animals out, it should be a large opening
Australian-type fencing material (at least 30 cm) (otherwise the
communication signals may be reduced).
NOTE
The final coverage and corresponding location determination must be done
during a site survey and could vary according to specific farm environment.