Figure 14. Batterycabinethangerbrackets.
4.3.2 Integral battery cabinet electrical connections
All battery cabinets will arrive at the site with each battery connection string electrically
disconnected. If you are installing more than one battery cabinet, the battery cabinet adjacent to
the UPS will be the only cabinet directly connected to the UPS.
Figure 15. Generalbatterycabinetwiringinstallation.
Use this procedure to wire an integral battery cabinet to the UPS cabinet:
1. Locate the battery cabinet-to-battery cabinet breaker sensing cable in the first battery
cabinet. Route this connector into the cabinet to the immediate left and mate with the
matching connector in that cabinet.
Figure 16. BatteryauxiliaryandUVRwiring.