Secvest 2WAY I NSTALLATI ON1 I NSTRUCTI ONS BOM-No.
Preface Introduction Dear customers, This wireless alarm centre is used to secure your property in combination with detectors and transmitters. Among others, it can be used to protect your company premises, house, garage, summer house or weekend cottage. Many thanks for your purchase of the SECVEST 2WAY wireless alarm centre. This device is built according to state-of-the-art technology. It complies with current domestic and European regulations.
5.5 5.6 5.7 Contents PREFACE......................................................................................................................2 MODULES AND EXTERNAL SIRENS ....................................................................... 30 ACCESSORIES ................................................................................................. 31 WIRELESS TESTING BOX.................................................................................... 31 INTRODUCTION ........................
13.5 13.6 13.7 13.8 13.9 13.10 13.11 14. 16.4 16.5 16.6 16.7 17. ADDING OUTPUTS .......................................................................................52 EDITING OUTPUTS .......................................................................................53 ASSIGNING THE OUTPUT NAME ......................................................................53 INVERT OUTPUT ..........................................................................................54 SELECTING THE OUTPUT TYPE ..
19.8 19.9 20. SECURE CALLBACK.......................................................................................79 MODEM BAUD RATE ...................................................................................79 20.3.8 Alarm call with voice message .................................................... 91 20.4 SMS ....................................................................................................... 91 20.4.1 Call Mode................................................................
25. INSTALLING ADDITIONAL MODULES..............................................................99 26. FITTING THE ISDN MODULE..........................................................................100 27. FITTING THE GSM MODULE..........................................................................100 28. FITTING THE ETHERNET MODULE.................................................................101 29. FITTING THE GPRS MODULE ....................................................................
1.
1.1 Cellar installation Number 1 1 1 3 5 5 Installed components Cellar Info module Motion sensor Water detector Smoke detector Opening detector Glass breakage detector Abbr.
1.2 Ground floor installation OD No. 1 5 1 3 14 16 1 Installed components Ground floor Secvest 2WAY Motion sensor Water detector Smoke detector Opening detector - with Glass breakage detector Wireless key switch Abbr.
1.3 Top floor installation No. 1 1 3 3 1 4 6 9 4 4 1 Installed components Top floor Control panel Internal siren Wireless motion sensor Wired motion sensor Water detector Smoke detector Opening detector Glass breakage detector Wired opening detector Info module External siren Abbr.
1.4 Number of components No. 1 1 1 3 5 5 No. 1 5 1 3 14 16 1 No. 1 1 3 3 1 4 6 9 4 4 1 Installed components Cellar Info module Motion sensor Water detector Smoke detector Opening detector Glass breakage detector Abbr. No. IM MS WD SD OD Installed components Ground floor Secvest 2WAY Motion sensor Water detector Smoke detector Opening detector - with Glass breakage detector Wireless key switch Abbr.
1.
2.1 230 V a 50 Hz mains connection 2. Installing the system The following pages describe basic system programming. A step-by-step guide of the most important aspects on the Secvest 2WAY system is presented. Detach the cable relief points and secure the power cable. Attach the Secvest 2WAY alarm centre. 230 Volt a 50 Hz The alarm centre may only be installed by qualified specialists. The device is designed for indoor use only.
2.2 PSTN telephone connection 3. Training the detectors The alarm centre is connected to the telephone connection as follows. Call up the installer menu. Enter a valid installer code (default setting = 7890): 7890 It may also be necessary to enter the administrator code 1234 (default). Coding B1 Æ A1 Æ Å B Å A “You are now in the installer menu” a b TAE N-plug White ¾ Select the Detectors menu item. ¾ Select Add/Del Detectors. ¾ Select Zone 01.
Enter letters and characters via the keypad. Letter-to-key assignment: When using the smoke detector, press the test button and hold it until the alarm sounds (about 10 seconds). Press the wall break contact on the opening detector.
3.2 Checking the detector range 3.3 Checking the signal strength of the detector The detector signal strength test is made in the same way as the walk test. The displayed signal strength corresponds to the reception strength of the last received signal on this detector. The signal strength must be higher than 3 for satisfactory wireless communication. If the detector signal is too weak, use a repeater (accessory module) to ensure good wireless communication.
Train the alarm centre to the info module. 3.4 Installing and training the info module In the installer menu: The example shows a house in four partitions. The status of each partition should be displayed on each floor. Each partition can be activated or deactivated separately. Therefore, an info module must be installed for each partition. Please note that the info modules require a 12 V power supply. Æ Partition 1 (cellar) Select the Info Module/Int Siren menu item.
3.5 Accessing the alarm centre In order to not trigger an alarm when leaving (Ext Time) or entering (Ent Time) the area, a delay time must be defined for accessing the centre in Partition 01. Access the installer menu and set the exit or entry delay under the “Partitions” menu item.
3.6 Internal alarm active (Prt Set All) This setting is used when the inside of the house should be accessed freely whilst being protected against break-ins from the outside. The detectors must be configured so that external surveillance is created. Change Part Set to Yes. The Part Set setting is displayed with I. When activation is made, you also have the possibility of Part Set All in addition to Full Set All. Set the detector for external surveillance to “Part Set”.
3.7 Forwarding alarm messages over the telephone (speech dialler) This setting is used for informing the user over the telephone. Call up the installer menu and select the “Reporting” menu item. Installed microphone In the installer menu: Æ The recording should contain the following information: Select the Speech Dialler menu item. Who is calling: In the speech dialler menu: “Break-in on detector system of Smith family” Location: “Sample Street 1 in Sampletown” Æ Select the Enabled menu item.
Trigger list Enter a maximum of four names and numbers in the telephone book who are to be called when an event occurs. The call sequence starts with number 01, then number 02 up to the “Follow me” number. Trigger Triggered by None Triggers do not trigger messages Fire Smoke detector In the speech dialler menu: Æ Select the Telephone Number 01 menu item. A dial pause of three seconds can be entered using the “*” key. Please note that the last telephone number is designated as the Follow me number.
3.8 Informing other persons 3.9 Signaller To prevent manipulation of the siren, it should be attached out of arm’s reach (at least 3 metres from the ground). Please also take local legislations into account. In some European countries, the use of external sirens is forbidden or the maximum alarm duration is restricted. Contact your local authorities for more information in case of doubt. In the speech dialler menu: Æ Select the Enabled menu item.
Select the trained Ext Siren. When the sirens have been trained, the alarm centre beeps twice as confirmation. A message is displayed with the siren confirmation and the signal strength value. If the external siren should be activated when the relevant partition triggers a local or external alarm, then the partition must be set to Yes. Leave this display by pressing Back. 3.10 Configure a user If a siren has been trained, then the siren number.
You are now in the user menu (administrator). User menu Æ Select the “User” menu item. Now enter an access code for your guest. You have a guest that may only access the ground floor. Enter a user name. Confirm the access code by repeating it. You now have the possibility of training diverse components for activation. Confirm with OK. If you do not wish to train chip keys (tags), then confirm by pressing No Tags… Select the Normal User user status. Allocate the relevant access rights to the user (e.g.
If you do not wish to train telecommands (remote control), then confirm by pressing No Telecommands…. If you do not wish to train social care, then confirm by pressing No Social… If you do not wish to train panic transmitters, then confirm by pressing No PA… The user is added with this display. Further users can now be added.
4. Scope of delivery Installation instructions Downloader CD Operating instructions Secvest 4 wireless alarm centre Chip key (tag) Keyring 2 x housing screws 6 x NiMH R6 AA rechargeable batteries 1.2 V / 2000 mAh 3 x wall plugs 3 x screws (wall fixation) 8 x hole adapters 2 x 4.7 k 26 2 x 2.
5.
5.1 Wired detector MK1010W MK1300W with WKS FU7300 5.
5.3 Transmitter Emergency call transmitter (pendant) FU8390 Panic transmitter FU8305 5.
5.
5.6 Accessories 6 V standby rechargeable battery for the accessory module FU3821 12 V / 1 A PSU FU3822 12 V / 1 A built-in PSU for 55 mm UP switch boxes TVAC35200 5.
6. Safety information WARNING! Caution! To avoid fire and injury, please note the following: Please observe the following precautionary measures to ensure trouble-free operation of your system. x Securely fasten the device in a dry location in the building. x The alarm centre is supplied with power from the built-in PSU. x Ensure sufficient ventilation for the alarm centre. x The PSU is connected to the 230 V AC domestic mains network over a separate, electrically protected line.
!WARNING! Warning: Radiation level of the emitted high frequency The emitted high frequency of this component is below the European limit values, which are considered safe. Nonetheless, the product must be attached so that the possibility of a user being exposed to it during normal operation is kept to a minimum. To keep the radiation level to a minimum, users must be more than 200 mm away from the component during normal operation.
7. Notes on connection and extension options Alarm centre characteristics: x 48 freely programmable wireless zones, all of which can be programmed as follows: Normal Alarm, Final Exit, Entry Route, 24 Hour, Fire, Panic, Key Sw Moment, Key Sw Latched, Technical or Key Box. x 2 freely programmable wired alarm zones in the wireless alarm centre that can be programmed in the same way as the wireless zones.
8. Notes on the security system 8.2 Connections on the top part of the alarm centre High-frequency emission warning! The limit value of the emitted high-frequency signals for these components is below the European standard (considered as safe). Nonetheless, the device must be attached so that potential contact with users during normal operation is kept to a minimum. To keep signal emissions to a minimum, users must be more than 200 mm away from the components during normal operation.
8.3 Connections on the base plate of the alarm centre 8.5 Assembling the base plate The following diagram shows the connections on the base plate of the alarm centre. Fix the base plate to the wall as shown in the diagram. Ensure that the alarm centre is installed so that the rear is not screened by hidden metal. Fix the device at a height where the user can easily read the information on the display.
8.6 Connecting the alarm centre to the 230 V mains supply 8.7 Connecting wired components Connecting the alarm centre to the 230 V AC mains network is subject to national regulations. Check that no voltage is present in the connection cable when fitting. Connect the 230 V power supply to the mains connector according to EN60950-1 as shown in the diagram. Remember to fix the cable with suitable tension relief.
8.8 Connecting the analogue telephone connection 8.10 Inserting the rechargeable batteries for emergency power supply Connection instructions for ISDN / GSM / ethernet and GPRS modules can be found in chapter 24. Connect the analogue telephone line as shown in the diagram: Insert the six batteries correctly into the compartment. Replace the batteries every two years at the latest with batteries of the same type. Only use batteries with the following specifications: 1.
8.11 Closing the alarm centre 8.13 Final tasks Reconnect the top part to the base plate. Remember to connect the connection cable of the base plate to the alarm centre. At the same time, check that all other connections (emergency power supply and loudspeaker) are correctly connected to the top part. Close the alarm centre and attach it to the bottom part using the housing screws. All connections are now made and the wireless alarm centre is ready for programming.
9. Explanation of terms SILENT ALARM In the event of a silent alarm, the connected acoustic and optical signalling devices are not activated. Transmission is only made over the telephone line. Before starting to program the alarm centre, you should become familiar with the terms used. SYSTEM ACTIVATED When the wireless alarm centre is activated, it monitors all zones for changes and triggers a local alarm and an external alarm (optional). PARTITIONS The wireless alarm system has a total of 4 partitions.
10.
11. Graphic display The graphic display informs you about all events concerning the wireless alarm system. The following is an overview of the different display messages and their meaning: partition 1-4 The four black bars stand for the four individual partitions of the wireless alarm system. A letter in the black bar represents the state of the partition (1–4).
12. Installer menu 12.1 First steps in the installer menu The wireless alarm centre is configured in the installer menu. There are two ways of programming the wireless alarm centre: In the user mode, proceed as follows: If you are in user mode, you must first change to the installer mode. Do this as follows: A: B: Enter a valid installer code (default setting = 7890): 7 8 9 0 You may also have to enter an administrator code (default setting = 1234) or user code.
System Options Perform user functions, select language, restore default settings, change installer code, define delay and siren times, configure supervision and jamming detection IP Network Configure IP settings Download Configure download settings Reporting Configure telephone settings, define transmission types Social Care Set social care, define activation times Test Centre and detector test, output test, walk test, wireless communication View Log Read the event log About Panel Read inform
If a detector has been trained, then the zone number. symbol is shown next to the In the case of an assigned zone of a WAM (WAM function 3 transmitter/receiver) "w2" appears, for example. This display shows which zone the detector has been trained to, the zone type programmed for this zone, the partition that the detector monitors and the additional zone attributes. SS is also displayed, which shows the received signal strength. This value should be higher than 3 for satisfactory communication.
Some detectors do not have tamper contacts (e.g. smoke detectors) and only send an alarm (A). The display with the number of tested zones without tamper contacts remains. To delete the detector and the zone information, select the Default Zone menu item and confirm with Next. Select Test Select Walk Test Number of zones to be tested T = Tamper A = Alarm Information: All zones tested Trigger a tamper contact (T) and an alarm (A). Confirm deletion by pressing Yes. 13.
Select the Delete All menu item. ¾ You will now be prompted to activate the Tamper contact. Example: Motion sensor Tamper contact (wall break contact) Confirm deletion by pressing Yes. 13.5 Adding the zone 01 detector manually In the installer menu: Æ Æ Display of the signal strength Select the Add/Del Detectors menu item. ¾ ¾ The detector was successfully trained. Select Zone 01. To ensure satisfactory communication, the signal strength should be more than 3.
13.6 Editing detectors (zones) In the installer menu: Æ Æ Select the Edit Zones menu item. Select the Name menu item. The detector transmits its standard settings automatically to the alarm centre after training. This setting can be changed at any time. Delete the existing name (Zone 01) and assign a unique name for the zone (max. 12 characters). Editing Zone 01 13.
13.8 Selecting the zone type “Normal Alarm” zone type with FTS 96 E function The preset zone type can be changed here. Pay attention to the zone type descriptions in this chapter. To use the FTS 96 E wireless window lock (item no. FU841x) or the FTS 96 wireless upgrade set (item no. FU8402), program the “Normal Alarm” zone type in the alarm centre. x When the alarm centre is deactivated, these detectors are monitored for detachment and opening. The window must be closed and the FTS 96 E locked.
The info module FU8200 beeps once every second and the red alarm LED lights up. The indoor siren FU8230 beeps once every second. It must however be supplied by a power supply unit for this and the jumper "Alarm Only" must not be inserted. (This sound is an "Info" sound, not an "Alarm" sound.) The duration of all signals is 30 seconds. An output of the "Perimeter Warn" type is enabled for 30 seconds.
Example: Shared office Further properties can be allocated to the zone here. Property Chime Soak Test Activity Mon. An overview of partition characteristics can be found in chapter 15.1 of these instructions. Part Set The following types can be assigned to one or more partitions: Normal Alarm, Entry Route, Final Exit, Key Sw Latched, Key Box, Exit Norm. Alm.
14. Outputs The controller has 34 outputs. The first two outputs (O/P1 and O/P2) are wired outputs. Outputs 3 to 34 are wireless outputs. They can be accessed using a FU8210 accessory module or a wireless socket. The Soak Test function should only be set when the detector has a tendency of triggering false alarms. This function works automatically. To test the detector range, use the walk test function.
14.2 Editing outputs In the installer menu: Æ Æ Select the Edit Output menu item. Select Add Output. Now edit Zone 01. Select (HW)Output 01 Select the Name menu item. Confirm by pressing Yes. 14.3 Assigning the output name It is sensible to assign a clear and unique output name so that the output can be identified quickly in the event of a malfunction. Now edit Zone 01. Delete the existing name (Output01) and assign a unique name for the output (max. 12 characters).
Type Not Used Letter-to-key assignment: The letters and characters can be selected by pressing the keys several times. The cursor goes to the next position after around two seconds. Local E/E Follow Armed Lamp 24 Hour Strobe Strobe Set Confirm the changes by pressing OK. 14.4 Invert output Pulse Set Whether the relevant output is inverted or operates without being inverted can be selected here. Select yes or no. Pulse Unset Setting Complete 14.
User Defined FullSet RDY P1 - P4 Part Set P1 - P4 Full Set P1 - P4 Jamming Perimeter Warning System Fail AC Fail Reporting failure Tampering Burg Any FULL SET This zone can be remote-controlled by various components such as remote control units or the code keypad. The output can also be assigned times at which it is to be activated and deactivated. If this output type is selected, the times at which the output is to be activated or deactivated can be entered at the end (see the note below).
14.8 WAM outputs In the installer menu: Æ Select (RF)Output 03, for example. Æ Select the Edit Output menu item. The WAM wireless outputs can be edited after training the WAM as a wireless transmitter or receiver (function 3). Please note that the disconnected WAM outputs have a maximum load of 500 mA at 24 V. This is an opto-isolator with a forward resistance of 2 Select SEND to send the learn signal to the receiver. Select output 31 using the arrow keys (WAM 1).
Assign a new name and finish data entry by pressing OK. 15. Other Devices The following components can be added under this menu item: External siren Internal siren Select the Type menu item. An overview of output types can be found in chapter 13.5.
15.1 External siren When the sirens have been trained, the alarm centre beeps twice as confirmation. A message is displayed with the siren confirmation and the signal strength value. In the installer menu: Æ Select Ext Sirens Leave this display by pressing Back. If a siren has been trained, then the siren number. Select Add/Del Ext Siren. Leave this display by pressing Back. Select the corresponding Siren. Select “Edit Ext Siren”. Trigger the tamper contact of the siren.
If the external siren should be activated when the relevant partition triggers a local or external alarm, then the partition must be set to Yes. If the receiver beeps twice, the learn message was correctly received. End the learning procedure by pressing Yes. Cancel the process by pressing No. The learn procedure is now started again. No further settings have to be made on the info module or internal siren.
15.2.2 Rdy-to-Set LED 15.3 Add WAM This function must also be set if the info module is equipped with properties of the “Ready” display. This signals that at least one zone in the partition is open (zones connected with “Force Set” property). Proceed as follows: Please ensure that reserved outputs and zones are allocated to each WAM. See the table on reserved WAM outputs and zones.
Select the corresponding accessory module (WAM). In total, up to eight accessory modules can be trained. Select WAM 1. Select a module (e.g. WAM 1). When the WAM is trained, it also transmits its programming so that you can see the function in which the WAM has been trained under “View WAM”. Trigger the tamper contact on the WAM. Function Not Used 1 Wireless Repeater 2 Output Module Trained WAM modules have the symbol next to the WAM number. 3 T/R Module Exit the menu by pressing Back.
15.3.1 WAM as wireless repeater 15.3.4 WAM as siren module WAM function 1 WAM function 4 If the accessory module is trained with the wireless repeater function, then the wireless repeaters whose signals are to be transmitted via this module must also be trained to the WAM. Consult the WAM operating instructions for more information. 15.3.
Trigger the tamper contact on the arming station (see the station operating instructions). When the arming station has been trained, the wireless alarm centre Select the function from the table and allocate it to the arming station key. Confirm the selection by pressing Select. Function Not Used Full Set beeps twice in acknowledgement. At the same time, the graphic display shows the symbol next to the arming station number. 15.4.
15.4.2 Arming station with new function 15.4.3 Switching outputs 15.4.3.1 Using the arming station The arming station can also be used outdoors (IP54). Using the “Instant Set” function, the alarm centre can be activated without any exit delay after entry of the user code. The outputs can be switched using the arming station or the remote control. Each of the four keys on the arming station can be assigned to an output, as can the double-arrow key on the remote control.
Arming station (1) F3 Now program the F3 function key on the arming station. (HW)Output 01 (HW)Output 02 (RF)Output 03 (RF)Output 04 Call up the installer menu. INSTALLER MENU Select Select OTHER DEVICES Other Devices Ext Sirens Info Module/Int Sirens WAM Arming station Select Back Close Arming station (1) F3 On Off Toggle Impulse Under Other Devices, select the Arming station menu point.
15.4.3.2 Using the remote control TC01,T4:User01 Output number (HW)Output... Now program the double-arrow key Internal activation Output number on the remote control. Select Back Select Back Now select the (HW)Output... (HW)Output 01 On Off Toggle Impulse Access the user menu as an administrator. SYSTEM SETTINGS MENU Date & Time Edit Outputs Telecommands Call Downloader Select System setting Select Close Select Back Back Select the Impulse function for output 01.
P.Set ER As 16. Partitions Behaviour of the “Entry Route” zone at internal activation (ER remains ER or ER becomes FE). Behaviour of activation acknowledgement. The options are as follows: OFF – No visual acknowledgement on external siren after successful activation. ON – Visual acknowledgement on external siren after successful activation. Behaviour of deactivation acknowledgement. Programming is made in the same way as activation acknowledgement. Acknowledgement of enabling.
Instant Set Silent Set As Prtn 1 The partition is activated immediately. This exit mode is recommended for activation over remote control or wireless cylinders. Same as the “Timed Set” exit mode, except that no exit signal can be heard during the delay time. This option is available for partitions 2, 3 and 4. When this option is selected, the system uses the same type as for partition 1. 16.
16.5 Internal activation of the partition 16.7 Behaviour of ER zones at internal activation Each individual partition can also be internally activated. This means that you can remain in the building without losing all-round protection. With internal activation, some detectors are not monitored – e.g. motion sensors. The exit mode for internal activation is programmed in the same way as the exit mode for normal activation of the partition.
Batt Load Test Siren in PSet 17.2 Remote control / remote access by telephone Used for activating the battery test function. Used for controlling the siren properties with an internally activated system. Used for activating and deactivating the Force Set function or activating it with a confirmation. Used for setting the response of the wireless siren. Force Set RF Siren Options 17.1 User access Select the corresponding options for the user from the table.
In the event of a deactivated system: “The alarm system is deactivated” In the event of an internally activated system: “The alarm system is activated internally” In the event of an alarm: “An alarm has been triggered” xYou can now listen to the “Voice prompts” of the alarm centre on the phone.
17.3 Selecting a language 17.5 Installer code Select the desired language. Enter the new four-digit installer code. You are then prompted to repeat the new installer code. If both inputs are identical, the new code is stored and is active. 17.4 Default settings Select the corresponding functions from the table. The default installer code is 7890. Security Center recommends changing this code to one of your choice. The system loads all default settings (apart from the access codes) and the log.
17.7 PA response 17.10 Siren Time Select whether an external alarm is also made in the case of a panic alarm (Full), or whether only a telephone message is sent (Silent). Select how long the siren should sound when a local or external alarm is triggered. 17.11 Stray on ent dly 17.8 Auto rearm Additional delay when the entry delay time is exceeded or the entrance to the property differs.
Function Meaning when system is activated No response. Fault is reported by telephone. Deactivated Fault Tamper External alarm. Transmission of supervision failure and tamper. Alarm External alarm. Transmission of supervision failure and alarm. 17.14 Batt Load Test Meaning when system is deactivated No response. Fault is reported on the display and by signal tone. Fault is reported on display and by signal tone. External alarm. Transmission of supervision failure and tamper.
17.19 Time source for the clock 17.16 Force Set Installer menu Æ System options Æ Time source Æ Mains frequency* Crystal xChoose the time source here for synchronising the clock and date. xThe “Crystal” option is sometimes useful if interference frequencies in the mains supply line impact the accuracy of the time. oNote: the accuracy for crystal is approx. ±3.9 min per month.
18. IP Network With an installed GPRS module, the menu contains the following options: When an ethernet or GPRS module is attached, this menu allows the user to allocate the wireless centre an individual IP address. This is then used for IP alarms or the IP download. IP Address Enter the individual IP address of the wireless alarm centre, or leave blank. The IP address consists of four groups. Each group is three digits long and separated from the next group by a “dot”, e.g. “192.168.000.001”.
19.1 Account Name 19. Download settings Select the corresponding function. For a list of functions and their attributes, see the table below. Select “Download”. If no account name is entered here by the software, nothing is displayed here. Function Account Name Connection Type Rings to Answer Answer on 1 ring Access Mode Phone Book IP Network Secure Callback Modem Baud Rate 19.2 Connection Type Meaning The account name is allocated by the download software in order to guarantee a secure connection.
19.3 Rings to Answer 19.5 Access Mode Select which functions are used for the remote maintenance access mode over remote data transmission (see table). Select when the wireless alarm centre should accept a call. To select a number of rings, press Select. Function Call out only If the value is set to 255, the alarm centre never answers the call. 19.4 Answer on 1 ring Secure Callback “Secure Callback” must be deactivated (default) until the first accompanying upload is made.
19.7 IP Network 19.9 Modem Baud Rate If an ethernet module is attached to the wireless alarm centre, then it is possible for the downloader to communicate with the wireless alarm centre using the Internet protocol. This menu allows you to save two IP addresses that can be called by the wireless alarm centre to start a download. The user starts the call by dialling one of the IP addresses. The available options are as follows: Select the baud rate (bps) for data transmission.
20.1 Alarms “Low battery” message for a zone by ALARM and SMS xThe alarm centre only transmits one “Low battery” error message a day for a detector by ALARM and SMS. This occurs separately for each zone. Note: When a battery comes to the end of its service life, the voltage drops when energised (of the detector sending) to below the threshold for “Low battery”.
20.1.1 Call mode 20.1.3 Phone Book (ALARMS) Select the corresponding function. For a list of functions and their attributes, see the table below. Select which number should be changed. Enter the callback number of the command centre that you received for transmitting the respective report. Press the star key to enter a dial pause. Each dial pause interrupts the dial procedure for 3 seconds. Function Deactivated Single Alternate 20.1.
20.1.5 Account numbers 20.1.6 Report Type Enter the account number that you have received for transmitting from the command centre. Select which account number should be changed. Select the report type to be used for digital alarm transmission to the command centre. The command centre usually indicates which type of report to select. The available report types are as follows: Fast Format Channel, Contact ID Reports, SIA Level I, SIA Level II, SIA Level III, Extended SIA Level III and CID in SMS.
Network Error (see note 3) Tamper Alarm Unset (see note 1) Set (see note 1) Zone Omitted (see note 2) Medical Alarm Key Box 20.1.9 SIA Report Mode Select this, then select the Level of the transmission. The following table details which events should be transmitted for the SIA 1 report. 1. Open and close have the same functions as “Open/Close”, but are made on two separate channels. 2. Zone blocked: The wireless alarm centre sends this signal for five seconds when the user blocks a zone. 3.
Battery fault OK Battery missing Battery missing OK ISDN/GSM fault ISDN/GSM fault OK PSTN fault PSTN fault OK Jamming Supervision fault Supervision fault OK RF battery fault Set Internal active Unset Key switch set Key switch unset Download successful Tamper user code Omit zone Man. trigger test report Period. test report Time / day changed Prog. mode start Prog.
Fire control panel OK Fire OK Panic Panic control panel Panic control panel OK Panic OK Duress Burglary Burglary OK Cover tamper contact Cover tamper contact OK Tamper ext. siren Tamper ext.
20.1.17 No Transmission To make a test call once per month, select Reporting -> ALARMS -> Static Test Call -> Monthly. 20.2 Social Care The wireless alarm centre sends a social care message for the following alarm types: Emergency The user presses Social Care on the alarm center or activates an emergency call transmitter (pendant). The wireless alarm centre then reports this to the emergency call centre with the SOCIAL CARE KEY event (SCANCOM channel 2).
20.2.1 Call Mode 20.2.3 Phone Book (Social Care) Select the corresponding function. For a list of functions and their attributes, see the table below. Select which number should be changed. Enter the callback number of the command centre that you received for transmitting the respective report. Press the star key to enter a dial pause. Each dial pause interrupts the dial procedure for 3 seconds.
20.2.5 Report Type 20.2.6 Call Acknowledge Select a report. For a list of report types and their attributes, see the table below. Select whether the social call must be acknowledged by the receiver by pressing DTMF button “5” or not. If the function is disabled, the call is considered to have been transmitted when the called party accepts it. After transmitting the alarm according to the selected digital report type, the wireless alarm centre opens an audio channel.
20.3.3 Messages Select the corresponding function. For a list of functions and their attributes, see the table below. Select the corresponding function. For a list of functions and their attributes, see the table below. Function Call Mode Primary Telecoms Messages Phone Book Trigger Destinations Call Acknowledge Meaning Setting for transmitting voice messages. Settings for the primary transmission path of the voice messages. Recording of messages for voice messages.
Select the Trigger menu point. Select to which of the displayed telephone numbers the voice message should be sent. Mark phone numbers to be called in the event of an trigger for this voice message with YES. After Trigger has been confirmed with the Select button, the following graphic display is shown: (Please note that the home message does not appear. This is always sent by the alarm centre at the start of every transmission.) Five voice messages are available in total.
20.3.8 Alarm call with voice message 20.4.1 Call Mode It may take several seconds until the text message is announced when an alarm call with voice message is received. After the announcement of the text message, an audio connection is established. Consult the following table for details on controlling after establishment of the audio connection. Please remember that an alarm call may need to be confirmed on the telephone by pressing “5” or “9”.
20.4.4 Phone Book Enter the phone numbers to be dialled. Press the star key to enter a dial pause. The dial pause is displayed as a comma. Each dial pause interrupts the dial procedure for 3 seconds. The display can then be used to enter a name for this number. The alarm centre shows these names in the phone book so that you can see which destination was used for the message. 20.4.5 SMS Triggers Select the corresponding function. For a list of functions and their attributes, see the table below.
20.4.7 Destinations 20.5 Reporting Options Select a message where one or more phone numbers should be assigned. 20.5.1 Line Fault This menu can be used to program the system so that it reacts with an acoustic or silent alarm when the alarm centre determines a fault in the remote transmission lines. Select the Line Fault menu item. When a GSM or ISDN module is integrated, then line faults can be set for the PSTN line that is directly attached to the alarm centre or for the installed module.
20.5.2 GSM Omit Digit Reporting = Alarms(L663), Speech Dialler (L247), SMS (L248) For security reasons, this setting has no effect on the reporting of alarms for "Panic" (L561), "Fire" (L560), "Medical" (L620), "Social Emergency" (L571) and "Social Inactivity" (L572). Installer menu Æ Reporting Æ Reporting options Æ GSM omit digit: No* GSM omit digit: Yes If "Yes" is selected, all alarms are reported.
21.2 Monitoring Interval 21. Social Care Select the corresponding function. For a list of functions and their attributes, see the table below. Select the monitoring interval in hours. Within this interval, every detector programmed for activity monitoring must be triggered at least once to avoid the triggering of a social care alarm. Select the monitoring interval so that it is within the monitoring period defined by the monitoring start and end times. Confirm the chosen interval by pressing OK. 21.
Function Local Loudspeaker Keypad Walk Test Detector Signals Ext Sirens WAM Arming Station Outputs Telecommands Pendants PA Detector Tag Secvest Key Meaning Tests the function of the local sirens in the alarm centre. Tests the function of the local loudspeaker in the alarm centre. Tests the keypad input function. Used to go through each trained detector and test its function. Tests the signal strength of the trained detectors. Tests the signal strength of the external sirens.
22.4 Walk Test 22.8 Arming Station A list of all detectors trained to the system is shown on the display. The test of the arming station signal is used for displaying the signal strength. The signal strength should be higher than 3. 22.9 Outputs A list of all outputs installed on the system is shown on the display. Select the output to be tested. Press Done to end the test. When the test is ended, check whether the output has the required status.
22.14Arming Station with SecvestKey functionality 23. Viewing the log A list of log displays can be found in the user manual. Installer Menu Æ Testing Æ Secvest Key Select the corresponding Secvest Key 2WAY wireless cylinder (Door Lock 1, Door Lock 2, Door Lock 3 or Door Lock 4). The wireless cylinder functions and correct positioning of DIP switch 3 to the door hinge in the Secvest Key 2WAY can be tested here. “Unlocked” is shown on the Secvest 2WAY display when the door is unlocked.
the top part around and remove the four housing screws (1) on the bottom. Ensure that you also disconnect the loudspeaker cable and the battery supply cable (2). 25. Installing additional modules Before connecting the ISDN / GSM / ethernet / GPRS module to the alarm centre, disconnect the electric power supply. Firstly, access the installer menu on the alarm centre. This prevents a tamper alarm from being triggered when the top part is removed from the base plate.
26. Fitting the ISDN module 27. Fitting the GSM module Insert the ISDN module carefully and exactly into the base of the ISDN module. Ensure that all base feet are correctly attached to the base holder. Before inserting the GSM module, insert a SIM card into the GSM module. Any SIM cards whose PIN code can be disabled are suitable (or SIM cards with a PIN changed to “0000”). If you have not done so already, insert the SIM card into a mobile phone and deactivate the PIN request (or change it to 0000).
28. Fitting the ethernet module 29. Fitting the GPRS module Insert the ethernet module carefully and exactly into the base of the module. Ensure that all base feet are correctly attached to the base holder. Before inserting the GPRS module, insert a SIM card into the GPRS module. Any SIM cards who support this service and whose PIN code can be disabled are suitable (or SIM cards with a PIN changed to “0000”).
30. Final tasks 32.1 Establishing the local USB-connection Finally, plug the siren plug from the cover of the top part back into the PCB and replace the tamper contact spring. Make sure that the microphone is also exactly located in the top part and place the cover back on the top part. Screw the top part back in place. Reconnect the battery and loudspeaker cables and the connecting cable between the base plate and the top part. Place the top part back on to the base plate and tighten the housing screws.
Power supply The internal power supply meets the requirements of EN50131-6 Type A, Class 2 and Environment Class 2. Connect the other end of the USB cable to your PC or laptop. In the installer menu, go to “Download” . In the “Download” menu, select “Connection Type”. Mains supply voltage: Power consumption: Emergency power supply: Standby time: Maximum recharging time: Power supply monitoring: Fuse: Select “Local” and press “Select” under the display.
Wireless Wireless frequency: Wireless output: Range: Compatibility to EC standards This product meets the safety requirements of the 89/336/EEC, 73/23/EEC and 1999/5/EC EC guidelines (comparison and harmonisation across European member states) on the electromagnetic compatibility and safety of electrical devices used in certain voltage ranges, plus wireless devices and telecommunication terminal devices.
35. Glossary Term / abbreviation ARC Command centre Force Set GPRS GPRS APN GSM ISDN Jamming Line MAC NC NO NTBC PSTN Report S0 Signaller Explanation SMS Alarm and relay command centre. Organisations where alarm and system messages are transferred to in digital form (by telephone). Used as an initial point for intervention measures (police / fire department). Supervision Zones with this attribute are automatically hidden when an alarm system or partition is activated (provided they are open).