Systemair FDR-3G-EX - Atex Fire Damper FDR-3G
A-FDR-3G-EX
Categories
Description
Atex fire dampers represent passive fire protection, designed with the help of compartmentalization to prevent the spread of toxic gases, smoke and fire. Standard fire dampers are designed and certified in accordance with EN 15650 and tested for EIS criteria according to EN 1366–2. Fire dampers together with their installation form an inseparable part of a fire resistivity rating. This Atex version is modified by the 2014/34/EU directive, which sets out the technical requirements for equipment and protective systems intended for use in potentially explosive atmospheres. Atex fire dampers are designed for group II category 2 G and 2 D against the ignition of gas explosion group IIB and dust explosion group IIIB, temperature class T85 °C...T100 °C for Db or temperature class T6...T5 for Gb. Equipment Protection Level Gb and Db according to EN ISO 80079-36.2016. Highlights • Lightweight construction • Tightness class 3C as standard • Suitable for Gas and Dust explosive atmosphere • Inspection opening built-in...
Manuals
# | Title | Languages | Pages | Updated |
---|---|---|---|---|
1 | 1396 CPR 0162GB | EN | 1 | 2022-09-30 |
2 | DeclarationOfPerformance FDR 3G Den GB | CA,EN | 6 | 2022-09-30 |
3 | EUC ExMaxGB | EN | 1 | 2022-09-30 |
4 | EUC ExPro TT | FR | 1 | 2022-09-30 |
5 | EUC RedMaxGB | EN | 1 | 2022-09-30 |
6 | ExMax S BFen GB | EN | 4 | 2022-09-30 |
7 | Form OperatingJournal FireDampers201908 | EN | 4 | 2022-09-30 |
8 | HandBook FDR 3G EX2021 04 27 en GB | EN,HU | 48 | 2022-09-30 |
9 | RedMax S BFen GB | EN | 4 | 2022-09-30 |