Honeywell Pneumatic Thermostat Direct Acting, Single Temperature
TP973A2076
Categories
Description
Note: For one-pipe order an external 0.005 in. restriction. Order cover separately (not included). One- or two-pipe, single temperature, low capacity, pneumatic thermostat used to provide proportional control of pneumatic valves and damper actuators in heating and air conditioning systems. Replacement kits are available for Johnson, Powers, Robertshaw, Barber-Colman, and older Honeywell pneumatic thermostats. Specifications Description: Pneumatic Thermostat Direct Acting Application: Wall Thermostat, Single Temperature Remote Bulb: No Setpoint: Single Action: Direct Number of Pipes: 1 or 2 Setpoint Temperature Range: Day: 59 F to 90 F Sensor Element: Bimetal Maximum Safe Operating Pressure: 25 psi Operating Temperature Range (F): 100F Maximum Throttling Range (F): 2 F to 10 F (factory set 4 F) Airflow Usage: 0.011 scfm (5.2 mL/s) Dimensions: 3-1/4 in. high x 2 in. wide x 1-5/8 in. deep Mounting: wall Features Durable TP970 series thermostat Pilot operated for high capacity Direct Acting (DA) and Reverse Ac...
Manuals
# | Title | Languages | Pages | Updated |
---|---|---|---|---|
1 | Install Instructions | EN,FR | 6 | 2022-03-26 |
2 | Submittal Sheet | EN | 2 | 2022-03-26 |