User manual

60
ENGLISH
ir33 +030220441 - rel. 2.5 - 16.06.10
8.2 Table of alarms and signals: functions enabled/disabled
The following table highlights the functions that are enabled and disabled in the various alarm situations.
Code PD valve Compressor Defrost Evap. fans Cond. fans Continuous cycle
rE Duty setting (c4) Duty setting (c4) unchanged unchanged unchanged unchanged
E0 Duty setting (c4) Duty setting (c4) unchanged unchanged unchanged unchanged
E1 unchanged unchanged unchanged unchanged unchanged unchanged
E2 unchanged unchanged unchanged unchanged unchanged unchanged
E3 unchanged unchanged unchanged unchanged unchanged unchanged
E4 unchanged unchanged unchanged unchanged unchanged unchanged
‘___’ unchanged unchanged unchanged unchanged unchanged unchanged
LO unchanged unchanged unchanged unchanged unchanged unchanged
HI unchanged unchanged unchanged unchanged unchanged unchanged
AFr o o unchanged unchanged unchanged unchanged
IA Duty Setting (A6) Duty setting (A6) unchanged unchanged unchanged unchanged
dA Duty setting (A6) if A7<>0 Duty setting (A6) if A7<>0 unchanged unchanged unchanged unchanged
dEF unchanged unchanged unchanged unchanged unchanged unchanged
Ed1 unchanged unchanged unchanged unchanged unchanged unchanged
Ed2 unchanged unchanged unchanged unchanged unchanged unchanged
Pd unchanged unchanged unchanged unchanged unchanged unchanged
LP o o unchanged unchanged unchanged unchanged
Ats unchanged unchanged unchanged unchanged unchanged unchanged
cht unchanged unchanged unchanged unchanged unchanged unchanged
CHt unchanged o o unchanged unchanged unchanged
dor unchanged unchanged unchanged unchanged unchanged unchanged
Etc unchanged unchanged unchanged unchanged unchanged unchanged
EE o o not performed o o not performed
EF o o not performed o o not performed
HA unchanged unchanged unchanged unchanged unchanged unchanged
HF unchanged unchanged unchanged unchanged unchanged unchanged
n1-n6 unchanged unchanged unchanged unchanged unchanged unchanged
dnL unchanged unchanged unchanged unchanged unchanged unchanged
d1 - d6 unchanged unchanged unchanged unchanged unchanged unchanged
Tab. 8.b
Code
AUX dead zone
AUX light anti-sweat AUX auxiliary anti sweat AUX second step
rE o o o Duty setting (C4)
E0 o o o Duty setting (C4)
E1 unchanged unchanged unchanged unchanged
E2 unchanged unchanged unchanged unchanged
E3 unchanged unchanged unchanged unchanged
E4 unchanged unchanged unchanged unchanged
‘___’ unchanged unchanged unchanged unchanged
LO unchanged unchanged unchanged unchanged
HI unchanged o o unchanged
AFr unchanged unchanged unchanged o
IA o o o Duty setting (A6)
dA o if A7<>0 o if A7<>0 o if A7<>0 Duty setting (A6) if A7<>0
dEF unchanged unchanged unchanged unchanged
Ed1 unchanged unchanged unchanged unchanged
Ed2 unchanged unchanged unchanged unchanged
Pd unchanged unchanged unchanged unchanged
LP unchanged unchanged unchanged o
Ats unchanged unchanged unchanged unchanged
cht unchanged unchanged unchanged unchanged
CHt unchanged o o o
dor unchanged unchanged unchanged unchanged
unchanged unchanged unchanged unchanged
EE o o o o
EF o o o o
HA unchanged unchanged unchanged unchanged
HF unchanged unchanged unchanged unchanged
n1 - n6 unchanged unchanged unchanged unchanged
dnL unchanged unchanged unchanged unchanged
d1 - d6 unchanged unchanged unchanged unchanged
tab. 8.c
CAREL reserves the right to modify or change its products without prior notice.