ir33 +030220441 - rel. 2.5 - 16.06.10
M--- - C 0 14 3
A5 Digital input 2 con guration (DI2) MSYF - C 0 14 0
A6 Stop compressor from external alarm -SYF min C 0 100 0
A7 Enable alarms Ed1 and Ed2 -SYF min C 0 250 0
A8 Digital input 3 con guration (DI3) -SYF ag C 0 1 0
A9 Light management mode with door switch - C 0 14 0
Ado High condenser temperature alarm MSYF ag C 0 1 0
Ac High condenser temperature alarm di erential -SYF °C/°F C 0.0 200 70.0
AE High condenser temperature alarm delay -SYF °C/°F C 0.1 20 10.0
Acd High condenser temperature alarm delay -SYF min C 0 250 0
AF Light sensor OFF time -SYF s C 0 250 0
ALF Antifreeze alarm threshold MSYF °C/°F C -50 200 -5.0
AdF Antifreeze alarm delay MSYF min C 0 15 1
Code Parameter Model UOM Type Min Max Def.
F0 Fan management ---F ag C 0 2 0
F1 Fan start temperature ---F °C/°F F -50 200 5.0
F2 Fan OFF with compressor OFF ---F ag C 0 1 1
F3 Fans in defrost ---F ag C 0 1 1
Fd Fan OFF after dripping ---F min F 0 15 1
F4 Condenser fan stop temperature MSYF °C/°F C -50 200 40
F5 Condenser fan start di erential MSYF °C/°F C 0.1 20 5.0
Code Parameter Model UOM Type Min Max Def.
H0 Serial address MSYF - C 0 207 1
H1 Function of AUX output MSYF ag C 0 13 1
H2 Disable keypad/IR MSYF ag C 1 6 1
H3 Remote control enabling code MSYF - C 0 255 0
H4 Disable buzzer MSYF ag C 0 1 0
H5 Function of AUX output 2 - C 0 13 3
H6 Lock keypad MSYF - C 0 255 0
H7 Select keypad MSYF ag C 0 1 0
H8 Select activation of output with time band MSYF ag C 0 1 0
H9 Enable set point variation with time band MSYF ag C 0 1 0
HPr Print pro le MSYF - C 0 15 0
Hdh Anti-sweat heater o set MSYF °C/°F C -50 200 0.0
Hdn Number of default parameter sets available MSYF - C 0 6 0
Hrl Enable the remote signalling of the status of the
master light relay
MSYF ag C 0 1 0
HrA Enable the remote signalling of the status of the
master auxiliary relay
MSYF ag C 0 1 0
HSA Enable alarms from other devices in the local network MSYF ag C 0 1 0
In Establishes whether the unit is normal, master or
slave
MSYF - C 0 6 0
Code Parameter MSYF UOM Type Min Max Def.
HAn Number of HA events recorded MSYF - C 0 15 0
HA Date/time of last HA event MSYF - C - -
y__ Year Years 0 99 0
M__ Month Months 1 12 0
d__ Day Days 1 7 0
h__ Hours Hours 0 23 0
n__ Minutes Min. 0 59 0
t__ Duration Hours 0 99 0
HA1 Date/time of penultimate HA event MSYF - C - - -
HA2 Date/time of third from last HA event MSYF - C - - -
HFn Number of HF events recorded MSYF - C 0 15 0
HF Date/time of last HF event MSYF - C - - -
y__ Year Years 0 99 0
M__ Month Months 1 12 0
d__ Day Days 1 7 0
h__ Hours Hours 0 23 0
n__ Minutes Min. 0 59 0
t__ Duration Hours 0 99 0
HF1 Date/time of penultimate HF event MSYF - C - - -
HF2 Date/time of third-to-last HF event MSYF - C - - 0
Htd HACCP alarm delay MSYF min C 0 250 0
Code Parameter MSYF UOM Type Min Max Def.
td1 Defrost time band 1 -SYF - C - - -
d__ Day Days 0 11 0
h__ Hours Hours 0 23 0
n__ Minutes Min. 0 59 0
td2 Defrost time band 2 -SYF - C - - -
td3 Defrost time band 3 -SYF - C - - -
td4 Defrost time band 4 -SYF - C - - -
td5 Defrost time band 5 -SYF - C - - -
td6 Defrost time band 6 -SYF - C - - -
td7 Defrost time band 7 -SYF - C - - -
td8 Defrost time band 8 -SYF - C - - -
ton Light/aux on time band -SYF - C - - -
d__ Day Days 0 11 0
h__ Hours Hours 0 23 0
n__ Minutes **** Min. * 0 59 0
toF Light/aux o time band -SYF - C - - -