6.13 Anti-sweat heater function
The anti-sweat heater function is used to maintain the aux1 or aux 2 output, con gured as the light or aux: (H1 or H5= 2, 3, 8, 9)
deactivated while the control temperature (virtual probe) is less than ‘St’+‘Hdh when the instrument is  rst powered up, the ‘HI’ ‘IA
dA ‘CHt’ ‘EE’ ‘EF’ rE’ alarms are reset, or when switching on.
During the aforementioned alarms, the aux1 or aux 2 output, con gured as above, is deactivated. ‘Hdh’ represents the o set from
the set point for the anti-sweat heater function. If ‘Hdh’=0, the anti-sweat heater function is disabled. Note: at the end of the anti-
sweat heater function the outputs con gured as the light or auxiliary can be controlled by the user using the keypad, the supervisor
or the digital inputs.
If the aux1 or aux 2 output is con gured as light or auxiliary on power-up, it maintains the same status as prior to shutdown. If
the anti-sweat heater function is enabled, this is no longer true: on power-up, the output remains o for the entire time that the
function remains active. When the control temperature (virtual probe) reaches the value of ‘St’+‘Hdh, the function ends, activating
the light output and the auxiliary output, irrespective of their status prior to shutdown.
Function active Function with anti-sweat heater
Normal direct or reverse-cycle control Normal operation
Remote o , from supervisor or keypad Function restarted when switching on
Defrost Normal operation
Continuous cycle Normal operation
Temperature alarm monitoring Normal operation
Evaporator fan control Normal operation
Power on Normal operation
Normally-open or normally-closed alarm output Normal operation
Auxiliary output Normal operation
Light output Normal operation
Second evaporator output Normal operation
Control output for pump down valve Normal operation
Condenser fan control output Normal operation
Second delayed compressor output Normal operation
Auxiliary output with switch o Normal operation
Light output with switch o Normal operation
No function associated with the AUX output Normal operation
Reverse output in control with dead band Normal operation
Second compressor step output Normal operation
Second compressor step output with rotation Normal operation
Door switch with compressor, fan o and light management Normal operation
Door switch with compressor o and light management Normal operation
Curtain switch with set point variation and light management Normal operation
Light sensor and light management Normal operation
Auxiliary output activation switch Normal operation
Door switch with compressor, fan o , no light management Normal operation
Door switch with compressor o , no light management Normal operation
Light activation from keypad or supervisor Normal operation
Auxiliary activation from keypad or supervisor Normal operation
Alarms See table of alarms and signals
Virtual control probe alarm Function restarted.
Product probe alarm Normal operation
Defrost probe alarm Normal operation
Condenser probe alarm Normal operation
Antifreeze probe alarm Normal operation
Tab. 6.o
6.14 Antifreeze alarm
The antifreeze alarm is only active if a probe has been set as the antifreeze probe, /Ax = 4 (x=2-5).
ALF de nes the temperature value below which the antifreeze alarm and AFr is activated, delayed by the time set for parameter
AdF. The alarm is reset manually or from the supervisor. This condition involves the deactivation of the compressor and the
activation of the alarm relay, if H1=0, 1.
Function active
Function in antifreeze
Normal direct or reverse-cycle control Normal operation
Remote o , from supervisor or keypad Function disabled (timer restarted)
Defrost Normal operation
Continuous cycle Sospeso o pendente
Temperature alarm monitoring Normal operation
Evaporator fan control Normal operation
Power on Normal operation
Normally-open or normally-closed alarm output Output energised with AFr’
Auxiliary output Normal operation
Light output Normal operation
Second evaporator output Normal operation
Control output for pump down valve Normal operation
Condenser fan control output Normal operation
Second delayed compressor output Normal operation
Auxiliary output with switch o Normal operation
Light output with switch o Normal operation
No function associated with the AUX output Normal operation
Reverse output in control with dead band Normal operation
Second compressor step output Normal operation
Second compressor step output with rotation Normal operation
Door switch with compressor, fan o and light management Normal operation
Door switch with compressor o and light management Normal operation
Curtain switch with set point variation and light management Normal operation
Light sensor and light management Normal operation
Auxiliary output activation switch Normal operation