6.6.7 Dripping
The dripping time is set by parameter dd, when the compressor is OFF and the fans are OFF. At the end of dripping time, the post-
dripping phase starts with the fans OFF (Fd):
the compressor restarts normal operation;
the fans remain o .
If the post-dripping time with fans OFF is set to zero, normal control is resumed directly.
6.6.8 Post-dripping (fans OFF)
The post-dripping time with fans OFF is set by parameter Fd. At the end of the post-dripping time with the fans OFF, normal
control resumes.
Notes on the defrost function
If defrost with RTC is selected, the parameter dI has no e ect. In any case, the dI timer is updated and the parameter becomes
valid on all days only in the event of RTC alarms. The parameter dI should therefore be set for safety reasons.
The timer used to determine the defrost interval dI is updated cyclically when reaching the end of the interval, thus enabling
cyclical defrosts. The timer is also updated when the unit is OFF. If the timer dI expires when the unit is OFF, a defrost is
performed when the unit is started. If an “RTC” or manual defrost is run from the keypad or the supervisor, the timer linked to
dI is not reset at the start of the defrost. Consequently, at the end of the defrost, the dI timer may expire, and another defrost
may be performed. If a defrost is run from the digital input, with the compressor running time algorithm, or from the supervisor
in Slave controllers, the timer dI is reset when the defrost request is generated. In this way, the defrost interval is a timeout
for the generation of the defrost requests (used, for example, when the external timer is not working correctly). If defrost on
start-up (d4) has been selected, and a defrost on start-up delay (d5) has been set, the timer dI must be set to the end of the
defrost delay on start-up. For units programmed in the same way, and with the same value of dI’ and di erent values of d5’, this
enables the defrosts at start-up to be distributed through time, and the time staggering of the defrosts to be maintained for
the subsequent events too. If control with 2 compressor steps is selected (with or without rotation, H1 = 12 or 13) the hot gas
defrost requires the activation of the 2 steps, while the heater defrost deactivates the steps.
Function active Function with defrost
Normal direct or reverse-cycle control On hold
Remote o , from supervisor or keypad When o the defrost is terminated
Defrost Normal operation
Continuous cycle If required, the request remains during the
defrost
Temperature alarm monitoring Normal operation
Evaporator fan control Normal operation
Power on Normal operation
Normally-open or normally-closed alarm output Normal operation
Auxiliary output Normal operation
Light output Normal operation
Second evaporator output Normal operation
Control output for pump down valve Normal operation
Condenser fan control output Normal operation
Second delayed compressor output Normal operation
Auxiliary output with switch o Normal operation
Light output with switch o Normal operation
No function associated with the AUX output Normal operation
Reverse output in control with dead band Normal operation
Second compressor step output On hold
Second compressor step output with rotation On hold
Door switch with compressor, fan o and light management Normal operation
Door switch with compressor o and light management Normal operation
Curtain switch with set point variation and light management Normal operation
Light sensor and light management Normal operation
Auxiliary output activation switch Normal operation
Door switch with compressor, fan o , no light management Normal operation
Door switch with compressor o , no light management Normal operation
Light activation from keypad or supervisor Normal operation
Auxiliary activation from keypad or supervisor Normal operation
Alarms See table of alarms and signals
Virtual control probe alarm Normal operation
Product probe alarm Normal operation
Defrost probe alarm Defrost ended due to timeout.
Condenser probe alarm Normal operation
Antifreeze probe alarm Normal operation
Tab. 6.h