User manual

20
ENGLISH
ir33 +030220441 - rel. 2.5 - 16.06.10
6.3 Switching the controller ON and OFF
The unit can be switched ON/OFF from a number of sources; keypad, supervisor and digital input. In this operating mode, the
display will be show the temperature selected for parameter /tI, alternating with the OFF message. The digital input can be used
to switch the controller on/o , setting parameter A4/A5/A9 to “6”. Switching on/o from digital input has priority over the same
function from the supervisor and from the keypad.
Origin Priority Note
Digital input Priority 1
Disable On/O from keypad and supervisor
Keypad Priority 2
Supervisor Priority 3
Tab. 6.c
Important: if there is more than one digital input selected as the On/O function (A4 and A5 = 6), the ON status will be activated
when all the digital inputs are closed. If event one contact is open, the unit is switched OFF.
Function Enabled Disabled
compressor control (pump down valve OFF and shut)
AUX control (H1= 11) with dead band
second compressor step control with and without rotation (H1= 12, 13)
defrost (cyclical and manual)
fan control
fan control at low relative humidity (if enabled)
continuous cycle
condenser fan control (if enabled)
low temperature alarm (LO, alarm reset, and monitoring initialised)
high temperature alarm (HI, alarm reset, and monitoring initialised)
immediate alarm from external contact (IA, alarm reset and monitoring initialised)
delayed alarm from external contact (dA, alarm reset and monitoring initialised)
defrost ended due to timeout alarm (Ed1 and Ed2, alarm reset)
pump down ended due to maximum time alarm (Pd, alarm reset)
low pressure from external contact alarm (LP, alarm reset and monitoring initialised)
autostart alarm in pump down (AtS, alarm reset and not displayed)
pre-alarm: high condenser temperature (cht, alarm reset, and monitoring initialised)
high condenser temperature alarm (Cht, alarm reset, and monitoring initialised)
door open for too long alarm (dor, alarm reset)
antifreeze alarm (AFr, alarm reset)
HA HACCP alarm (alarm reset, and monitoring initialised)
HF HACCP alarm (alarm reset, and monitoring initialised)
buzzer (OFF) and alarm relay (non-alarm status)
HACCP control
defrost according to programmed time bands
defrost according to compressor running time (if enabled)
defrost from digital input (if enabled)
defrost from keypad and supervisor
defrost started from digital input (if enabled)
direct/reverse from digital input (if enabled).
modi cation and display of frequent and con guration parameters and the set point
ON/OFF auxiliary relay 1 and 2 (set as LIGHT or AUX)
select the probe displayed (model M only)
compressor autostart in pump down (if enabled)
door switch (with fan and compressor shutdown) limited to light management
remote ON/OFF
curtain switch, limited to light management
door switch (with fan shutdown only) limited to light management
management of the light sensor
updating of the defrost interval timer dI”
control probe error (rE)
probe 1 error (E0)
probe 2 error (E1)
probe 3 error (E2)
probe 4 error (E3)
probe 5 error (E4)
clock alarm (Etc)
EEPROM alarm, unit parameters (EE)
EEPROM alarm, operating parameters (EF)
light or AUX on/o based on the set time bands
modi cation of the set point based on the set time bands
Tab. 6.d
Note: In the OFF status, the defrost interval dI’ is always updated, to maintain the regularity of the interval. If a defrost interval expires during the OFF status, this event is saved and, when controller is switched back ON, a defrost
request is generated.
The controller switches from ON to OFF with the following sequence:
the compressor protection times are observed;
the pump down procedure is performed (if enabled);
the defrost is forced OFF and will not resume when switched back ON;
the continuous cycle is forced OFF and will not resume when switched back ON.
The controller switches from OFF to ON with the following sequence:
the compressor protection times are observed;
the defrost on start-up (if enabled) is not performed, as this in fact refers to power-up;
the compressor and fan delays on start-up are not set.
OFF status: