Instruction manual
36
CommerCial low-pressure regulators
TYPE CS400 TYPE CS800
TYPE CS200
Regulator Technologies has a wide range of low-pressure regulators
to meet almost any commercial or industrial application. For ease
of reference, only the most popular commercial and industrial
regulators are shown on this page. Other ori ce sizes, body sizes
and outlet pressure ranges are available. See the product guides on
pages 37 and 39. The Commercial Service (CS) Regulator Series
have a temperature rating of -20 to 160°F / -29 to 71°C, but have
passed Fisher
®
internal testing for lockup, relief start-to-discharge
and reseal down to -40°F / -40°C.
Note: Because of various spring ranges and orifi ce sizes, all
commercial and industrial regulators should be individually
sized for the particular installation. Consult specifi c product
bulletins for maximum pressures ratings. Contact your local
LP-Gas Equipment Distributor for assistance.
Type CS400 – The Type CS400 is a medium capacity low-pressure,
direct-operated regulator designed for loads up to 7,800,000 BTU
per hour / 88 SCMH, ideal for installations at schools, bakeries and
many other commercial/industrial applications. Available in 1-1/4,
1-1/2 and 2-inch body sizes with spring ranges from 4.5 inches w.c.
to 5.5 psig / 11 mbar to 0.38 bar.
Low-Pressure Commercial Regulators
TYPE NUMBER
CAPACITIES (PROPANE)
(1)
ORIFICE SIZE
INLET AND OUTLET
CONNECTIONS,
INCH
OUTLET
PRESSURE RANGE
OUTLET PRESSURE
SETTING
MAXIMUM OPERATING
INLET PRESSURE
BTU / hour SCMH Inch mm psig bar psig bar psig bar
CS200IR-6EC1 2,500,000 28
1/2 12.7
3/4 FNPT
10 to 14
inches w.c.
25 to 35
mbar
11 inches
w.c.
27 mbar
40 2.8CS200IR-6EC3 3,800,000 43 1 FNPT
CS200IR-6EC6 3,900,000 44 1-1/4 FNPT
CS400IR-8EC6 6,800,000 76
3/4 19.1
1-1/4 FNPT
20 1.4CS400IR-8EC7 7,600,000 85 1-1/2 FNPT
CS400IR-8EC8 7,600,000 85 2 FNPT
CS800IR-8CC7 10,460,000 118
1 25.4
1-1/2 FNPT
8 to 12
inches w.c.
20 to 30
mbar
30 2.1
CS800IR-8CC8 21,809,000 245 2 FNPT
CS200IR-6HC1 3,760,000 42
1/2 12.7
3/4 FNPT
1 to 2 0.06 to 0.14
2 0.14
40 2.8CS200IR-6HC3 4,780,000 54 1 FNPT
CS200IR-6HC6 5,327,000 60 1-1/4 FNPT
CS400IR-8HC6 9,715,000 109
3/4 19.1
1-1/4 FNPT
20 1.4
CS400IR-8HC7 10,500,000 118 1-1/2 FNPT
CS400IR-8HC8 8,775,000 99 2 FNPT
CS820IR-8FC7 15,011,000 169
1 25.4
1-1/2 FNPT
1 to 2.5 0.06 to 0.17 30 2.1
CS820IR-8FC8 21,436,000 241 2 FNPT
CS400IR-8IC6 7,365,000 83
3/4 19.1
1-1/4 FNPT
2 to 5.5 0.14 to 0.38
5 0.35
20 1.4CS400IR-8IC7 6,895,000 77 1-1/2 FNPT
CS400IR-8IC8 7,365,000
(2)
83
(2)
2 FNPT
CS820IR-8HC7 15,262,000 171
1 25.4
1-1/2 FNPT
2.5 to 5.5 0.17 to 0.38 30 2.1
CS820IR-8HC8 16,532,000 186 2 FNPT
1. Capacities are based on 10 psig / 0.69 bar and 2 inches w.c. / 5 mbar droop.
2. Capacities are based on 10 psig / 0.69 bar and 20% droop.
NOTE: Additional combinations of body sizes, spring ranges and ori ce sizes are available. See guides on page 37. Consult your LP-Gas Equipment distributor for more information.
Type CS200 – The Type CS200 is a medium capacity low-pressure,
direct-operated regulator designed for loads up to 3,800,000 BTU per
hour / 44 SCMH, ideal for installations on smaller commercial/industrial
applications. Available in 3/4, 1 and 1-1/4-inch body sizes with spring
ranges from 3.5-inches w.c. to 2 psig / 9 mbar to 0.14 bar.
Flanged Bodies – The Types CS400 and CS800 are available with
a fl anged body. Flanges are available in 2-inch / DN 50 body size and
CL125 FF end connection.
Type CS800 – The Type CS800 is a direct-operated, spring-loaded
regulator which has been engineered for low-pressure commercial
service applications. This regulator can accommodate up to 21,600,000
BTU per hour / 243 SCMH of fl ow capacity and is available in 1-1/2 and
2-inch body sizes with 8-inches w.c. to 5.5 psig / 20 mbar to 0.38 bar
pressure ranges.
Note: Types CS200, CS400 and CS800 regulators should be
installed with additional/external overpressure protection. These
units when installed as part of a two-stage system in fi xed piping
serving 14 inches w.c. / 35 mbar appliance systems require
additional overpressure protection to make the system compliant
with NFPA 58 requirements for a two-stage system. Please consult
with your LP-Gas Equipment Distributor for more information.