Instruction manual
27
Integral Two-Stage regulators combine a First-Stage regulator and
a Second-Stage regulator into one compact unit. Recommended
for installations where piping distance is short, integral Two-Stage
regulators provide all of the advantages of Two-Stage regulation
(refer to page 23). Fisher
®
brand integral Two-Stage regulators
are color coded gray for easy identi cation. Vents are screened
with standard Second-Stage vent orientation over the outlet.
The Types R632A and R232A rst-stage screened vent is threaded
to accept a 1/4-inch OD copper tube inverted fl are with a
7/16-24 UN thread. The Types R232A and R632A have a
temperature rating of -20 to 160°F / -29 to 71°C, but have passed
Fisher internal testing for lockup, relief start-to-discharge and reseal
down to -40°F / -40°C.
Type R632A – is an Underwriters Laboratories (UL
®
) listed regulator
with a capacity of up to 950,000 BTU per hour / 10.7 SCMH,
recommended for on-site cylinder installations, mobile homes and
domestic installations, where separation of the First and Second-
Stage is not cost effective. This unit offers a POL inlet connection for
the easy drop-in replacement of Single-Stage regulators.
Type R632A’s high capacity relief valve and large 3/4-inch screened
vent limit downstream pressure to less than 2 psig / 0.14 bar in
an overpressure situation as required by NFPA 58. Type R632A is
adjustable from 9 to 13 inches w.c. / 22 to 32 mbar, with a factory
setpoint of 11 inches w.c. / 27 mbar. The Type R632A features
include the 20-year recommended replacement life.
Type R632A has 1/8-inch NPT built-in gauge taps ori ced to a
No. 54 drill size, on the upstream and downstream sides. These taps
provide easy access for testing the proper operation of the
First and Second-Stage while the system is pressurized. This
regulator also features a large 3/4-inch drip-lip vent to reduce the
chance of blockage by freezing rain or sleet when properly installed
with the vent pointing down.
Type R232A – Designed for installations with small capacity loads
up to 550,000 BTU per hour / 6.2 SCMH. With an overall length
of 6.5 or 7 inches / 165 or 178 mm for NPT or FPOL connections
respectively, this compact unit ts easily into con ned spaces
and is ideal for ASME tanks used on small domestic loads.
Intermediate and outlet gauge taps facilitate easy system testing.
A 3/8-inch NPT vent allows easy installation of vent piping. Use
of a valve stem and lever provide stable regulation and excellent
durability. A large fabric-reinforced diaphragm provides accurate
regulation. The large ori ce assists in minimizing freeze problems.
Stainless steel internal and corrosion resistant coatings provide
excellent corrosion resistance. The Type R232A also has the design
that provides a recommended replacement life of 20 years.
Twin Cylinder Installations – The Type R232A can also be used
on twin cylinder hook-ups found on travel trailers and stationary
applications. These units offer a drip-lip vent style for installations
without a vent protector. Proper installation requires the vent to be
pointed down in a vertical position. Additional protection may be
required if road splatter is a problem.
integral two-stage regulators
Integral Two-Stage Regulators
TYPE NUMBER
CAPACITIES (PROPANE)
(1)
INLET
CONNECTION,
INCH
OUTLET
CONNECTION,
INCH
OUTLET
ADJUSTMENT RANGE
OUTLET
PRESSURE SETTING
BTU / hour SCMH Inch w.c. mbar Inch w.c. mbar
R232A-BBF
550,000 6.2
1/4 FNPT
1/2 FNPT 9.5 to 13 24 to 32
11 27
R232A-BBFXA
(2)
R232A-HBF
FPOL
R232A-HBFXA
(2)
R632A-BCF
850,000 9.6
1/4 FNPT
1/2 FNPT
9 to 13 22 to 32
R632A-BCFXA
(2)
R632A-CFF
950,000 10.7 3/4 FNPT
R632A-CFFXA
(2)
R632A-HCF
850,000 9.6
FPOL
1/2 FNPT
R632A-HCFXA
(2)
R632A-JFF
850,000 9.6 3/4 FNPT
R632A-JFFXA
(2)
1. Based on 30 psig / 2.1 bar inlet pressure and 2 inches w.c. / 5 mbar droop.
2. First and Second-Stage spring case vents opposite gauge taps.
TYPE R232A
TYPE R632A
TYPE R632A