EUKC 09, 12, 18, 24 R by johnson controls Ref: GB Duct Multisplit Inverter Installation Instructions Johnson Controls Manufacturing España, S.L. is participating in the EUROVENT Certification Programme. Products are as listed in the EUROVENT Directory of Certified Products, in the program AC1, AC2, AC3, LCP and FC.
User Notice The total capacity of the indoor units which runs at the same time can not exceed 150% of that of the outdoor units; otherwise, the cooling (heating) effect of each indoor unit would be poor. Switch the main power on 8 hours before start the unit, helpful for a successful startup. It is a normal phenomenon that the indoor unit fan will still run for 20~70 seconds after the indoor unit receives the “stop” signal so as to make full use of after-heat for the next operation.
by johnson controls Contents Safety Precautions....................................................................................... 4 Installation Location and Matters Needing Attention ................................. 5 1 2 3 4 How to select the installation location for the indoor unit .................................. 5 Electric Wiring ..................................................................................................... 5 Earthing Requirements ......................................
by johnson controls Safety Precautions Ⅰ Safety Precautions Please read this manual carefully before use and operate correctly as instructed in this manual. Please especially take notice of the following two symbols: Warning! It indicates improper operation which will lead to human casualty or sever injury. Cuation! It indicates improper operation which will lead to injury or property damage.
by johnson controls Installation Location and Matters Needing Attention Installation Location and Matters Needing Attention The installation of the unit must comply with the national and local safety regulations. The installation quality directly affects the normal use, so the user should not carry out the installation personally. Instead, the installation and debugging should be done by the professional personnel. Only after that, can the unit be energized.
by johnson controls Installation Location and Matters Needing Attention ① Running water pipe; ② Coal gas pipe; ③ Sewage pipe; ④ Other places where the professional personnel think unreliable. 4 Accessories for Installation Refer to the packing list for the accessories of the indoor and outdoor units respectively.
by johnson controls Installation Instructions Installation Instructions 1 Outline Dimension Drawings of the Indoor Unit Note Fig.1 is applicable to EUKC(09)R, EUKC(12)R, EUKC(18)R, EUKC(21)R, EUKC(24)R Model EUKC(09)R EUKC(12)R EUKC(18)R EUKC(21)R EUKC(24)R Item : Fig.
by johnson controls Installation Instructions 3 Installation of the Indoor Unit a. 1) 2) 3) 4) Requirements on the Installation Location Ensure the hanger is strong enough to withstand the weight of the unit. The drainage of the drain pipe is easy. No obstacle is in the inlet/outlet and the air circulation is in good condition. Ensure the installation space shown in Fig.2 is left for the access to maintenance.
by johnson controls Installation Instructions ② . If there is an opening in the ceiling, it is better to reinforce it to keep it flat and prevent it vibrating. Consult the user and builder for more details. ③ . If the strength of the ceiling is not strong enough, a beam made of angle iron can be used and then fix the unit on it. ④ . If the indoor unit is not installed in the air conditioning area, please use sponge around the unit to prevent condensing.
by johnson controls Installation Instructions 1 2 3 4 5 6 Fig.8 7 9 8 No. Name No. Name 1 Hanger 6 Transition Duct 2 Return Air Duct 7 Air Supply Duct 3 Canvas Duct 8 Diffuser 4 Return Air Louver 9 Diffuser Joint 5 Air Supply Outlet Table 3 c. Installation Steps of the Round Air Supply Duct 1) Preinstall the outlet of the round duct on the transiti 2) Place the transition duct to the air outlet of the unit a .
by johnson controls Installation Instructions Table 4 Dimensions of the Air Supply Outlet and Return Air Inlet (unit: mm) Model Air Supply Outlet Item EUKC(09)R EUKC(12)R EUKC(18)R EUKC(21)R EUKC(24)R Return Air Inlet A B C D 156 662 580 162 156 862 780 162 156 1062 980 162 7 Installation of the Return Air Duct a. in the bottom, as shown in Fig.11. Rectangular Flange Backward Return Air Downward Return Air Return Air Cover Plate Fig.11 b. cover plate. c.
by johnson controls Installation Instructions 8 Installation of the Condensate Pipe a. The condensate pipe should keep a inclination angle of 5~10° , which can facilitate the drainage of the condensate water. And the joints of the condensate pipe should be insulated by the insulation material to prevent condensing(see Fig.13). Insulating Layer for the Condensate Pipe Pipe Lid Fig.13 Thermal Insulation of the Condensate Pipe b. There is a condensate outlet on both left and right sides of the unit.
by johnson controls Installation Instructions (Right) with a min. degree of slope 1/100 (Wrong) Fig.14 e. Insert the drain hose into the drain hole and tighten it with clamps. f. Wrap the clamps with large amount of sponge for thermal insulation. g. The drain hose inside the room also should be insulated. Clamp (accessory) Sponge (accessory) Clamp (accessory) Sponge (gray)D rain Hose Max. 4mm Fig.15 11 Precautions for the Lift Pipe The installation height of the lift pipe should be less than 850mm.
by johnson controls Installation Instructions I - Joint of drain pipe Drain Hose (accessory) Max.75mm Max.1000mm The specification of the joint of the drain pipe should be suitable to the running capacity of the unit Fig.17 12 Test for the Drainage System a. After the electric installation, please take a test for the drainage system. b. During the test, check if the water flow goes through the pipe correctly and observe carefully the joint to see if it leaks or not.
by johnson controls Installation Instructions d. Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape. CUATION ! ① . During the connection of the indoor unit and the refrigerant pipe, never pull any joints of the indoor unit by force; otherwise the capillary pipe or other pipe may crack, which then would result in leakage. ② . The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of it.
by johnson controls Installation Instructions crimpling pliers. 4) Let the screw go through the terminal of the multi-core wire and then fix it on the wiring board. Fig.20 WARNING! ① . If the power cord or the signal line is damaged, they must be replaced with the dedicated one. ② . Prior to the wiring, please check the voltage marked on the nameplate and then carries out the wiring following the wiring diagram. ③ .
by johnson controls Installation Instructions ERJC(36)R INDOOR UNIT A XT5X POWER INDOOR UNIT B T4 INDOOR UNIT C INDOOR UNIT D XT3X N L T2 XT1 OUTDOOR UNIT Fig.21 ERJC(42)R INDOOR UNIT D XT5 INDOOR UNIT C XT4 INDOOR UNIT B XT3 INDOOR UNIT A XT2 OUTDOOR UNIT INDOOR UNIT E XT6 L N POWER XT1 Fig.
by johnson controls Installation Instructions 17 Wiring of the Signal Line of the Wired Controller 1) Open the cover of the electric box of the indoor unit. 2) Let the signal line go through the rubber ring. 3) Insert the signal line to the four-pin socket on the printed circuit board of the indoor unit. 4) Fix the signal line with the binding wire.
by johnson controls Rated Working Conditions Ⅳ Rated Working Conditions Table 8 Working Temperature Range Indoor side state Outdoor side stae Dry bulb temp. ℃ Wet bulb temp. ℃ Dry bulb temp. ℃ Wet bulb temp. ℃ Rated Cooling 27 19 35 24 Max. cooling 32 23 48 26 Min. cooling 21 15 18 — Rated Heating 20 15 7 6 Max. heating 27 — 24 18 Min.
by johnson controls Error Analysis Ⅴ Error Analysis If your conditioning unit runs abnormally, please check the following items before contact the maintenance serviceman. Table 9 Errors Failed startup Possible Causes There is no power supply. The breaker opens owing to electrical leakage. Voltage is too low. Stop after a short while of operation The air inlet/outlet of the indoor/outdoor unit is clogged. Poor cooling effect The air filter screen is too dirty or clogged.
by johnson controls Maintenance Ⅵ Maintenance CAUTION! Take notice of the following items before clean your air conditioning unit. ① . Cut off the main power supply before contact any wiring device. ② . Only when the unit is turn off and the main power supply is cut off, can the unit be cleaned; otherwise it would cause an electric shock or injury. ③ . Do not wash the unit with water; or it may cause an electric shock. ④ .
by johnson controls 22
DECLARACION CE DE CONFORMIDAD SOBRE MAQUINAS FABRICANTE: JOHNSON CONTROLS MANUFACTURING ESPAÑA, S.L. DIRECCIÓN: Paseo Espronceda, 278, 08204 SABADELL Certificamos que el equipo descrito, ha sido diseñado, fabricado y probado de conformidad con los requisitos básicos de la Directiva de Equipos a presión 97/23/CEE y sus correspondientes módulos de aplicación.