INSTALLATION INSTRUCTIONS
SERIES RSS AND RSSP STROBE APPLIANCES
(WALL MOUNT VERSIONS)
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
Wheelock’s Series RSS and RSSP Strobes can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm
Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync
Module (DSM) or Power Supply (PS-12/24-8). The Series RSS and RSSP Strobe Appliances are UL Listed under Standard 1971
(Signaling Devices for the Hearing Impaired) for indoor fire protection service. These Strobes are listed for wall mount only,
with the
backboxes specified in these instructions (See Mounting Options). RSS models have an integrated Strobe Mounting Plate (SMP) that
can be mounted to a single-gang, double-gang, 4” backbox, 100mm European backbox or SHBB surface backbox. The strobes use a
Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective
visible signaling. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by the FACP.
NOTE: All CAUTIONS and WARNINGS are identified by the symbol
. All warnings are printed in bold capital letters.
WARNING: THE RSS STROBE APPLIANCE IS A "FIRE ALARM DEVICE - DO NOT PAINT."
WARNING: READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE
FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION,
INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD
RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
Table 1: Ratings Per UL 1971
Model
Regulated
Voltage
VDC/VRMS
Voltage
Range Limit
VDC/VRMS
Strobe
Candela
(CD)
Mounting
Options
RSS-2415W 24 16.0-33.0 15 A,B,C,D
RSSP-2415W 24 16.0-33.0 15 E,F
RSS-2430W 24 16.0-33.0 30 A,B,C,D
RSSP-2430W 24 16.0-33.0 30 E,F
RSS-2475W 24 16.0-33.0 75 A,B,C,D
RSSP-2475W 24 16.0-33.0 75 E,F
RSS-24110W 24 16.0-33.0 110 A,B,C,D
RSSP-24110W 24 16.0-33.0 110 E,F
RSS-1215W 12 8.0-17.5 15 A,B,C,D
RSSP-1215W 12 8.0-17.5 15 E,F
NOTE: THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE
MAXIMUM NUMBER OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47.
WARNING: THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS
FOR 24V MODELS AND 8-17.5 VOLTS FOR 12V MODELS USING FILTERED (DC) OR UNFILTERED FULL-WAVE
RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY
BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE
THE APPLIED VOLTAGE TO THE STROBES.
Copyright 2001 Wheelock, Inc. All rights reserved.
Table 1A.
Audibles/Speakers for RSSP Strobe/Plate
Product Series
Multitone Appliances AMT, MT, MT4
Motor Bells MB-G6/G10
Speakers
ET-1010/1070/1080, ET70,
E7025/7070, E70
Chimes CH70
NOTES:
1. Strobes will produce 1 flash per second over the “Regulated
Voltage” range.
2. All models are UL Listed for indoor use with a temperature
range of +32
o
F to +120
o
F (0
o
C to +49
o
C) and maximum
humidity of 85% RH.