EG-30 thru -75 PEG-30 thru -65 Gas-Fired Boilers – Series 4 Control supplement – Standing pilot For additional information, refer to . . . EG•PEG•EGH Boiler manual for Natural or Propane gas (tankless heater application optional) This supplement must only be used by a qualified heating installer/service technician. Before installing, read all instructions, including this supplement, the boiler manual and any related documents. Perform steps in the order given.
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Please read this page first! Hazard definitions The following defined terms are used throughout these instructions to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product. Indicates presence of hazards that will cause severe personal injury, death or substantial property damage.
Standing Pilot Boilers — Control Supplement Table of contents Hazard definitions and Note to the installer.....................................................................................2 Control installation — EG-30 thru -75 water boilers without tankless heaters......................... 4-5 Control installation — EG-30 thru -65 water boilers with tankless heaters............................... 6-7 Control installation — EG-30 thru -75 and PEG-30 thru -65 steam boilers with probe............
Part Number 550-110-032/0706 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4
Standing Pilot Boilers — Control Supplement Control installation For your safety, turn off electrical power supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial property damage. EG-30 thru -65 water boilers without tankless heaters 1. Mount and wire controls per wiring diagram, page 4, and Figure 1. Figure 1 a. Attach junction box inside left jacket panel with #8-32 x ½” machine screws provided.
Part Number 550-110-032/0706 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4
Standing Pilot Boilers — Control Supplement Control installation continued For your safety, turn off electrical power supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial property damage. EG-30 thru -65 water boilers with tankless heaters 1. Mount and wire controls per wiring diagram, page 6, and Figure 3. Figure 3 a. Install combination limit control and relay in tapping.
Part Number 550-110-032/0706 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4
Standing Pilot Boilers — Control Supplement Control installation continued For your safety, turn off electrical power supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial property damage. EG-30 thru -65 and PEG-30 thru -65 steam boilers with probe-type low water cutoff 1. Mount and wire controls per wiring diagram, page 8, and Figure 4. Figure 4 a.
Part Number 550-110-032/0706 EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4
Standing Pilot Boilers — Control Supplement Control installation continued For your safety, turn off electrical power supply and turn off external gas supply valve before attempting to work on the boiler. Failure to comply can cause severe personal injury, death or substantial property damage. EG-30 thru -65 steam boilers with float-type low water cutoff 1. Mount and wire controls per wiring diagram, page 10, and Figure 6. Figure 6 a.
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Damper installation Once damper is installed, boiler will not operate without a damper installed. Only dampers listed in the Replacement parts table on page 24 are approved for use on EG and PEG Series 4 standing pilot boilers. Any other vent damper installed could cause severe personal injury or death. The following boiler models must have damper installed: • EG-30 thru EG-65, natural or propane gas. • PEG-30 thru PEG-65, steam, natural gas.
Standing Pilot Boilers — Control Supplement Damper installation continued Minimum clearances to combustibles Provide a minimum of 6” between the vent damper and any combustible material. (Provide a minimum of 46” between jacket top and combustible ceiling.) See EG • PEG • EGH Boiler manual for complete clearance requirements. Installation Do not modify draft hood or damper, or make another connection between draft hood and damper or boiler except as noted below.
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Checkout procedure 1. See pages 15-18 for “Lighting Instructions”. 2. Raise room thermostat to call for heat. Damper actuator will slowly open damper. 3. When damper is fully open, main gas valve will open and main burners will ignite. Damper must be fully open before main burners light. If damper does not fully open, flue products will escape into house, causing severe personal injury or death. 4. Lower thermostat setting.
Standing Pilot Boilers — Control Supplement Lighting instructions — Robertshaw 7200 Part Number 550-110-032/0706 15
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Lighting instructions — Honeywell VR8200/VR8300 Natural gas boilers only 16 Part Number 550-110-032/0706
Standing Pilot Boilers — Control Supplement Lighting instructions — Honeywell VR8200/VR8300 Propane boilers only Part Number 550-110-032/0706 17
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Lighting instructions — Robertshaw 7000ERHC 18 Part Number 550-110-032/0706
Standing Pilot Boilers — Control Supplement Troubleshooting Burner access panel must be in position during boiler operation to prevent momentary flame rollout on ignition of main flame. Severe personal injury or substantial property damage will result. Never jumper (bypass) any device except for momentary testing as outlined in Troubleshooting Charts. Substantial property damage and/or severe personal injury could occur. Label all wires prior to disconnection when servicing controls.
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Troubleshooting continued Pilot does not stay lit — Troubleshooting thermocouple or thermopile and high limit control circuit Figure 10 1. Checking thermocouple or thermopile open system (Figure 10): a. Use an electronic multimeter, with leads fitted with alligator clips. Set meter scale to DC Millivolts. b. Unscrew thermocouple or thermopile fitting from gas valve. c.
Standing Pilot Boilers — Control Supplement Troubleshooting Part Number 550-110-032/0706 continued 21
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Troubleshooting 22 continued Part Number 550-110-032/0706
Standing Pilot Boilers — Control Supplement Troubleshooting Part Number 550-110-032/0706 continued 23
EG-30 thru 75 Series 4 and PEG-30 thru 65 Series 4 Replacement parts Only dampers listed below are approved for use on EG-30 thru 75 Series 4, and PEG-30 thru 55 Series 4, standing pilot ignition system boilers. Any other damper installed can cause severe personal injury or death.