User Documentation

Weidmüller Interface GmbH Co. KG; Klingenbergstraße 16, 32758 Detmold-Germany
WDK 4N
WDK 4N PE
550 V
- Rated voltage with LS 2.8 137 V
30 A / ΔT 40 K
38,6 K / 30 A
30 A / ΔT 40 K
0,2 mΩ
0,4 mΩ
0,4 mΩ
0,7 mΩ
4 mm² 4 mm²
0,13 - 6 mm²
0,13 - 6 mm²
0,13 - 6 mm²
0,13 - 6 mm²
0,13 - 4 mm²
0,13 - 4 mm²
26 - 10 AWG
26 - 10 AWG
0,13 - 1,5 m 0,13 - 1,5 mm²
0,5 - 1,0 Nm 0,5 - 1,0 Nm
8 mm 8 mm
440V
440V
275V
440V
440V
Max. voltage data with optional screen bus bar LS2.8: 137 V
- Rated voltage
Technical data according to IEC/EN 60079-7 (increased safety "eb"):
- Rated conductor cross section
- Conductor cross section flexible
- 2 conductors with same cross-section
- Tightening torque range, terminal screw
- cross section, American Wire Gauge
- Conductor cross section solid
- Stripping length
Application
Case
A - Continuous no difference between one or two cross connections
- Contact resistance top level
with rated conductor, 2,5 m
- Contact resistance top to lower
with rated conductor, 2,5 m
- Contact resistance lower level
with rated conductor, 2,5 m
- Conductor cross section stranded
- Rated current
IECEx / ATEX Terminal and Cross-Connector Arrangements:
Max voltage data with ZQV 4/... according to IEC/EN 60079-7 in conjunction with
protective earth terminal blocks of the WDK PE-Series, (increased safety "eb"):
- Rated current with ZQV
- Temperature rise with rated current
C - Adjacent – separated by an end plate no difference between one or two cross-connections
D - Intermediate - bridging one or more unconnected terminals (e.g. every 3rd terminal) no difference
between one or two cross connections
E - Next to a protective conductor terminal (earth)
F - Next to a protective conductor terminal (earth) separated no difference between one or two cross-
connections
Information for further cross-connector arrangements will be provided on request.
Version: WDK 4N V-WDK 4N PE 7556292 Index: 02 Date: 06.2019
2