Brochure/Catalogue

C
C.18 2028840000
Lightning and surge protection
for low voltage supply
Type I and II lightning arrester
Suitable with 25kA (10/350 µs) for protective level I, II,
III and IV (LPL I/II/III/IV)
Pluggable arrester
Tested according to IEC 61643-11 for Type I and II surge
protection
Can also be used as Type II surge protection
Field of application downstream of the main electrical
meter
Technical data
Rated voltage (AC)
Max. continuous voltage, Uc (AC)
Lightning test current Iimp (10/350 µs) [L-PE]
Discharge current I
n
(8/20µs) wire-PE
Discharge current I
max
(8/20µs) wire-PE
Requirements class, acc. to EN 61643-11
Short-circuit current rating I
SCCR
Leakage current at U
n
Rated load current I
L
Fuse
Temporary surge voltage (over-voltage) - TOV
Protection level with I
N
(L/N-PE)
Response time
Optical function display
Design
Colour
Ambient temperature (operational)
Storage temperature
Connection according to IEC 947-7-1
Solid
Stranded
Stripping length
Tightening torque
Approvals
Approvals
Standards
Dimensions / Signalling contact info
Clamping range (nominal / min. / max.) mm²
Height x width x depth mm
Signalling contact
Note
Ordering data
without remote signalling contact
with remote signalling contact (R)
Note
Accessories
Note
VPU I 3/R 400 V / 25 kA
TN-C
OK OK
CHANGE
U
CHANGE
U
OK
CHANGE
11 1412
U
PE (N)PE (N)
400 V
400 V
25 kA
25 kA
100 kA
T1, T2
25 kA
30 µA
100 A
250 A gL (if mains > 250 A)
620 V
≤ 1.9 kV
≤ 25 ns
green = OK; red = arrester is defective - replace
Installation housing; 6 TE, Insta IP 20
Black, Arrester red
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
CE; EAC; OEVE
IEC61643-11, EN61643-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
94 / 106.8 / 69 106 / 106.8 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 3 400V/25KA 1 1351870000
VPU I 3 R 400V/25KA 1 1351850000
Pluggable spare arrester VPU I 0 400 V/25 kA-1351790000
VPU I 1/R 400 V / 25 kA
1-phase
U
OK CHANGE
400 V
400 V
25 kA
25 kA
100 kA
T1, T2
25 kA
30 µA
100 A
250 A gL (if mains > 250 A)
620 V
≤ 1.9 kV
≤ 25 ns
green = OK; red = arrester is defective - replace
Installation housing; 2TE, Insta IP 20
Black, Arrester red
-40 °C...70 °C
-40 °C...80 °C
4...16 mm²
2.5...50 mm²
15 mm
2...3 Nm
CE; EAC; OEVE
IEC61643-11, EN61643-11
no remote sig. contact with remote signalling (R)
16 / 4 16 / 4
94 / 35.6 / 69 106 / 35.6 / 69
No 250 V 1A 1CO
Type Qty. Order No.
VPU I 1 400V/25KA 1 1351820000
VPU I 1 R 400V/25KA 1 1351800000
Pluggable spare arrester VPU I 0 400 V/25 kA-1351790000